  • Page 1 NEX-6101 February 21, 2025 NX6100 Integrated Burner Controller Commissioning Manual...
  • Page 2 UV, UV-Self Check, and Infrared sensors, provide fast reliable scanning of most commonly burned fuels in addition Fireye Self Checking CANbus sensor may be used for simplified wiring. For exotic fuels and applications, the NX6100 is also compatible with Fireye Phoenix and Insight Integrated Flame Scanners. Seven low voltage and two-line voltage user defined auxiliary inputs provide supervision of safety critical and non-safety critical inputs.
  • Page 3 M20 male to ½” NPSM female adapter for NXC40 35-372 Type 2 O2 PROBES AND EXPANSION MODULE FOR NX6100 NXO2TRIM CANbus O2 interface module with Fireye and generic (4-20mA) probe inputs. NX-CAB-SET Interconnecting Cable from O2 probe to controller 33ft (10 m.) ONLY NXPK224455 O2 probe assembly (for flues 300mm to 1000mm).
  • Page 4 CANbus self-checking Flame Scanner for Axial view. NX224763 6094 UV Tube Replacement Kit NX224762 6095 UV Tube Replacement Kit 5m (15') CANbus quick disconnect connection cable for Pressure sensors. NX224760-15 and scanners. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 5 B1266- 20 feet. For use with InSight scanner and direct coupled amplifiers. 59-497-020RC-WR Factory wired cable assembly with right angle connector and flexible conduit adapter - 20 feet. For use with InSight scanner and direct coupled amplifiers. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 6: Safety Information

    QUALIFIED BY TRAINING AND EXPERIENCE. 5. After installation or modifications to the installation, all functions of the equipment MUST be checked to make sure safe and reliable operation of the controller. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 7 NOTE: The manufacturer of this equipment has a policy of continual product improvement and reserves the right to change the specification of the equipment and the contents of this manual without notice. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4...
  • Page 8 VSD, Oxygen and CO Trim options. Faults and Fault Finding: Faults and Fault codes Engineers Keys. Troubleshooting. Technical specifications and Connections. Appendix: Option parameter descriptions Glossary of Terms Licenses. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 9 Nothing contained in this manual constitutes a warranty of any kind in respect of the machine or of the results to be achieved by its use. The only warranties given by Fireye LLC in respect of any device are those expressly given by Fireye LLC or your supplier in the contract under which it sells the device to its purchaser.
  • Page 10: Table Of Contents

    NX6220 and NX6330 OLED Display & Keypad option ..........23 The Start-up Sequence ....................29 Flame detection ......................33 Gas Safety Valve Leak Test (VPS) using FIREYE fail-safe sensors ......33 Gas Safety Valve Leak Test (VPS) using a pressure switch ........34 Modulation of the Burner .................... 35 Non-volatile lockout ....................
  • Page 11: Nx6100 Introduction

    • interfaces with VFD feedback as a current signal or pulse signal from an encoder that measures the speed of the relevant motor, fan or pump shaft. • monitors a rotary cup speed via an encoder input. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 12: Description Of Operation

    You use it by tapping the buttons on the screen, to make selections and settings, or to operate the boiler. This unit includes a lithium battery for the clock / calendar / event log functions. The boiler type can be represented in various, user-selectable designs: 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 13: Touch Screen Power On

    ON and the relays will be held in their No Alarm state, to avoid the possibility of nuisance alarms that may otherwise occur. 5 seconds after power is applied, the FIREYE splash screen (shown here) will display for 6 seconds, after which a blank white screen will show for 5 seconds.
  • Page 14 If you were to select Adjust Ratio mode, the display background changes to YELLOW, and you can adjust a limited number of settings: For more details, see “How to go into Adjust Ration mode (Yellow)” in section 3, Commissioning. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 15: Indications On The Display

    ), the Profile number and fuel type (e.g., the Modulation mode (e.g., ), and the boiler unit address (e.g., 2. Pictorial representation (user selectable) of your boiler, burner and fuel delivery system. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 16 You see this when Oxygen Interface related fault is present. You see this when a passcode has been entered to enable changes to the boiler or burner operation. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 17 This example is for the Burner Startup Sequence display. After the sequence is completed, the display will return (after a short delay) to the overview screen. Example showing the Burner Start Sequence 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 © 2025 Fireye...
  • Page 18: Touch Screen Lockout Reset (Alarm Mute) Function

    • If you press Mute/ Reset button while the controller is in safety shutdown and the fault has cleared, the alarm will be silenced. If you press the button for more than 3 seconds, the burner will re-start. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4...
  • Page 19 • It will then move all drives to the P2 position of the new profile and open the appropriate main fuel valves. To exit from this operation panel and return to the overview screen, tap the Overview button. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4...
  • Page 20: Touch Screen 'Menu'

    To exit this operation panel and return to the overview screen, tap the Overview button. Example after pressing Menu button 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-10 © 2025 Fireye...
  • Page 21 The scroll bar at the side of the data tab allows you to move up and down the list. Example after tapping Menu > Burner Settings > EngValues tab 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-11 © 2025 Fireye...
  • Page 22 For more information on fault codes and fault finding, refer to the Fault-Finding section of the product manual. Example after tapping Menu > Fault/Event Log 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-12 © 2025 Fireye...
  • Page 23: Using The Touch Screen Keypad

