INSTRUCTIONS FOR
SYSTEM DESIGN,
INSTALLATION
PREPARATION,
INSTALLATION, AND
MAINTENANCE
System designer, Installation
Technician, User
_
ADAPT MAX
ADAPT MAX System

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ADAPT MAX and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Kronoterm ADAPT MAX

  • Page 1 INSTRUCTIONS FOR SYSTEM DESIGN, INSTALLATION PREPARATION, INSTALLATION, AND MAINTENANCE System designer, Installation Technician, User ADAPT MAX ADAPT MAX System...
  • Page 2 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System ADAPT MAX 10035 1575 1575 ADAPT MAX 10070-10140 1575 ADAPT MAX 10035 EN 17-24-34-220102-02...
  • Page 3 • Low-pressure sensor (ADAPT MAX 10070-10140) • Temperature sensors • Compressor drive chokes INLET : R 6/4'' ET (ADAPT MAX 10035) / DN65 Victaulic (ADAPT MAX 10070-10140) Electrical cabinet with the heat pump regulator, communication and power supply terminal blocks...
  • Page 4 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System KRONOTERM INSTRUCTION SYSTEM This document is a part of the KRONOTERM instruction system, which follows our products’ lifecycle from design phase to service support. The installation instructions serve as the foundation for the professional installation and implementation of the KRONOTERM heat pump system.
  • Page 5: Table Of Contents

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System T A B L E O F C O N T E N T S IMPORTANT INFORMATION ......... 6 INTERNET CONNECTION ..........29 SYMBOLS ..................6 KT-2A CONTROLLER ............29 GENERAL WARNINGS ............
  • Page 6: Important Information

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 1.2. GENERAL WARNINGS IMPORTANT INFORMATION Heed the recommendations and WELCOME TO THE KRONOTERM FAMILY! requirements in these instructions to ensure the appliance’s proper operation. Improper These instructions support the planning...
  • Page 7: Safety Warnings And Instructions

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 1.3. SAFETY WARNINGS AND INSTRUCTIONS CAUTION DANGER Service and maintenance of the device can Do not clean or tamper with the device only be performed by an authorised service while it is in operation.
  • Page 8: Transport And Storage

    Transport and store the device in a dry place at a temperature of 4 to 45°C (50°C for 24 h). ADAPT MAX is delivered on a pallet. Use a forklift Keep the device in a place without any or a pallet truck for transportation.
  • Page 9: Handling The Packaging And End Of Life Device

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 1.5. HANDLING THE PACKAGING AND END OF LIFE DEVICE Dispose of the packaging in compliance with applicable regulations. Dispose of the device in accordance with applicable legislation on waste electrical and electronic equipment.
  • Page 10 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System EN 17-24-34-220102-02...
  • Page 11: Installation Planning

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System SYSTEM DESIGN INSTALLATION PLANNING OPTIONAL KT-2A / KT-1 NOTE KT-2A / KT-1 Choose the necessary heating and cooling capacity of KT-2A / KT-1 the heat pump based on the project's thermal needs.
  • Page 12: Connection Diagram In The

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 2.2. CONNECTION DIAGRAM IN THE UTILITY ROOM OPTIONAL KT-2A / KT-1 KT-2A / KT-1 KT-2A / KT-1 UTP 5e KT-2A / KT-1 UTP 5e UTP 5e KT-2A...
  • Page 13: Glycol Heat Exchanger

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 2.4. LOCATION REQUIREMENTS FOR Heating loop set – mixed THE HEAT PUMP Power Supply Cable WR KSM 2 NOTE WR KSM+ Temperature – DHW tank Ensure that the floor of the selected location has a...
  • Page 14 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 2.4.2. HEAT PUMP NOISE EMISSION BASED ON PLACEMENT NOTE The heat pump emits noise during operation. Im-proper placement can amplify noise. Consider the following recomendations when placing the heat pump.
  • Page 15 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System min 1000 min 1000 min 3000 min 3000 Figure 10: ADAPT MAX 10035 minimal functional clearances Figure 13: ADAPT MAX 10140 minimal functional clearances min 1000 min 3000...
  • Page 16: Safety Clearances

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 2.4.4. SAFETY CLEARANCES 2500 DANGER ADAPT MAX contains the R290 flammable refrigerant, which is heavier than air. Safety clearances encompass a space around the heat pump where no spatial features such as windows, shafts, holes, doors and other that could trap the refrigerant are allowed.
  • Page 17: Requirements For Installation Of Wall Control Unit

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 2.5. REQUIREMENTS FOR INSTALLATION OF WALL CONTROL UNIT CAUTION Heed required clearances during installation. NOTE 2500 2500 The room must be dry, humidity in the room must not exceed 60 %.
  • Page 18: Further Information

