1 WARNINGS AND SAFETY DEVICES he boilers b case, contact the Technical Assistance Centre or professionally We pay attention to every single component of t uilt in our plants, to protect users and installers from any risk of inju- qualified personnel ry. After working on the product, qualified personnel must always If the boiler is not used for a long time, you are advised to carry out carefully check the electrical wiring, in particular the stripped part...
2 DESCRIPTION OF THE APPLIANCE HEATING COLD DELIVERY WATER HEATING RETURN WATER Water gauge 11 High modulation mixer 20 Return probe Drain valve 12 Main heat exchanger 21 Gas baffle 3-way electric valve 13 Flame detection electrode (conden- 22 Gas valve Pressure transducer sate/ignition sensor) 23 DHW probe...
Meteo X Meteo X Parametro Simbolo Unità Classe di efficienza energetica stagionale del riscaldamento d’ambiente Classe di efficienza energetica di riscaldamento dell’acqua Potenza nominale Pnominale Efficienza energetica stagionale del riscaldamento d’ambiente ηs Potenza termica utile Alla potenza termica nominale e a un regime di alta temperatura (*) 19,5 24,4 Al 30% della potenza termica nominale e a un regime di bassa temperatura(**) Efficienza Alla potenza termica nominale e a un regime di alta temperatura (*) η4...
Circulator residual discharge head The boiler is fitted with a high-efficiency modulating circulator already hydraulically and electrically connected. The relative usable perfor- mance values are shown in the chart. The modulation is managed by the board via the PUMP DUTY CY- CLE parameter (INSTALLER access level). This value defines the boiler pump management mode: [41÷100] = proportional operation The boiler has an anti-lockout system that launches an operating cy- cle after 24 hours of stoppage in any operating status.
Multi-row wiring diagram ITRF05 V Hv marrone nero (-) bianco (sign.) nero (-) C.S.A. bianco (sign.) rosso (alim.) rosso (alim.) 230 V VALVOLA GAS blu (-) F= 3.15A F marrone (+) marrone rosa R FS R FS T.AG. NOTA : LA POLARIZZAZIONE L-N E' CONSIGLIATA Elettrodo A/R ACC1 F1=4A T...
Page 10
rosso (+24 Vdc) giallo (B) arancione (A) nero (-) CE4 (connettore estraibile posizionato sotto mensola) Collegamenti a cura dell'installatore - A B + bianco (TBT) bianco (TBT) arancione (SE) arancione (SE) rosa (OT+) rosa (OT+) nero (TA) nero (TA) CE8 (connettore estraibile posizionato sotto mensola) F.S.
Page 11
ACCESSORIES L-N anti-freeze heaters (low temperature thermostat) (room thermostat) (outdoor temperature sensor) Dir/mix zone control Hybrid modules Remote access to alarms Zone valve or supplementary pump AKJ02 … Control board ITRF05 Interface board (semi-automatic loading) Remote control panel BE18 Power supply unit X1-X25 Connectors (X2–X21 accessories) ACC1...
Control panel Boiler control panel REC10EXPH-N Confirm IMPIANTO 18/05/2021 12:17 back= return to the previous screen 1.3 bar MENU STATO cancel selection return to the main screen (press > 2 sec.) °C - On the main screen, used to choose from: INFO MENU, INFO, SET, STATUS, SYSTEM TEMPERATURA SANITARIO...
Page 13
Below there is a summary of the MENU tree structure of the REC10EXPH-N. Some of the information might not be available on the REC10EXPH-N depending on the access level, machine status or system configuration. This manual explains the operation of the boiler with the REC- Scan the QR CODE to access the Programming manual for 10EXPH-N machine interface.
Page 14
Default value Minimum Maximum Access level set in the factory value value MENU AGGIUNGI ZONA INSTALLER CANCELLA ZONA INSTALLER TARATURA SENSORE 0.0°C - 6.0°C 6.0°C INSTALLER RESET SISTEMA INSTALLER PARAMETRI INSTALLER SPENTO RISCALDAMENTO 3 min 0 min 20 min INSTALLER IST ON ALTA TEMP 5°C 2°C...
