TABLE OF CONTENTS INTRODUCTION ............................................. 6 ORDER CODE ( !) ..................................7 NOT ALL COMBINATIONS POSSIBLE 2.1........................................8 CCESSORIES TO BE ORDERED 2.2. ............................................. 8 LOAT SELECTION TECHNICAL DATA ............................................9 ...
Thank you for choosing a NIVELCO instrument. We are sure that you will be satisfied throughout its use! 1. INTRODUCTION Application Operating principle NIVOTRACK MI−, MX−, MY−5 series working on the The magnetostrictive transmitter is using the special feature of the magnetostrictive principle are suitable for high accuracy level measurement magnetostrictive wire spanned in the rigid probe.
3. TECHNICAL DATA STANDARD MINI PLASTIC COATED VERSION TYPE MI MY MX Liquid level, distance Measured process value 0.3…3 m (1…10 ft) 0.3…3.5 m (1…11.5 ft) 0.3…1.5 m (1…4.9 ft) Nominal length (L) PFA coated, Stainless steel: DIN 1.4571 Stainless steel: DIN 1.4571 Material of the tube 3 bar (0.3 MPa, 43.5 psi) Max.
3.1. M (MSZ EN 60770-1:2011, MSZ EN 61298-1:2009, MSZ EN 61298-3:2009) EASUREMENT DATA M–5– Resolution (on HART transmitted value) ® 1 mm (0.04") ±2 mm (±0.08") or ±0.085% whichever is greater Nonlinearity (on HART transmitted value) ® Under reference conditions Hysteresis (under reference conditions) ±0.25 mm (±0.01") Zero span (in LEVEL measurement mode)
These effects can be attenuated in applications with rigid tube probes by the use of stilling pipe along the whole probe. Please consult with a NIVELCO distributor! ...
4.1. WIRING This transmitter is designed to operate on 12.5…36 V DC power only. The measured voltage on the terminals of the unit should be at least 12.5 V. Using transmitter with HART a terminal resistance ® with a minimum value of 250 Ω should be applied. CAUTION! the enclosure of the transmitter should be grounded.
Page 14
P1: - - - a: Primary value (PV) source Parameter: P1: a This mode determines the primary value and the displayed value. It also determines the value which will be proportional to the output current. • • a=0: DISTANCE • • a=1: LEVEL Default value: a=0 (DISTANCE) Zero-point offset Description: This Parameter is used for zero-point offset.
Page 15
P11: Output current value 20 mA Description: Measured value assigned to 20 mA. The transmitted value is in accordance to the primary value (PV) (P01:a). Assignment can be done that the change in measured value and the change in the output value are the same (normal), or opposite directional (inverse operation).
Our official form (Returned Equipment Handling Form) must be enclosed. Download it from our website www.nivelco.com. The device must be sent with a declaration of decontamination. Please provide a statement in the declaration that the decontamination process is completed, the device is clean and free from harmful materials, and there are no hazardous substances on it.