Teknim Intelligent Addressable Panels. TFP-12xx Teknim Intelligent Addressable panels can be handled within three optional categories as those supporting 1, 2 or 4 loops. Up to 240 devices can be employed per loop in TFP-12xx series panels and all these devices operate through Teknim Flashlink protocol.
Configuration Software. In addition to this, panel access through internet connection, and monitoring facility through the Teknim Fire Detection System Monitoring Software are also provided. The Teknim Addressable Fire Detection System Configuration Software provides technical teams with ease of use for the configuration process.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels - Panel User Interface This chapter describes the indicators and buttons on the panel. Figure 1 : Control Panel User Interface The letters displayed in the Figure 1 : Control Panel User Interface are respectively listed below. Table 1 : User Interface Button Functionality Label Function...
Page 10
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Table 2 : LED Indicators Label Name of LED LED - Permanent Light LED - Blinking Light Color Indicates that the panel is in FIRE alarm status (250 ms) Indicates that the system is Energy being supplied from any Green...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels - Installation This section describes the mechanical and electrical connection techniques of TFP-12xx series panels. Caution: Do not start installation until you have read all of this entire manual! - Recommended Cables It is recommended to employ the cables specified in the "Table 3: Recommended Cable Specifications" for wiring installations and all electrical connections.
In case of any blackouts, the external supply output is supplied until the battery reaches the cutoff voltage. - Loop Expansion Card Connection TFP-12xx Teknim Intelligent Addressable panels support 2 or 4 loops. In order to add a new loop card to a single loop panel;...
The connection form of the loop line and devices (Class A) is shown in “10.2 Appendix-Electrical / Figure 42 : Loop Connection”. The unused loop line must be deactivated through the panel or using the "Teknim Loop Configuration" software. If there is no connection made to the loop, the panel will issue a "Loop X Open Circuit" error.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels - Configuration This section contains information on the configuration and use of the fire detection system. - Panel Activation Activation is a process that enables access to the programming menu for the first installation of the addressable fire detection system.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 6.2.3 - Level 3 All the authorizations and functionality with regard to the system (except scenario management) are made available at this level. Users of this level are authorized persons trained to install and maintain the system. In order to switch to Level-3, it is necessary to have Level-3 password in the first place.
Establish the connection with the computer as shown in “10.4 Appendix-Level / Figure 44 : PC Ethernet Connection” and run the "Teknim Addressable Fire Detection System Configuration Software". Teknim recommends the use of "Teknim Addressable Fire Detection System Configuration Software" in order to get the best result for the installation of fire system.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 3 : Manually entered IP Settings If it is connected directly to a computer, it is enough to fill in the “IP” information. The “Subnet mask, Gateway, DNS” information should be entered as “0”. However, if the panel is to be connected to an external IP system such as AHM or Cloud over a network, information such as “Subnet mask, Gateway, DNS”...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Follow the guidelines below to change the default values: First, enter the main screen. Select “Menu » Programming » ”Network Settings” » “ARC Settings”. Navigate the forms with the arrow keys, Go to the form to be changed and press "OK", Use arrow keys to enter a new value and press the "OK"...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Test Status Settings Play Siren Play Buzzer Delays General Delay General Delay Closed Delay Mode Automatic Delay Time Zone Based delay Zone Delay Zonel Although addressable devices are connected to the loop line, there is no device added in the memory of a newly installed panel.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 6.4.2 - Login to Level-3 System administrator is required to first login to Level 3 in order to make configuration settings. For the procedure for login to Level-3, refer to the topic “Level 3”. 6.4.3 - Panel Time Settings The proper setting of the panel clock and date ensures real-time traceability of the panel.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 8 : Date and Day/Night Setting 6.4.5 - Panel Parameter Settings It is necessary to set the values shown in “Table 6 : Default Panel Parameters” after completing the time and date setting.
Page 22
TFP-12xx Series Intelligent Addressable Fire Alarm Panels * Language Setting To change the language option, go to the "Language" form and press the "OK" key. Language options: • Turkish • French • Dutch • Romanian • English • Italian • Lithuanian Select one of the language options and press "OK"...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels * Zone Start Address Each panel can be divided into 72 zones within itself. The zone start address can be used as a distinguishing feature in order to avoid confusion regarding the zone addresses between the panels, especially in networked systems. Addresses can be selected as 1, 73, 145, 217, etc..
Configuration through Panel ”. How to add the devices which have been addressed and connected to the loop line, to the system will be told under this heading. Teknim TFP-12xx series panels can do the procedure for adding devices very simply and quickly. For addition of new devices, refer to “7.9.4. Add Device”.
Page 25
TFP-12xx Series Intelligent Addressable Fire Alarm Panels * Day/Night Sensitivity In day and night modes, it may be desirable to change the fire detection sensitivities of the detectors. For this reason, nighttime and daytime sensitivity can be adjusted separately. For this: Select "Night"...
Page 26
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Latching : The change in status (input or error value) in the input module is evaluated once transmitted to the panel. The input values are not changed, even though a new situation occurs, until a reset command is delivered.