    [m3/h] drop of the [kPa ] pipe [mm] ADAPT MAX DN40 Ø40 52,7 10035 Figure 22: Minimum clearances WR KSM C and WR ADAPT MAX DN50 Ø51 50,8 KSM+ 10070 2.5.3. WR KSM MAX 10070-10140...
  • Page 19: Requirements For Utility Room

    Table 4: Thickness of pipe insulation [mm] ADAPT MAX 10035 40 mm CAUTION ADAPT MAX 10070 50 mm ADAPT MAX needs to be combined with a buffer tank ADAPT MAX 10105 65 mm suitable for heating and cooling (insulated with vapor ADAPT MAX 10140 65 mm barrier insulation).
  • Page 20 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 2.7.4. REQUIRED SAFETY ELEMENTS NOTE CAUTION For recommended buffer tanks, see the DATA SHEET. The following elements must be installed in the utility FURTHER INFORMATION room: Magnetic dirt separator of appropriate size - AVAILABLE DATA SHEET AS ADDITIONAL EQUIPMENT.
  • Page 21: Installation Preparation

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System INSTALLATION PREPARATION PREPARATION OF THE FOUNDA- TION AND PIPE CONNECTIONS ADAPT MAX can be installed in multiple ways, depending on the needs of each project. Table 7: Possible pipe connection ADAPT MAX...
  • Page 22: Concrete Foundation - Adapt Max 10035

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System FURTHER INFORMATION NOTE FOUNDATION PLAN FOR ADAPT For hydraulic connection of the heat pump to the MAX TPZ AM 10035 heating system, use pipes of appropriate dimensions.
  • Page 23: Structural Steel Foundation - Adapt Max 10035

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System FURTHER INFORMATION FURTHER INFORMATION FOUNDATION PLAN FOR ADAPT FOUNDATION PLAN FOR ADAPT MAX TNZ(AF) AM 10035 MAX TPZ-AF AM 10035 Frost depth Perforated drain pipe Drain outflow pipe Conduits for power and communication cables.
  • Page 24: Concrete Foundation - Adapt Max 10070-10140

    MIN R600 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 3.3. CONCRETE FOUNDATION - ADAPT MAX 10070-10140 W1 | W2 CAUTION Ensure the sufficient number of drains are prepared: - ADAPT MAX 10070 - 2...
  • Page 25 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System FURTHER INFORMATION FOUNDATION PLAN ADAPT MAX 10070 - above-ground pipe connection - TNZ(AF) AM 10070 FOUNDATION PLAN ADAPT MAX 10105 - above-ground pipe connection - TNZ(AF) AM 10105...
  • Page 26: Structural Steel Foundation - Adapt Max 10035 -10140

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM 4825 ADAPT MAX System ADAPT MAX 10140 3.4. STRUCTURAL STEEL FOUNDATION - ADAPT MAX 10035 -10140 538 698 1125 500 1125 698 538 6450 Figure 30: Dimensions and mounting positions for a...
  • Page 27: Utility Room Preparation

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System INSTALLATION, PREPARATION UTILITY ROOM PREPARATION 4.1. INSTALLATION OF TEMPERATURE SENSORS Figure 32: Installation of temperature sensors in the buffer tank EHSTDHW Figure 33: Installation of temperature sensor in the...
  • Page 28: Installation Of Magnetic Dirt Separator

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System ELECTRICAL CONNECTION 1/2'' connection PREPARATION 1/2'' sensor sleeve Sanitary cold water OPTIONAL Electric immersion heater KT-2A / KT-1 EHSTDHW Electric heater for DHW tank KT-2A / KT-1...
  • Page 29: Communication Connection

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System Table 8: Max electrical capacity, dimensions of fuses FURTHER INFORMATION and cables (installation method C) OUTDOOR TEMPERATURE SENSOR Electrical Fuse [A] Cable capacity [kW] [mm2] ADAPT MAX 16.4...
  • Page 30: Installation

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System INSTALLATION 6.1. REMOVAL OF PACKAGING ADAPT MAX is delivered on a pallet, protected by card- board and plastic film. TX30 TX30 TX20 TX30 TX30 TX20 Figure 37: Removal of packaging TX30 Figure 39: Removal of sides –...
  • Page 31: Removal From The Pallet

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 喨 TX 30 夊 90° 90° Figure 41: Removal from the pallet - ADAPT MAX 10070-10140 6.4. INSTALLATION ON THE Figure 43: ADAPT MAX 10070-10140 – Installation on FOUNDATION AND LEVELING the foundation and leveling.
  • Page 32: Removal Of The Transport Protection