    “Demo text”. Tap OK to save the text. To exit from the keypad without saving your changes, tap the Cancel button. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-13 © 2025 Fireye...
  • Page 24: Cleaning The Touch Screen

    Example after tapping Menu > Clean Screen There will now be a 20-second count- down to show you how much time you have left to finish cleaning the screen. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-14 © 2025 Fireye...
  • Page 25: Nxtsd007 7" Touch-Screen Hmi Option

    Do not use a sharp object such as a biro, pencil or metal stylus to operate the Touch screen – you may damage the screen or cause undue wear. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-15 ©...
  • Page 26 Because you can only enter Commission mode if the burner is OFF, you cannot monitor certain safety functions such as the Fuel: Air ratio positions. For more details, see “How to go into Commission mode (Red)” in section 3, Commissioning. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-16...
  • Page 27 Starts the burner and Stops the burner at a stage where burner Stop is valid. Menu Used to access Configuration and Adjustment modes. Home Returns the screen to Burner Overview mode. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-17 © 2025 Fireye...
  • Page 28 Indicates the current profile number, followed by the fuel type. Unit 1 Indicates the boiler unit address number that is used by the digital communications system and for data back-up purposes. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-18...
  • Page 29 The alarm Mute ‘button’ on the Touch screen is multi-functional. In normal operation, you can use this to test the alarms, by pressing the button for more than 10 seconds, after which the alarm relays will activate. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-19...
  • Page 30: Touch Screen 'Menu' Button

    The “Hours Run” counter for each profile is shown here. Tap the Menu or Home button to exit this screen. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-20 © 2025 Fireye...
  • Page 31 Control panel. You can change the Set-point, PID and Limit values by tapping the value and adjusting it using the up/down arrow buttons. Tap the Menu or Home button to exit this screen. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-21...
  • Page 32 EK table to view the values. Tap the Menu or Home button to exit this screen. Example after pressing Menu > Burner Settings > EngValues 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-22 © 2025 Fireye...
  • Page 33: Nx6220 And Nx6330 Oled Display & Keypad Option

    Press this key to mute (open) the alarm relays, and then press and hold the key Reset down for approximately three seconds to reset the cleared faults. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-23 © 2025 Fireye...
  • Page 34: System Overview

    This is the Engineers Key screen, it is used to view the value or status of various control parameters. It is accessed using the Engineers Key on the keypad. Current Faults on System Engineers Keys Values Descriptions Soft Keys F1-4 Engineers Keys Screen 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-24 © 2025 Fireye...
  • Page 35 Enter the fuel highlighted profile fuel profile. select. Fuel (Profile) Selection Screen Function Go Back to the system overview display. Selects the current highlighted fuel profile. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-25 © 2025 Fireye...
  • Page 36 These are accessed using the commissioning soft key (F4) from the system overview. Currently Current selected burner profile status, setpoint including flame intensity Current values for setpoint Soft Keys F1,2 and 4 Profile Adjust Screen 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-26 © 2025 Fireye...
  • Page 37: Data Screen

    This is the Data screen, it is used to view operating data, profiles and backup. Current profile setpoint and burner status. Current servo positions. Soft Keys F1, 2, 3 and 4 Data Screen 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-27 © 2025 Fireye...
  • Page 38: Setup Screen

    Setup menu options Soft Key Enter F1 go highlighted back to menu option system Setup Screen overview Function Return to system overview. Enter highlighted menu selection. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-28 © 2025 Fireye...
  • Page 39: The Start-Up Sequence

    10. Pre-ignition After the fuel and air valve actuating motors reach their ignition positions, the ignition transformer output is energized, and pre-ignition time t3 starts. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-29 © 2025 Fireye...
  • Page 40 When the air drive(s) have reached their post purge positions then the Post Purge Time t9 is started. When t9 has elapsed, the burner motor is turned OFF and the controller returns to state 1 to wait for another startup command. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-30...
  • Page 41 Section 1: Introduction 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-31 © 2025 Fireye...
  • Page 42 Section 1: Introduction 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-32 © 2025 Fireye...
  • Page 43: Flame Detection

    The NX609x Flame detectors are shuttered UV detectors, suitable for continuous operation of burner plant. Gas Safety Valve Leak Test (VPS) using FIREYE fail-safe sensors. If the gas valve leak (prove) test has been programmed and a gas profile is selected, then the controller will start the gas safety valve leak test sequence on stage 5 of the start-up sequence.
  • Page 44: Gas Safety Valve Leak Test (Vps) Using A Pressure Switch

    During this time, the test section pressure may not rise by more than P . If this test occurs, the pressure switch will close, and the controller will indicate a fault. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1–34 © 2025 Fireye...
  • Page 45: Modulation Of The Burner

    The controller has two modes of operation using the standard FIREYE modulation functions, Normal and Local. The mode of operation is set via the keypad by pushing the “Burner ON/OFF” key and selecting the mode.
  • Page 46: Local Mode

    When not configured to control an VFD, the 4-20 mA outputs may be configured to transmit system variables as current outputs. There are special wiring requirements for VFD feedback – see “Wiring Requirements” in section 2, Installation and Wiring. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1–36 © 2025 Fireye...
  • Page 47: Post Purge Operation

    – the controller does not wait for drives to position before starting the post-purge time. ——— End of Section 1 —— 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1–37...
  • Page 48: Section 1 Update History