Page 27
TFP-12xx Series Intelligent Addressable Fire Alarm Panels * Flash Level Flash level is the parameter valid only for the addressable fire alarm flasher and the addressable fire alarm flasher siren. Under this menu, the brightness of the flash can be adjusted by selecting the flash intensity selection "Down, Normal, Bright".
Page 28
TFP-12xx Series Intelligent Addressable Fire Alarm Panels General Alarm : In case of any alarm or in case of evacuation, output modules are pulled. It will not restore until the "Reset" key is pressed. General Siren : In case of any alarm or in case of any evacuation, output modules are pulled immediately if there is not delay time, and at the end of the delay time, if there is any delay time.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels The default current values are as follows: Table 14 : Default Conventional Module Current Values Current Value Normal Circuit 4 mA Short Circuit 50 mA Alarm 20 mA 6.4.10 - Zone Parameters Apart from device parameters, there are zone labels and disabled parameters related to zones. Under this heading, the zonal parameters and their associated meanings will be discussed.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 12 : Smoke Alarm Warning Message For more detailed definition about the fire, a fire is selected from the fire list with the "UP" and "DOWN" keys and the definitions of these spaces can be reached together with the loop address, zone address and locale address of the fire by pressing the "OK"...
Page 31
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 15 : Error Detail Window The types of errors that may occur are listed below: No Battery It is stated that there is no battery under 2V. "No battery" is displayed on the error screen. The event is saved as "No battery"...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 16 Device [x] General Error "General Error" will be displayed on the screen when an input is detected if activation type is selected as "Error" for the input modules. 17 Device [x] Dirtiness There is dirt on the smoke detector.
Page 33
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 17 : Warning Details Window The warning window is used to notify the system user of the existence of the data listed below. • Disabled devices • Disabled zones • Disabled outputs •...
- Event Log The event log is the section where situations that are important to the Teknim addressable panel are recorded and displayed. In the event log, records are divided into 10 categories and each category is evaluated with different events within itself.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 18 : Sample Event Memory Window - Disable Menu Disable menu is used to put devices, zones, siren outputs and loop lines into the "Disabled" state. 7.3.1 - Disabled Devices Deactivated devices continue to communicate with the panel, but do not participate in the process of a fire situation. The fire detection process continues when the disabled state is removed from the device.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 20 : Disabled Zones 7.3.3 - Disabled Sirens Deactivated siren outputs will not be active in case of any fire and scenario situations. However, siren outputs will be continuously monitored for short-circuit and open-circuit conditions. •...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 22 : Loop Parameters - Zone Test Zone testing is a feature that is used to test the alarm functions of fire detection devices. In cases where the settings depicted under topics of the “6.4. Sirens Under Testing” and “6.4. Buzzer under Testing” are fulfilled, sirens or buzzer sounds for 10 seconds for the zone positioned within the scope of every test alarm and thereafter the system resets.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels - Displaying Technical Service Contact Information Technical service contact information can be used to notify events that are outside the intervention of a level 2 user when an emergency occurs. Contact information can only be accessed by level 2 users. This information consists of executive name, company name, company address/web address and telephone number.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 25 : Addition of New Devices You should re-enter the "Add Device" menu and check whether a new device is added or not in order to make sure that the process is completed properly. You can visit the "Device List"...
TdNET is a multi-master protocol and communication technology that works with Token-Passing topology that provides the network infrastructure of Teknim addressable fire detection systems. A network is created with up to 16 devices supporting the TdNET protocol. In order to connect the TFP-12xx panels to the network line, the TFC-1208 TdNET Network Card must be integrated through the P2 port on the motherboard.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 7.10.2 - TdNET Parameters The general settings of the panel for TdNET are made with the TdNET parameters menu. All parameters included in this menu are reviewed in detail below. TdNET Mode Independent: Default value. The panel will not send any messages to the network line. It does not evaluate any messages coming through the network.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 7.10.4 - Outgoing Commands All panels operating in the Station and Main panel mode will continuously transmit "Alarm", "Error" and "Warning" information to the network line as default. In addition to this, they transmit "Reset", "Buzzer Muted", "Siren Muted", "Evacuation"...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 31 : User Programming Window 7.11.1 - Permissions Permissions menu is only available for level 2 users under the "User Programming" window. When a user other than the 2nd level user enters the "User Programming" window, they cannot display the "Permissions" line. The selection of which menus 2nd level users will have access to and which buttons they can use can be made under this menu.
Then press the "Connect" button Select the latest firmware version you downloaded from Teknim website by pressing the Browse button. All hardware to be updated will be selected in the list of devices. You can optionally deselect hardware that you do not want to be updated.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels WARNING! Do not attempt to repair the device on your own. You may be subjected to electrical shock when you open the cover of the device. In case of any malfunctions, contact your dealer or authorized service agency. Technical interventions in the device should be carried out only by the qualified and authorized service personnel.