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System Figure 46: Removal of transport protection for ADAPT MAX 10035. Figure 45: ADAPT MAX 10070-10140 - installation of condensate drain tube into the foundation drain pipe. 6.6. REMOVAL OF THE TRANSPORT...
  • Page 33: Pipe Connection

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System PIPE CONNECTION Coupling WIPEX PN6 50X4,6-G1 1/4'' (1018331) Elbow WIPEX PN6 G1 1/4'' - G1 1/4'' (1018351) 7.1. ADAPT MAX 10035 - UNDERGROUND CONNECTION Adapter G1 1/4'' - G1 1/4'' - 85...
  • Page 34: Adapt Max 10070 - Adapt Max 10140 Underground Pipe Connection

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 7.3. ADAPT MAX 10070 - ADAPT MAX 7.4. ADAPT MAX 10070 - ADAPT MAX 10140 UNDERGROUND PIPE 10140 ABOVE-GROUND PIPE CONNECTION CONNECTION W1/W2 Figure 51: ADAPT MAX 10070-10140 – underground...
  • Page 35: Electrical Connection

    OF THE DEVICE. ADAPT MAX 10035 & ADAPT MAX 10070: Connect the device to the electrical supply, which is protected by a type B or B+, 30mA RCD switch. (ADAPT MAX 10035 – 10070). 8.1. POWER SUPPLY CONNECTION Connect the electrical power supply cable as shown in the pictures below.
  • Page 36: Connection Of Communication

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 8.2. CONNECTION OF COMMUNICATION FILLING THE SYSTEM 9.1. REQUIREMENTS FOR WATER 8.2.1. ADAPT MAX 10035 QUALITY CAUTION See table 10 for heating system water quality R290 R290...
  • Page 37: Filling Process

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 10 SYSTEM COMMISSIONING NOTE For installations in Switzerland ensure that the heating CAUTION system water is in accordance with SWKI BT 102-01. Commissioning may only be carried out by suitably 9.2.
  • Page 38 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System EN 17-24-34-220102-02...
  • Page 39: Maintenance

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System MAINTENANCE MAINTENANCE DANGER 11.1. HEAT PUMP MAINTENANCE If a leakage of refrigerant is found that requires brazing, all refrigerant must be recovered from the system. The removal process for refrigerant is explained later in the CAUTION manual.
  • Page 40: Handling Of Refrigerant

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 11.2. HANDLING OF REFRIGERANT 1x A YEAR we recommend inspecting the heat pump: 11.2.1. REMOVAL OF REFRIGERANT INSPECT CHECK ESPECIALLY ENTIRE DEVICE General inspection, ✓ ✓ DANGER...
  • Page 41: Heating System Maintenance

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 11.2.3. RECOVERY 11.3. HEATING SYSTEM MAINTENANCE In addition to a quality system and good implementa- DANGER tion, the correct use of the system is crucial. Only in this...
  • Page 42: Technical Data

    Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System 12 TECHNICAL DATA Unit ADAPT 10035 ADAPT 10070 ADAPT 10105 ADAPT 10140 DEVICE DEDICATED INDOOR UNIT WR KSM 2, WR KSM C, WR KSM 2, WR KSM C,...
  • Page 43 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System Unit ADAPT 10035 ADAPT 10070 ADAPT 10105 ADAPT 10140 DEVICE SEASONAL ENERGY EFFICIENCY FOR HEATING ACCORDING TO DIRECTIVE (EU) 811/2013 – DATA SHEET °C Temperature mode 35/55...
  • Page 44 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System Unit ADAPT 10035 ADAPT 10070 ADAPT 10105 ADAPT 10140 DEVICE ELECTRICAL DATA* ELECTRICAL DATA v/Hz Rated voltage 3N~ 400; 50 3N~ 400; 50 3N~ 400; 50 3N~ 400; 50 Max.
  • Page 45 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System WR KSM 2 WR KSM+ WR KSM C DEVICE ELECTRICAL DATA * ~ 230; 50 ~ 230; 50 ~ 230; 50 Rated voltage; Frequency V/Hz Max. operating current Max.
  • Page 46 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System Unit ADAPT 10035 ADAPT 10070 ADAPT 10105 ADAPT 10140 DEVICE SOUND ACCORDING TO EN 12102 AT THE CONDITION OF A7W35 THE DECLARED SOUND POWER ON THE ECOLABEL ENERGY LABEL...
  • Page 47 Instructions For System Design, Installation Preparation, Installation, and Maintenance KRONOTERM ADAPT MAX System EN 17-24-34-220102-02...
  • Page 48 KRONOTERM d.o.o. Trnava 5e, 3303 Gomilsko, SLO T +386 3 703 16 20 www.kronoterm.com info@kronoterm.com...