NIVELCO NIVOTRACK M-500 User And Programming Manual

Two-wire magneto strictive level transmitters

Advertisement

Quick Links

mba505en1910p
1 / 40

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NIVOTRACK M-500 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for NIVELCO NIVOTRACK M-500

  • Page 1 mba505en1910p ♦ 1 / 40...
  • Page 2 APPROVALS Reference document number FM Canada, Certificate No.:FM16CA0037X mba5052a0600s_01 FM US, Certificate No.:FM16US0068X mba5052a0600s_01 BKI ATEX, Certificate No.:BKI16ATEX0012X/2 mba5052m0600p_10 BKI IECEx, Certificate No.:IECEx BKI 12.0002 issue No.:1 mba5052a0600p_10 Ex Russia, Certificate No.:RU C-HU.MF62.B.04454 mba5052o0600p_03 Metrology OIML-R85, Certificate No.:TH-8592/3/2010 Metrology Romania, Certificate No.:9772/29.10.2013 2 / 40 ♦...
  • Page 3 BASIC CONCEPT OF MEASUREMENT WITH NIVOTRACK 100%, 20 mA (P11) Programmed measurement range 0%, 4 mA (P10) LEVEL = L – DIST + P04 mba505en1910p ♦ 3 / 40...
  • Page 4 4 / 40 ♦ mba505en1910p...
  • Page 5: Table Of Contents

    TABLE OF CONTENTS 1. INTRODUCTION ..................7 5.3.1.5 Installation mode (ONLY USD (UpSide Down) – „Reverse installation position” devices) ..............27 2. ORDER CODE ..................8 5.3.2. Analogue Output ..................28 2.1. D ...................10 IMENSIONS 5.3.2.1 Output current mode ................28 3. TECHNICAL DATA................12 5.3.2.2 Output current value 4 mA ..............
  • Page 6 6 / 40 ♦ mba505en1910p...
  • Page 7: Introduction

    Thank you for choosing a NIVELCO instrument. We are sure that you will be satisfied throughout its use! 1. INTRODUCTION Application Operating principle NIVOTRACK M–500 / 600 series working on the magnetostrictive principle The magnetostrictive transmitter is using the special feature of the are suitable for high accuracy level measurement of storage tanks.
  • Page 8: Order Code

    2. ORDER CODE NIVOTRACK – – ROBE OUSING OMINAL LENGTH UTPUT ROCESS ONNECTION Transmitter Tube 1" BSP Aluminum 4…20 mA / 0.1 mm Transmitter + display Tube 2" BSP Plastic 0.1 m 4…20 mA / 1 mm Tube 1" NPT 0.2 m 4…20 mA + HART / 0.1 mm...
  • Page 9 CCESSORIES TO BE ORDERED : M F T – – LANGES IMENSION TANDARDS ATERIAL RESSURE NNER DESIGN DIN ANSI DIN / carbon steel DN65 2½" PN16 / 150 psi 1" BSP DIN / 1.4571 DN80 3" PN25 / 300 psi 2"...
  • Page 10: Dimensions

    2.1. D IMENSIONS IGID TUBE TRANSMITTER LEXIBLE TUBE TRANSMITTER WITH THREADED PROCESS CONNECTION WITH SLIDING SLEEVE PROCESS CONNECTION MA, MC, MD, MG MK, MN 10 / 40 ♦ mba505en1910p...
  • Page 11 IGID TUBE TRANSMITTER LASTIC COATED IGID TUBE TRANSMITTER IGID TUBE TRANSMITTER WITHOUT PROCESS CONNECTION WITHOUT PROCESS CONNECTION WITH THREADED PROCESS CONNECTION MTU, MBU MEU, MGU MM, MC mba505en1910p ♦ 11 / 40...
  • Page 12: Technical Data

    3. TECHNICAL DATA IGID TUBE VERSION PLASTIC-COATED LEXIBLE TUBE VERSION IGID VERSION TYPE MA, MC, MD, MK, MN MEU, MGU MG, MTU, MBU, MM, MC, Measured process values Level; distance, volume Nominal length (L) 0.5…4.5 m [1…14 ft] (MM and MC max. 1.5 m [4 ft]) 2…15 m [6…49 ft] 0.5…3 m [1…9 ft] Material of the probe...
  • Page 13: Measurement Data

    3.1. M (MSZ EN 60770-1:2011, MSZ EN 61298-1:2009, MSZ EN 61298-3:2009): EASUREMENT DATA M––2 M––1, M––A M––4 M–-3, M––B M––6 M–-5, M––C M––8 M–-7, M––D Resolution (of the displayed and the transmitted 1 mm 0.1 mm value on the HART line) ®...
  • Page 14: Special Data For Ex Certified Models