    Section 1 Update History New version Date Changes in brief V1pt4D May 2022 Updates to sections 2.1.12, 2.2.9, 2.6, 2.8. V1pt4D June 2024 Created Fireye Document. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1–38 © 2025 Fireye...
  • Page 49 Mounting details for the 12 Key Display option ............6 Mounting details for the Oxygen Probe Interface option ..........7 Mounting arrangements for FIREYE Boiler and Burner Sensors ......... 8 Mounting details for the NXCBH CANbus Hub and PSU........... 14 Option Link Selection in the Main Controller ..............
  • Page 50: How To Install And Wire The System

    • Choose the servomotors carefully to make sure they operate within their specification. • Make sure all sections of the control are earthed, to maintain electrical safety. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–2...
  • Page 51: Mounting Details For The Nx6100 Series Controller Module

    Allow 100 mm (4 in.) for the depth of the controller including the lid and LED window. Provide additional clearance as required. The controller MUST be earthed to maintain electrical safety and ensure reliable operation. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–3...
  • Page 52: Mounting Details For The Touch Screen Display Option

    • The screen of the CANbus cable is NOT designed to provide the earth connection for the Touch screen display. Therefore, you must make a separate earth connection using the largest cross-section area cable possible. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–4...
  • Page 53: Mounting Details For The 7" Touchscreen Display Option

    The clamps are put into place like this, then the hexagon cap head clamp screws (3mm AF) are tightened evenly. until the fascia plate of the HMI is tight to the panel door forming a IP65 seal to the door front surface. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–5...
  • Page 54: Mounting Details For The 12 Key Display Option

    The display unit MUST be earthed to maintain electrical safety and ensure reliable operation. An earth terminal is provided on the back cover of the display unit. Connect the screen of the CANbus cable to this earth connection point. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–6...
  • Page 55: Mounting Details For The Oxygen Probe Interface Option

    You can mount it in any orientation, either inside or outside a control cabinet. Maintain a clearance around the conduit entries to the unit to allow sufficient space for wiring Fireye. The ambient operating temperature range is specified as 0 to 60 °C (32 to 140 °F).
  • Page 56: Mounting Arrangements For Fireye Boiler And Burner Sensors

    Section 2: Installation 1.6 Mounting arrangements for FIREYE Boiler and Burner Sensors For full technical specifications of sensors, see “Specifications” in section 6. 1.6.1 Boiler Temperature sensors Conduit Adaptor PN 35-336 The temperature sensor has a protection level of IP65 if suitable conduit glands are used, and it can be mounted in any attitude.
  • Page 57: Gas Pressure Sensors

    • a 12mm plug and socket arrangement. Example pressure sensor • Fireye ½” Conduit Adapter P/N 35-371 1.6.3 Steam Pressure Sensors When fitting the sensor, make sure that the sensor operates within its environmental specifications. An important issue is the heating effect of the steam.
  • Page 58 If there is any doubt that the burner casing is not a good electrical Earth, then the clamp ring must be connected to electrical ‘Earth’ using suitable cable. FIREYE recommended that the detector is mounted in a horizontal attitude. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4...
  • Page 59 0.3 Nm. Over-tightening of the clam screws may damage internal components and degrade the performance of the device. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–11 © 2025 Fireye...
  • Page 60 If there is any doubt that the burner casing is not a good electrical Earth, then the clamp ring must be connected to electrical ‘Earth’ using suitable cable. FIREYE recommended that the detector is mounted in a horizontal attitude. Electrical connection is by way of a 12mm plug and socket on the square section of the body.
  • Page 61 Electrical connection is by way of a 12mm plug and socket on the square section of the body. The ambient operating temperature range for this device is -20 to 60 °C . 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–13...
  • Page 62: Mounting Details For The Nxcbh Canbus Hub And Psu

    The NXCBH may be mounted in any attitude; clearances of a least 30mm should be left around the unit to allow sufficient space for wiring and to ensure reliable operation. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–14 © 2025 Fireye...
  • Page 63: Option Link Selection In The Main Controller

    Below is a diagram of the circuit board layout showing the Main controller fuse and jumper locations. Main controller: option selection jumpers (JP), links (LK) and fuses (FS). 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–15 © 2025 Fireye...
  • Page 64 • For a 4-20 mA loop-power sensor, set JP4 for +30 V and JP1 to the IN position. • For a 0-5 V modulation signal, set JP4 for +5 V and JP1 to the OUT position. • For an FIREYE 1030 or 1040 sensor, set JP4 for +30 V and JP1 to the OUT position.
  • Page 65 CANbus Termination Link Use JP7 to select a CANbus termination resistor in or out of circuit. • In most (if not all) applications, set this link to the IN position. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–17...
  • Page 66: Nxcbh Line Supply Voltage Links (Lk1 - 4)

    500 mA anti-surge (IEC 127) 230 VAC LK2 and LK4 250 mA anti-surge (IEC 127) The manufacturers of this equipment recommend the fuse type Bussmann S506 series. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–18 © 2025 Fireye...
  • Page 67: Wiring Requirements