TFP-12xx Series Intelligent Addressable Fire Alarm Panels - Appendices Appendices are divided into 4 categories as Mechanical, Electrical, Menu and Level. 10.1 - Appendix-Mechanical Figure 34 : Panel Front Cover Screws TFP-12XX INSTALLATION & USER MANUAL...
Page 47
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 35 : Mounting Screw Holes TFP-12XX INSTALLATION & USER MANUAL...
Page 48
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 36 : Electrical Connections • A3 detail is 195~250 VAC 50 Hz input connector. • A4 detail shows the battery connection (batt) and main card power connection socket. • A5 detail shows the battery start switch in cases where 195~250 VAC 50 Hz is not present.
Page 49
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 37 : Battery Connection Battery Battery 2X12V 7A Battery Connection Diagram • Battery brackets marked with B1 are fixed through the screw locations • B3 and B5 are connected with battery jumper cable •...
Page 50
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 38 : Loop Card, Network Card and Repeater Panel Connection Points TFP-12XX INSTALLATION & USER MANUAL...
Page 51
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 39 : TFC-1201 Network Card Card TFP-12XX INSTALLATION & USER MANUAL...
Page 52
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Figure 40 : TFC-1201 Loop TFP-12XX INSTALLATION & USER MANUAL...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 10.3 - Appendix – Menu Table 17 : Level 1 Menu Flow 01.Logs Log Page Log Page 2 … Main Menu Log Page N 02.Enter Table 18 : Level 2 Menu Flow 01.Logs Log Page Log Page 2 …...
Page 56
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Table 19 : Level 3 Menu Flow 01.Logs Log Page Log Page 2 … Log Page N 02. Settings Mode: Auto/Night/Day General Delay: ON / OFF 03.Time Set Time 04.Contact Info Address, Company Name, Phone number, e-mail 05.Disablements 01.Devices Disablement...
Page 57
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 03.Delays 01.General Delay Delay Mode: Always/Night/Day Time: NN:NN General Delay : ON/OFF 02.Zone Based Delay Zone: [0-72] Delay: GENERAL/ZONAL time : 00:00 04.Panel Status Power: xx.x VDC Bat. : zz.z VDC Temp. : aa C SYST.: yy.y VDC SNDR.1: bb.b VDC SNDR .2: bb.b VDC...
Page 58
TFP-12xx Series Intelligent Addressable Fire Alarm Panels In New Zone Alarm Re-sound In Case Of Gas Alarm Plat Siren Play Siren In Case of Test Parameters Play Buzzer Date & Day/Night Setting Date: XX/XX/XXXX Day/Night : XX/XX/XXXX Monday: XX:XX, YY:YY Tuesday: XX:XX, YY:YY Wednesday:...
Page 59
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Add Device XXX New Device Remove Device XXX Loss Devices Loop Parameters Active: Yes/No Disablement: Yes/No Label: [Loop XX] Class: Class A / Class B 08.TdNET Functions TdNET Map Panel 1-16: ENAB./DIS. TdNET Parameters TdNET Mode: Station / Main Panel / Standalone...
Page 60
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 09.Network Settings IP Settings Automatic IP: ENAB./DIS. Subnet Mask Gateway Command Port Port Setting ARC Settings Active: ENAB./DIS. Subscriber Code Port Protocol Remote Connection Active: ENAB./DIS. Port 10.Users Users State: ENAB./DIS. Label : Label Level : 1/2/3 Users N Password : ****...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 10.4 - Appendix – PC Connection Figure 44 : PC Ethernet Connection TFP-12XX INSTALLATION & USER MANUAL...
Alarm counter Error signals from points Disabled status of addressable points Test status 1922 Teknim Elektronik San. ve Tic. A.Ş. Dudullu Organize Sanayi Bölgesi 1.Cadde İsmet Tarman İş Merkezi No:1 Daire:32 Ümraniye-İSTANBUL 1922-CPR-0876 1922-CPR-1079 EN 54-2:1997, EN 54-2:1997/A1:2006, EN 54-2:1997, EN 54-2:1997/AC:1999,...
TFP-12xx Series Intelligent Addressable Fire Alarm Panels 10.6 - Appendix - Maintenance Table Date Tested Device Device Location Explanation TFP-12XX INSTALLATION & USER MANUAL...
Page 64
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Date Tested Device Device Location Explanation TFP-12XX INSTALLATION & USER MANUAL...
Page 65
TFP-12xx Series Intelligent Addressable Fire Alarm Panels Date Tested Device Device Location Explanation TFP-12XX INSTALLATION & USER MANUAL...
Malfunctions arising due to improper handling are outside the scope of warranty. MANUFACTURER and SERVICE Teknim Elektronik Sanayi ve Ticaret A.Ş. Dudullu Organize Sanayi Bölgesi 1.Cadde İsmet Tarman İş Merkezi No:1 Daire:32 Ümraniye-İSTANBUL Telephone: +90 216 455 88 46 Fax: +90 216 455 99 06 www.teknim.com...