    3.2. S PECIAL DATA FOR EX CERTIFIED MODELS 3.2.1. ATEX APPROVALS No.: BKI16ATEX0012X/2 M–5/7–5 Ex M–5/7–6 Ex M–5/7–C Ex M–5/7–A Ex Type M–5/7–9Ex * M–5/7–7 Ex M–5/7–D Ex M–5/7–B Ex M–5/7–8 Ex II 1 G Ex ia IIB T6…T5 Ga II 1 G Ex ia IIB T6…T5 Ga II 1/2 G Ex d ia IIB T6…T5 Ga/Gb II 2 G Ex d IIB T6…T5 Gb...
  • Page 15: Fm Us Approvals No.: Fm16Us0068X

    3.2.3. FM US APPROVALS No.: FM16US0068X (see ’Safety Manual’) The following data is for information purposes only. The FM certificate and the safety instructions can be found in the attached ’Safety Manual’. M–5–E M–5–G M–5–J TYPE M–5–F M–5–H M–5–K Marking (FM US) Class I, Zone 1, AEx db IIB T6…T5 Gb Class I, Division 1, Groups C, D T6…T5 Class I, Division 2, Groups C, D T6…T5...
  • Page 16: Accessories

    3.3. A CCESSORIES For MK and MN types only Installation and Programming Manual • 1 pc weight Warranty Card, • • 1 pc M10 nut EU declaration of conformity, • • 1 pc M10 spring washer 2 cable glands (M20x1.5) •...
  • Page 17: Temperature Classes And Temperature Limits

    NIVOTRACK M–500 / 600 units do not require maintenance on a regular basis. Repair during or after the guarantee period should only be carried out by NIVELCO. Devices for repair should be returned fully cleaned, and disinfected. Unused devices must be stored within the ambient temperature range specified in the technical data, and a maximum of 98% relative humidity.
  • Page 18: Installation

    These effects can be attenuated in applications with rigid tube probes by the use of stilling pipe along the whole probe. Please consult with a NIVELCO distributor! To ensure consistent and durable operation the measurement medium should be free of suspended solid materials, which could stick between the float •...
  • Page 19: Wiring

    TTENTION In order to avoid damaging the probe, do not put it to torsion when installing or removing the unit. Therefore, special care has to be taken when the process connection is being screwed into or out of the flange. The best is to hold the rigid part of the probe with a suitable tool as long as the process connection is tightened to its place.
  • Page 20: Wiring Of Ex Certified Units

    4.2.1. Wiring of Ex certified units 200mV MultiCONT Ex power supply 250 Ohm HART With HART Standard With MULTICONT 4.3. L OOP CURRENT CHECKING After removing the cover and the display module the actual loop current can be measured with an accuracy of 0.5% by connecting a voltmeter (in the range of 200 mV) to the points indicated on the drawing above.
  • Page 21: Programming

    If the transmitter is left in Programming Mode by mistake, it will automatically return to Measurement Mode after 30 minutes and modifications will be unsaved. FACTORY SETTINGS The NIVOTRACK M-500 / 600 type transmitters will be delivered with the following Factory default values: ⇒ Measurement mode: level (LEV). Displayed value shows level.
  • Page 22: The Sap-300 Display Unit

    The SAP–300 module The SAP–300 is a 64 × 128 dot-matrix LCD display which can be plugged into the L:2.345m transmitter. (Universal – usable in other NIVELCO devices as well – provided that the 200.000 system software supports SAP-300.) Warning! The SAP–300 module is based on LCD technology, so please make sure it is not...
  • Page 23 Information displays: Press button to cycle between the information displays. L:2.345m 200.000 1. The general information display (DEV. INFO): overall running time (OV. RUN TIME), run time after power on (RUN TIME), type of interface (INTERFACE), relay (RELAY) and logger (LOGGER) indication.
  • Page 24: Programming With The Sap -300 Display Unit

    5.2. P –300 ROGRAMMING WITH THE SAP DISPLAY UNIT When entering the menu the instrument makes a copy of the actual parameters, all changes are done to this duplicated parameter set. During programming the instrument keeps measuring and transmitting with the current (and intact) parameter set. After exiting the menu the instrument replaces the original parameters with the new parameter set and will measure according the new parameters.
  • Page 25: Menu Structure

    Dialog window WARNING The system sends messages or warnings using dialog windows. These usually can be acknowledged by LOAD DEFAULT TO pressing the button or the user can choose between two options (usually YES or NO) by pressing PARAMETER TABLE! ARE YOU SURE? buttons.
  • Page 26: Programmable Features Description