    All cabling that operates at more than 50 V must be multi-strand, single core, PVC insulated, 16/0.2 mm (0.5mm ) (AWG 20) and must meet the requirements of IEC 227 or IEC 225. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–19...
  • Page 68 If the display unit is mounted into a burner cabinet door, make sure there is a good electrical connection between the door and the main cabinet, in addition to a good electrical contact between the display unit and the door. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–20...
  • Page 69 ‘clamps’, to make sure a ‘good’ electrical connection between the screen and the ‘clamp’ is achieved (3 and photograph). 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–21 © 2025 Fireye...
  • Page 70 Earth at the terminal rail but must pass to the screens of onward connecting cables in insulated terminals. Screen ‘tails’ and each cable core MUST not exceed 30 mm (1.25 in.), per cable ‘tail’. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–22 © 2025 Fireye...
  • Page 71 PB10 Main Controller Digital input 1 0 – 5 V PB11 Main Controller Digital input 2 0 – 5 V PB12 Main Controller Digital input 3 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–23 © 2025 Fireye...
  • Page 72 Main Gas Valve 2 relay output 0 – 230 Vac Main Controller Pilot Valve relay output 0 – 230 Vac PE10 Main Controller Main Oil Valve relay output 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–24 © 2025 Fireye...
  • Page 73 Relay output 2 normally closed 0 – 250 V Text Display Unit Relays 2 & 3 common 0 – 250 V Text Display Unit Relay output 3 normally closed 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–25 © 2025 Fireye...
  • Page 74 CANbus PSU Hub Neutral supply 115/230V ac 24 – 40Vac CANbus In 1 CANbus PSU Hub 24Vac Supply for Servos, Display Fireye. 24 – 40Vac CANbus In 2 CANbus PSU Hub 24Vac Supply for Servos, Display Fireye. 0 – 5V...
  • Page 75 CANbus PSU Hub CAN + *Notes Fireye self-test sensors NX103x/NX104x Fireye self-test NX103x/NX104x and external powered 4-20mA sensors Fireye Approved Integrated scanners type: Phoenix/Insight Scanners See section 1.11.17 for details Do not use shielded wire on this circuit 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4...
  • Page 76: System Connection Diagram

    Section 2: Installation 1.10.8 System Connection Diagram 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–28 © 2025 Fireye...
  • Page 77 If a fuse greater than 4 A is fitted in the supply to the control panel, the burner fan output terminal must be separately fused at 4 A maximum, to protect the relay contacts from ‘welding’. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–29...
  • Page 78 Line voltage while the other(s) operate at ELV (low voltage). The relay functions are set by option parameter 17.x. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–30 © 2025 Fireye...
  • Page 79 Therefore, the cable voltage rating must exceed the maximum voltage carried by any other cable connected to the controller or run in the same conduit. • This rule applies where referred to in the text. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–31...
  • Page 80 ‘braid’ screened, PVC insulated, 2 or 3 core (as required), 0.25mm wire (7/0.2 mm) (AWG 24). See Cable Voltage Rating rule in paragraph 1.10.14 on page 31. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–32 © 2025 Fireye...
  • Page 81 Never connect the Flow input or output to Line potential. Connection of any voltage above 5 V dc to these terminals will damage the controller. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–33...
  • Page 82 1.10.18 Main Controller CANbus output wiring CAUTION • The total electrical load for all CANbus devices connected to the FIREYE 6000 controller MUST NOT exceed 40 VA. • Incorrect connection may damage or destroy the devices connected to the CANbus.
  • Page 83 ‘CANbus In’ or ‘CANbus Out’. Each terminal block set has terminals 1 to 4 labelled and the ‘CANbus Out’ terminals have internal connections between the terminal numbers. The connection terminal positions are shown in the picture below. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–35...
  • Page 84 Section 2: Installation Connect the braided screen of each cable with the use of the screen termination clamp, at the NXCBH. The electrical scheme for the connections is shown below. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–36...
  • Page 85 0 – 5 Vdc Touch screen Unit CAN - Earth tag Touch screen Unit CANbus screen connection Note that all the relay outputs on the Touch screen are isolated. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–37 © 2025 Fireye...
  • Page 86 24 Vac Supply 0 – 5 V Text Display Unit CAN + 0 – 5 V Text Display Unit CAN - Text Display Unit Screen connection Not applicable 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–38 © 2025 Fireye...
  • Page 87 NX6100 NX604x or NX608x Pre-assembled wiring cables. Suitable connection wires are available from FIREYE. NX224760-0050, 5m (15’) CANbus quick disconnect connection cable for pressure sensors and scanners. Refer to paragraph Error! Reference source not found. for details on CANbus wiring.
  • Page 88 The manufacturer supplies the NX104x sensor with a 2m tail of cable, which has the core wires and screen terminated within the head. These are the connections: Terminal Function Color Test Ground Yellow Signal Green Power Blue 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–40 © 2025 Fireye...
  • Page 89: Pressure Sensor Screen Termination