Page 15
Default value Minimum Maximum Access level set in the factory value value MENU INSTALLER: if EXT PROBE TIPO EDIFICIO 5 min 5 min 20 min connected INSTALLER: if EXT PROBE REATTIVITA’ SEXT connected ATTIVA/DISATTIVA CURVE RISC. INSTALLER INSTALLER: if HP is fi tted and ATTIVA/DISATTIVA CURVE RAFFR.
Page 16
Default value Minimum Maximum Access level set in the factory value value MENU ATTIVA/DISATTIVA RID NOTTURNA FUNCTION DISABLED FUNCTION ACTIVE FUNCTION DISABLED INSTALLER INSTALLER: if NIGHT-TIME FREQUENZA RIDOTTA 100% RID ACTIVE INSTALLER: if NIGHT-TIME INIZIO RID NOTTURNA 20:00 00:00 23:59 RID ACTIVE INSTALLER: if NIGHT-TIME FINE RID NOTTURNA...
Info UP button Boiler control panel REC10EXPH-N CONFIRM Confirm IMPIANTO 18/05/2021 12:17 1.3 bar MENU STATO back= return to the previous screen cancel selection °C return to the main screen (press > 2 sec.) INFO TEMPERATURA SANITARIO - On the main screen, used to choose from: MENU, INFO, SET, STATUS, SYSTEM - In the sub-menus, used to navigate the various ANNUL button...
3 INSTALLATION Indoor installation Outdoor installation in a partially protected place Cleaning the system and characteristics of the water In the case of a new installation or replacement of the boiler, it is nec- essary to clean out the heating system. To ensure the device works well, after every cleaning intervention or addition of additives and/or chemical treatments (e.g.
Positioning the wall-hung boiler and making MINIMUM CLEARANCES the hydraulic connections Access the inside of the boiler for routine maintenance tasks, re- specting the minimum installation clearances. When positioning the appliance, bear in mind that: − it must be installed on a wall that can support its weight −...
You are advised to use wires with a section between 0.35mm and 1.5mm . For the BUS 485 connection, it is recommended to use the shielded cable if the signal passes near other electric wires or mains voltage wires (230V). In the case of a TA or TBT connection, remove the relative jump- ers on the terminal board.
(see the Beretta IT is therefore CRUCIAL to reposition the components correctly catalogue).
Page 22
B23P-B53P Ø60-100 Ø80-80 Ø80-125 B23P-B53P Ø60-100 Ø80-125 Ø80-80 For the length of the flue gas discharge pipes, refer to the table below: Maximum length (m) Pressure drops (m) Diameter Wall hole Type of pipe (Ø - mm) (Ø - mm) 25C100 30C100 bend 45° bend 90° vertical coupling with Ø 60-100 to Ø 80 horiz horiz 4.85...
Twin pipes Ø80 with ducting Ø50 - Ø60 - Ø80 camino per Thanks to the boiler characteristics, a Ø80 flue gas discharge pipe intubamento Ø 50 mm - Ø 60 mm - Ø 80 mm can be connected to the Ø50 - Ø60 - Ø80 ducting ranges. For the pipe, you are advised to make a project calculation in order to respect the relevant regulations in force.
company's logo the first system filling operation must be carried out using the filler tap (B) with the boiler OFF. See applicable legislation for the discharge of the combustion prod- NOTE: every time the boiler is powered up, the automatic venting ucts as well as local regulations. cycle is run. The flue gas pipe must be carefully chosen on the basis of the fol- NOTE: the presence of a water alarm (40, 41 or 42) does not allow lowing parameters: the venting cycle to be carried out.
4 COMMISSIONING ORA E DATA Preliminary checks IMPOSTA ORA E DATA The first ignition is made by the experienced personnel of an author- ised Technical Assistance Centre. Before starting up the boiler, check: 09 / 04 / 2021 − that the data of the supply networks (electricity, water, gas) corre- spond to the label data USA LE FRECCE PER MODIFICA −...
set, along with the FORCED HEATING OFF TIME. The factory value DO_AUX1: this value configures the functions associated with the is FUNCTION NOT ACTIVE. To reset the times, select FUNCTION digital output used to manage the supplementary pump and the zone ACTIVE and confirm.
Page 27
− Programming timing enabled = 1 When the room thermostat contact closes the heat request is ena- MENU bled according to the programming timing. NOTE: In this case make sure that the operating mode of the zone is IMPOSTAZIONI set to AUTO in the STATUS menu. 4.3.3 Timed program function BIBERON...