    5.3. P ROGRAMMABLE FEATURES DESCRIPTION 5.3.1. Basic measurement settings 5.3.1.1 Units Default measuring unit: Parameter: P00: c, where a: 0, 1. Default value: Menu path: BASIC SETUP / UNITS/ENGINEERING SYSTEM (for USA versions: US) Description: This should be configured as the first step of the programming. Here you can choose the default unit system: European unit system •...
  • Page 27: Damping Time

    5.3.1.3 Damping time Parameter: Default value: 0 sec Menu path: BASIC SETUP / DAMPING TIME Description: Damping time is used to damp the unwanted fluctuations of the output and display. If the measured value changes rapidly the new value will settle with 1% accuracy after this set time.
  • Page 28: Analogue Output

    5.3.2. Analogue Output 5.3.2.1 Output current mode Parameter: P12: b, where a: 0, 1. Default value: AUTO Menu path: OUTPUT SETUP / ANALOG OUTPUT / CURRENT MODE Description: Transmission mode of the current output [AUTO, MANUAL] AUTO The output current is calculated from the measured value, output is •...
  • Page 29: Output Current Error Mode

    5.3.2.4 Output current error mode Parameter: P12: a, where a: 0, 1, 2 Default value: HOLD Menu path: OUTPUT SETUP / ANALOG OUTPUT / ERROR MODE Description: Error indication by the current output HOLD Error indication has no effect on the output current. •...
  • Page 30: Calculation

    5.3.4. Calculation 5.3.4.1 Zero point offset (Distance between the lowest position of the float and the bottom of the tank) Parameter: Default value: Menu path: CALCULATION / LEVEL OFFSET Description: This Parameter is used for zero point offset. In level measurement mode the zero level is meant at the lowest position of the float. Due to the construction of the device, it cannot able to measure the level through the whole height of the tank, because it may not reach the bottom of the tank.
  • Page 31: Calculation Mode

    5.3.4.2 Calculation mode Parameter: P47: a, where a: 0,1. Default value: Menu path: CALCULATION / V/M CALC. MODE Description: Calculation of the volume and mass can be performed with two ways: TANK FUNCTION/SHAPE – volume and mass calculation with a tank shape •...
  • Page 32: Tank Dimensions

    5.3.4.5 Tank dimensions Parameter: P41-P45 Default value: Menu path: CALCULATION / V/M CALC. MODE / TANK FUNCTION/SHAPE Description: DIM1 (P41) • DIM2 (P42) • DIM3 (P43) • DIM4 (P44) • DIM5 (P45) • Standing cylindrical tank with Standing cylindrical tank with Standing rectangular tank with hemispherical bottom a = 0 conical bottom a = 1 ;...
  • Page 33: Volume And Mass Table (Vmt)

    5.3.4.6 Volume and Mass Table (VMT) Parameter: Menu path: CALCULATION / V/M CALC. MODE / V/M TABLE Description: View/Edit table • Add item • Delete item • If none of the formulas match perfectly to the characteristics of the needed tank, there is a possibility to use table V/M CALC.
  • Page 34: Service Functions

    5.3.5. Service functions 5.3.5.1 Security codes User codes Menu path: SERVICE / SECURITY / USER LOCK Description: Setting or unlocking the user security code. The instrument can be protected against unauthorized programming with a 4-digit PIN (Personal Identification Number) code. If either of the digits differs from 0 the code is active.
  • Page 35: Distance Simulation

    5.3.5.3 Distance simulation This function facilitates the user to be able to check the calculations (tank formula, table), outputs, and the additional processing instruments connected to the output. NIVOTRACK transmitters can perform simulation on the value of a constant or a variable. To start simulation the instrument must return to Measurement mode.
  • Page 36: Load Default Values

    5.3.5.4 Load default values Menu path: SERVICE / DEFAULTS / LOAD DEFAULT Description: This command loads all default values of the instrument. After loading the default values the parameters can freely be changed, the effect of the changes does not affect the measurement until the user exits programming mode and returns to measurement mode.
  • Page 37: Error Codes

    6. ERROR CODES ESSAGE ON THE SCREEN RROR ESCRIPTION ROCEDURE MEMORY ERROR Memory error in the electronics Contact the service! NO INPUT SIGNAL Probe error Contact the service! EE COM. ERROR Hardware error (EEPROM communication error) Contact the service! MATH. OVERLOAD Display overflow Check the programming! SIGNAL IN N.D.B.
  • Page 38: Menu Map

    7. MENU MAP 38 / 40 ♦ mba505en1910p...
  • Page 39 mba505en1910p ♦ 39 / 40...
  • Page 40 December 2019 NIVELCO reserves the right to change technical data without notice! 40 / 40 ♦ mba505en1910p...