    2) Clamp the braided screen between the lid and the clamp plate, with the wire tails protruding from the ‘D’ cutout as shown below. Fix the clamp plate into the sensor cap using the screws provided. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–41...
  • Page 90 Do NOT use shielded wire on the UV Scanner. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–42...
  • Page 91 NX6094/5 UVSC Pre-assembled wiring looms. Suitable connection wires are available from FIREYE. NX224760-0050, 5m (15’) CANbus quick disconnect connection cable for pressure sensors and scanners. Refer to paragraph 1.10.18 for details on CANbus wiring. 1.10.29 Photocell, I.R. Flame sensor or Volt-Free-Contact flame indication Install and wire the photocell/I.R.
  • Page 92 Important: There is no provision on the controller to supply power for external devices. Under no circumstances must the +30 Vdc supply be used for this purpose. Incorrect connection or application of voltage over 5 V may damage or destroy the devices being connected. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–44...
  • Page 93 Section 2: Installation 1.10.32 RS485 interface The RS485 interface included in the basic controller is for interconnecting several FIREYE controllers for boiler sequencing or for connecting a laptop computer during commissioning. If it is intended to make a permanent connection to a BCS or non-FIREYE equipment, then the optional daughter board should be installed, which provides communications via an isolated RS485 interface using the Modbus protocol.
  • Page 94 Insulation and the screen cover the conductors as much as possible. ◄── Route the screened signal cables through the clamps before terminating at connectors, as shown on the left. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–46...
  • Page 95 PG1 to PG8 Ring terminal point for screen termination. NOTE: Cable screen terminations are as short as possible Cable entries points are provided on this face. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–47 © 2025 Fireye...
  • Page 96 Max Voltage in use 5V d.c. Flue Gas temperature measurement. • Type ‘K’ compensating cable. • 2-core PVC insulated cable with 0.25 mm (24 AWG) conductors, covered in overall PVC sheath. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–48 © 2025 Fireye...
  • Page 97 Screen Connection". • See Cable Voltage Rating rule in paragraph 1.10.14 on page 31. Incorrect connection may damage or destroy the devices being connected. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–49 © 2025 Fireye...
  • Page 98: Final Checks

    • Check all metal ‘bodied’ parts of the system are correctly connected to earth. • Check that all cables where required are of the correct ‘braided screen’ specification and terminated as defined in this manual. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–50...
  • Page 99: How To Select And Install The Actuators

    2.1 Actuator (Servo Motor) Models 2.1.1 NXC04 4 Nm Actuator (3ft pd) Dimensions and mounting holes 2.1.2 NXC12 12 Nm Actuator (9ft pd) Dimensions and mounting holes 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–51 © 2025 Fireye...
  • Page 100 Section 2: Installation 2.1.3 NXC20 20 Nm Actuator (14.75ft pd) Dimensions and mounting holes 2.1.4 NXC40 40 Nm Actuators (29.5ft lb) Dimensions and mounting holes 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–52 © 2025 Fireye...
  • Page 101: Locking The Actuator To The Valve Shaft

    You can reverse this by setting Option parameters 5.0 to 5.9 to a value of 1. DO THIS BEFORE ALIGNING SETTING THE ZERO POSTION FOR THE VALVE OR DAMPER SERVO MOTOR. 2.5 Selecting and Calibrating Actuators 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–53 © 2025 Fireye...
  • Page 102: Motor Requirements

    2.5.1 Motor requirements Only actuators supplied by FIREYE may be used with this equipment; various actuators/servomotors are available to suit different applications. The information below is intended as a general guide only. When installing or adjusting the actuators fitted to the appliance, make sure you refer to the correct instruction manual.
  • Page 103: Aligning The Potentiometer Type Actuator

    90°, but we recommend that it is in the range 45° to 90°. Verify that the servomotor is being stopped by the micro-switch, and not by being stalled by some mechanical limit on the valve that it is operating. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–55...
  • Page 104 8. Move the motor, up and down a few times to check that the motor stops each time at the desired limit position. Repeat steps 3 to 7 for all servomotors. 2.6.2 Actuator micro-switch movement limiters NXC20/40 M NXC04 NXC12 NXC20 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–56 © 2025 Fireye...
  • Page 105: Aligning The Magnetic Feedback Actuators

    If the jumper is left in the programming position (Pins 1-2) when the controller exits to run mode, an ERR3 will be shown for the drive position, and the controller will move to Lockout. In this case you may need to repeat the Closed point setting process. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–57...
  • Page 106: Section 2 Update History

    June 2022 Minor text amendments. Addition of the description for the Service Schedule function. V1pt4D June 2024 Created Fireye Document. ——— End of Section 2 —— 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–58 © 2025 Fireye...
  • Page 107 The backup process..................... 36 Restoring commission data from the HMI............. 36 5. THE SERVICE SCHEDULE SYSTEM. Introduction ......................37 Using the Service Schedule system ..............38 6. SECTION 3 UPDATE HISTORY Commissioning Manual version 1.4 3–1 3 NX6100 Fireye - Commissioning V1pt4D...
  • Page 108: Commissioning

    • After entering and/or adjusting any profile points for any profile, it is the responsibility of the commissioning engineer to verify that the resulting fuel: air ratio is acceptable for the application being controlled. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–2...
  • Page 109: Passcode Access

    9. If the electrical configuration requires interlocks to digital inputs on the FIREYE6000, then set options 16.x, 18.x and 19.x to configure the response of the input and the display message. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–3...
  • Page 110: Option Parameters

    Curve Set". You can have up to four separate Profiles stored in the Fireye system, but it is not common to use all four. For example, you might have one Profile for gas and one for oil; or you may set up a full-power profile for 10MW output, and a reduced-power profile for 6MW output.
  • Page 111 42.7 to 42.9 Air pressure profiling options 43.x CAN Bus burner and boiler sensor - serial numbers 44.x FGR Hold-off options 45.x Erase and Restore options. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–5 © 2025 Fireye...
  • Page 112 2: Then you can test and fine-tune the profile in Adjust Ratio mode with the burner ON. In this mode you can then go to any set point in the sequence as required. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–6...
  • Page 113: How To Commission Using The Touch Screens