Page 28
CHOOSING THE COMPENSATION CURVE range [-5 - +5]. The compensation curve for heating maintains a theoretical tem- RIDUZIONE NOTTURNA PARALLELA perature of 20°C indoors, when the outdoor temperature is between +20°C and -20°C. The choice of the curve depends on the minimum outdoor temperature envisaged (and therefore on the geographical location), and on the delivery temperature envisaged (and therefore Curva climatica GIORNO on the type of system).
Membrane control interface To ensure correct operation, check the assembly surface (the wall) is flat. The boiler has a membrane control interface that uses LEDs to indi- - Pass the wire through the lower casing (B, fig. 4). cate the boiler operating status: - Take the control panel and detach the connector by slightly - green = normal operation bending the lower tab (fig.2).
The recommended length for the connection between the con- CALDAIA trol panel and the boiler is ≤30 m. The connection cable between the control panel and the boiler ESTATE should not have any joints; if these are required, they should be tinned and suitably protected. INVERNO Any ducting of the connection cable must be separated from live cables (230V AC).
4.10 Boiler start-up INFO menu from the main page of the REC10EXPH-N, you can see the SCREED HEATER FUNC HRS value, which shows the If a room thermostat or timer is installed, or if the REC10EXPH-N MAS- TER is set as an ambient regulator, the device in question must be ON number of hours since the activation of the function.
the indications in the table. If it doesn't, calibrate the gas valve - residue will have evaporated and you can: see paragraph “4.16 Adjustments” − make the combustion check CALDAIA METHANE PROPANE AIR LIQUID GAS GAS (G20) (G230) (G31) 25C100 10.0 10.0 ESTATE...
− use the arrows to visualise the parameter required - see table - minimum fan speed maximum fan speed Maximum output slow ignition adjustment screw Minimum output MAX CH maximum fan speed - heating adjustment screw RESTART reignition speed access the sub-menu by pressing OK ...
RANGE RATED 5100 E041 TRASDUTTORE ACQUA PREMERE OK/ENTER PER RIEMPIRE L’IMPIANTO − once the required output (maximum heating) has been set, indi- During the loading phase the scrolling message “SEMI-AUTOMATIC cate the value on the self-adhesive label supplied. For subsequent FILLING IN PROGRESS”...
Signal code Signal description Red LED Green LED OT+ signal o o o fl ashes fl ashes Vent cycle 0.5 ON - 1.0 OFF 0.5 ON - 1.0 OFF Screed heater fl ashes STOP 0.5 ON - 0.5 OFF CALL FOR SERVICE fl ashes E020...
4.21 INFO By pressing the INFO button on the REC10EXPH-N display (firm- ware revision 2.17), you can see a list of information relating to sys- 1 - 10:30 18/11/2020 tem operation. Press the up and down buttons to switch between E030 parameters.
Reprogram the boiler, carrying out the operations explained in para- REC10REXPH-N Rxx.xx graph “4.3 Programming the boiler” . 4.27 Boiler configuration The BOILER menu is used to modify the hydraulic configuration with- out necessarily having to make a SYSTEM RESET. The HYDRAULIC CONF parameter can assume values of between 0 PREMERE UN TASTO and 4 with the following meaning: PER CONTINUARE...
Page 38
− removing any oxidation from the burner − Vacuum out any dirt residue inside the heat exchanger, taking care − removing any scale from the heat exchangers NOT to damage the retarder insulating panel. − checking the electrode − Clean the coils of the heat exchanger with a soft bristled brush. −...
Page 39
sive as its geometric form ensures perfect coupling with the heat exchanger flange. − Refit the ignition/detection electrode using the screws removed previously, and replacing the relative sealing gasket. Cleaning the siphon − Disconnect the pipes (A) and (B), take out the clip (C) and remove ignition/ flame detection elec- the drain-trap.
Page 40
[EN] - RANGE RATED - EN15502-1 The calibration value of the heat output in heating mode is ___________ kW equivalent at a maximum fan speed of _____________ rpm in heating mode Date ____/____/____ Signature ____________________________________________ Boiler serial number ___________________________________ Via Risorgimento, 23 A 23900 - Lecco, Italy www.berettaclima.it The manufacturer strives to continuously improve all products.