    Section 3: Commissioning How to Commission using the Touch screens The Touch Screen used on many installations of the FIREYE system. The Touch-screen option is a more advanced interface than the text display and is much easier to use. Note: never use a sharp object such as a biro, pencil or metal stylus to operate the touchscreen. This could damage the screen, which would then not be covered by warranty.
  • Page 114: How To Go Into Commission Mode (Red)

    • Tap the EXIT COM mode button to confirm. You will return to the main screen. • Stop the burner and log in to Commission mode, as described above. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–8 © 2025 Fireye...
  • Page 115: How To Go Into Adjust Ratio Mode (Yellow)

    If the background is RED, then the burner is still OFF, and you are in Commission mode, not Adjust Ratio mode. • Exit from Commission mode as described above. You will then return to the main screen. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–9...
  • Page 116: Touch Screen Unit Settings

    Also, the Touch screen calibration process can be initiated from this tab. Example after tapping Menu > Screen Configuration > Display tab 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–10 © 2025 Fireye...
  • Page 117: Ethernet Settings

    Touch screen Configuration panel. This will ensure the changes are saved correctly. Example after tapping Menu > Screen Configuration > Ethernet tab 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–11 © 2025 Fireye...
  • Page 118 For example, this allows you to put a boiler on Standby SP2 for scheduled time zones during the week when full output is not required, then bring it up to full output SP1 during other time zones, and OFF if you don't need output on Sundays. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–12...
  • Page 119 ON. To switch off, tap again. 10) When you have finished, tap the X button at the top right of the tab pane. This returns you to the Burner Settings > Drives tab. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–13...
  • Page 120: System And Site Info: The 'About' Button

    Commission mode. You can back up Commission data to a USB memory stick. See 2.5. You can also install a firmware update from a USB memory stick. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–14 © 2025 Fireye...
  • Page 121: Entering The Local Site Details

    • Tap OK to finish. • To return to Run mode, tap Menu > Burner Settings > Run > Exit COM Mode. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–15 © 2025 Fireye...
  • Page 122: Plant Inputs Button

    Commission mode. For configuring and labelling these indications, see section 2.8, "Custom Naming of Plant Control Inputs". Example after tapping Menu > Plant Inputs 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–16 © 2025 Fireye...
  • Page 123: Make The Drive Settings

    Fine Adjust mode. After you have entered or changed the required values, you can exit to Run mode by tapping RUN followed by ENTER. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–17...
  • Page 124: Custom Naming Of Plant Control Inputs

    Description 'text' button On the left of the screen is the name of the Control Input, e.g. HIGH WATER, Low Water Fireye., which describes the measurement point on the plant. The text button sets the text for each on-screen indication on the left. In the screen shot above, the text for the first indicator is "HIGH WATER";...
  • Page 125: How To Program The Controller Via Touch Screen

    • If a VSD (Variable Speed Drive) is controlling the combustion air fan, then increase the speed of the fan to maximum. Tap to select the VSD box (labelled FAN) and use the UP arrow to increase the speed. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–19...
  • Page 126 • After you have completed all the profile points to build the curve, tap RUN and then ENTER. The system exits Commission mode back to Run mode, and then the system automatically modulates the burner according to the profile. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–20...
  • Page 127: How To Commission Using The Text Display

    If you entered the correct passcode, the display top line will show COM, and the next line will show which represents the Closed position set point. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3-21...
  • Page 128: Using The Option Set Mode

    ENTER key to store the new value. • Repeat the process to select another Option parameter and set or adjust the values as necessary. When you have finished, exit from Option Set mode. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–22...
  • Page 129: Option Parameter List And Descriptions

    Sets the SITE Passcode – a 3-digit code that allows access to change a 00.1 0-999 limited selection of parameters. 00.2 Used to assign a unique FIREYE serial communications address if 0-15 required. 00.3 Set to 1 to reset hours run for all fuels. Hours will be reset to 0 when the burner starts to modulate.
  • Page 130 High gas pressure limit 0-999 10.5 # Leak test volume 0-99.9 10.6 # Valve leak limits 0-99.9 10.7 Vent valve configuration 10.8 Valve leak test type 0/1 or 2-360 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–24 © 2025 Fireye...
  • Page 131 15.6 Modulation time 0-120 15.7 Bumpless transfer selection 15.8 Low before OFF 16.1 Go Back To Pilot input assignment 0-15 16.2 Enable on-line profile swap 0-16 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–25 © 2025 Fireye...
  • Page 132 Auxiliary Analog input function 20.8 Lead Boiler select input 0-16 or 21-36 20.9 Reserved 21.0 PID control loop 1 enable 21.1 Control loop 1 Set point 0-999 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–26 © 2025 Fireye...
  • Page 133 Output 1 zero (4 mA) value 0-999 29.2 Output 1 span (20 mA) value 0-999 29.3 – As 29.0 to 29.2 but for Analog output 2 29.5 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–27 © 2025 Fireye...
  • Page 134 44.9 Reset system Fault Log 45.0 Erase or Restore enable 0 – 5 45.1 Erase 0 – 999 45.2 Restore command END OF OPTION PARAMETERS LIST 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–28 © 2025 Fireye...
  • Page 135: Set Or Adjust The Fuel/Air Ratio

    Position during ignition; this may be outside the normal firing range. Low Fire Low Fire set point, (unless limited modulation range is selected). (others as ... required) 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–29 © 2025 Fireye...
  • Page 136 • If a non-volatile lockout occurs, the set points are kept in the same way as for a controlled shutdown. It will be necessary to remove all faults before moving further than step 2. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–30...
  • Page 137: Leaving Commission Ratio Mode

    Supplier passcode, scroll to ENTER ▲ ▼ select the second three-digit number [f4] 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–31 © 2025 Fireye...
  • Page 138: Using Adjust Ratio Mode

    ‘A.x’ adjustment mode. 6. Repeat steps 2-5 as required. Each time step 5 is completed, the new positions will be stored permanently. 7. Leave Adjust Ratio mode. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–32 © 2025 Fireye...
  • Page 139: Leaving Adjust Ratio Mode

    P7 is stage 5 output ON – PD4. After P8 is displayed, press [Run] and then [Enter] to exit Commission mode. DO NOT adjust the air damper position for P8. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–33...
  • Page 140 In Adjust Ratio mode, the controller operates in a similar manner to other NX6100 series controllers, but the number of Solenoids is fixed for each set point position. The Air Damper position can be adjusted Open or Closed at each set point position. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–34...
  • Page 141 16.9 Oil Valve Switch Point is set to zero). 7) Confirm the combustion is safe and reliable. 8) Repeat steps 3 to 7 for all stages including High Fire. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–35...
  • Page 142: Commissioning Data Backup And Restore

    If the CAN addresses of all devices on the bus match those in the restored backup, then the controller will allow the burner to start and run without further intervention. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–36...
  • Page 143: The Service Schedule System

    With the Service System activated and an item due date reached a ‘Service Due’ message will appear in the banner line at the top of the screen. This is a prompt to the user to call for a service visit. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–37...
  • Page 144: Using The Service Schedule System

    In the Setup screen the service items are shown along with the service due date and the time period in which the item should be checked. These can only be adjusted if the Commission or Adjust passcode has been entered in the burner adjust screen. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–38...
  • Page 145 ‘Change’ button. Next, tap the service item button (e.g., Burner service). A pop-up message will be displayed, like this… 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–39 © 2025 Fireye...
  • Page 146 Repeat the update procedure for any other schedule items covered during the service. button. Exit commission mode from the ‘Burner To save and exit the Service Schedule screen tap the adjust’ screen. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–40 © 2025 Fireye...
  • Page 147: Section 3 Update History

    New version Date Changes in brief V1pt4D June 2022 Minor text amendments. Addition of the description for the Service Schedule function. V1pt4D June 2024 Created Fireye Document. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–41 © 2025 Fireye...
  • Page 148 Section 3: Commissioning ——— End of Section 3 —— 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–42 © 2025 Fireye...
  • Page 149 CO Trim wiring......................21 CO Trim option parameters ..................21 CO Trim EK’s ........................21 4. SECTION 4 UPDATE HISTORY 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–1 © 2025 Fireye © 2024 Fireye...
  • Page 150: Inverter (Variable Speed Drive) Units

    If the values do not match those stored in memory, a positioning fault is given, and the controller performs a non-volatile lockout. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–2...
  • Page 151: Setting Up The Inverter For Use With The Nx6100 Series

    Configure the inverter in the following way: • RUN/STOP from external input (NOT inverter keyboard) • RUN/STOP active high (i.e., energize to start). 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–3 © 2025 Fireye...
  • Page 152: Setting Up The Nx6100 Series For Use With An Inverter Drive

    The inverter drive unit has a closed position (4 mA), a maximum position (20 mA), a pre-purge position, an ignition position and up to 20 profile positions. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–4...
  • Page 153: Encoder Wheel Design

    The following proximity detection devices are compatible with the NX6083-X daughterboard when using encoder discs of the types shown above: • Pepperl+Fuchs NBN4-12GM50-E2-12M • Omron E2E-X3D1-N • Carlo Gavazzi IA12ESF02UC. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–5 © 2025 Fireye...
  • Page 154: The Oxygen Trim Option

    There is a calibration port located in the back of the probe, which is sealed with a screw. You must keep this port sealed during normal operation, for safe and accurate performance. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–6...
  • Page 155 Section 4: VSD, Oxygen and CO Trim options. Oxygen Probe drawing: 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–7 © 2025 Fireye...
  • Page 156: Installing The Oxygen Probe

    Mounting the probe with the flange horizontal (2) is acceptable. Inverted probe mounting is not acceptable. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–8...
  • Page 157 100 °C. (212 °F) The maximum flue gas temperature rating is 540 ºC. (1,004 °F) 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–9...
  • Page 158 It can also provide closed loop oxygen trim control if required. The cabling between the NXO2TRIM oxygen probe interface and the NX6083-X probe consists of the following:- 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–10...
  • Page 159: Calibrating And Servicing The Oxygen Probe

    7. When the value displayed for option 30.1 (42.1) has settled to a value within range, scroll back to Option 30.6 (42.6), change the display to zero and then press Enter. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–11...
  • Page 160 Calibration air pump. 350cc/min 150mm (6ins) If the pressure is 150 mm (6 ins) water gauge or more, replace the filter. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–12 © 2025 Fireye...
  • Page 161: Removing The Oxygen Probe From The Flue

    • The only customer-replaceable items are the flue thermocouple and the oxygen filter. • Refitting is the reverse of the removal procedure. Make sure that the screws are tightened sequentially and evenly. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–13...
  • Page 162: Replacing The Filter

    • When the screws and washers have been removed, pull the sample tube away from the body to allow the captive filter assembly to be removed. • You can now insert the new filter assembly (Fireye number 19-117) into the sample tube, with the beveled side to the probe body.
  • Page 163: Commissioning Oxygen Trim

    • The flow for each profile position must be programmed to ensure correct operation. The flow value can either be measured for each profile position or calculated as a percentage of the flow at High Fire. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–15...
  • Page 164 Go into Adjust Ratio mode with oxygen trim disabled as outlined above. 1. Select the High Fire position. The display will then show A(n), where n is the number of the High Fire profile point. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–16...
  • Page 165 High Fire = A10 ------------ 99.9% 99.9% 1 = A9 (99.9) (y/c 0.812 81.1% 82.6% 2 = A8 (y/c 0.908 73.7% 74.4% 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–17 © 2025 Fireye...
  • Page 166 8 = A (y/c 9 = A (y/c 10 = A (y/c 11 = A (y/c 12 = A (y/c 13 = A (y/c 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–18 © 2025 Fireye...
  • Page 167 Fire) is stored in Option 30.7. Also, Option parameter 30.5 (oxygen trim enable) is set to zero. IMPORTANT: BEFORE ENABLING TRIM, USE ADJUST RATIO MODE TO MANUALLY CHECK THE CALCULATED FLOW VALUES, OXYGEN SET POINTS AND TRANSPORT DELAY. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–19...
  • Page 168 Fire set point as a value of 99.9(%). ● Typically, the transport delay will be 15 to 40s depending upon the size of the boiler. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–20...
  • Page 169: The Co Trim Option

    CO trim is enabled as follows. Description CO level (ppm) Oxygen set point after CO trim. CO trim modifier Oxygen set point before CO trim. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–21 © 2025 Fireye...
  • Page 170: Section 4 Update History

    V1pt4D Dec 2022 Updated description of the oxygen measurement system. V1pt4D June 2024 Updated Fireye Version ——— End of Section 4 —— 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–22 © 2025 Fireye...
  • Page 171 Non-Volatile Lockout ....................2 Fault Subsets ....................... 3 List of Fault Code Numbers ..................3 The Engineer's Key Data (EK) ................... 13 Troubleshooting ......................26 2. SECTION 5 UPDATE HISTORY 5–1 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4...
  • Page 172: Faults And Fault Finding

    If power is removed from the controller while a fault is still present, the fault will be stored in non-volatile memory. When power is restored to the controller, the fault number will still be present, and you will need to clear the fault before restarting the burner. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–2...
  • Page 173: Fault Subsets

    See Option parameters 18.1 to 18.9. Subset = burner status number External Alarm Fault External Alarm Fault External Alarm Fault External Alarm Fault External Alarm Fault External Alarm Fault 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–3 © 2025 Fireye...
  • Page 174 (subset: 1), or the air pressure switch detected when it registered air pressure for more than 3 minutes after the burner should not be. was turned OFF (subset: 2). 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–4 © 2025 Fireye...
  • Page 175 4 = span check failed, 5= 1+4 = out of range AND span check failed; 6= 2+4= zero check failed AND span check failed, etc. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–5 © 2025 Fireye...
  • Page 176 Subset = 0 to 128. Work out the binary number of the number displayed, to see which digital inputs have failed. • Check the panel wiring. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–6 © 2025 Fireye...
  • Page 177 • If this fault persists, return the controller to the supplier. Subset = Failed Page number in memory map when the fault occurred. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–7 © 2025 Fireye...
  • Page 178 The measured gas pressure was not correct during the gas valve test fault. leak test. Subset = Valve prove status number. • Check that Option 10.1 is set correctly 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–8 © 2025 Fireye...
  • Page 179 The oxygen level measured value has exceeded the oxygen set alarm point high alarm value for the current profile. Subset = 0 = Limit violation, 1 = Probe Failed. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–9 © 2025 Fireye...
  • Page 180 The option parameters have been uploaded via serial uploaded communications. Check all values are correct and match the application, then set option parameter 45.0 to 0. Subset: Not applicable. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–10 © 2025 Fireye...
  • Page 181 1.0 is set to 1. Subset = 1 – See option parameter 1.0. 254 – Serial EEPROM write failure. 255 – NV Lockout verification failed. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–11 © 2025 Fireye...
  • Page 182 The 4-20mA input selected by Opt 44.0 is out of range – FGR will FGR input fault. be held at P3 position 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–12 © 2025 Fireye...
  • Page 183: The Engineer's Key Data (Ek)

    To view EK data using the Touch screen, tap these buttons: Menu > Burner Settings > EngValues tab Scroll through the EK values using scroll bar to the right of the panel. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–13 © 2025 Fireye...
  • Page 184: System Event History

    128 events/faults and the associated status data. However, the Touch screen display will store thousands of events. You can see the full set using the Fireye ComFire2 software interface to a Windows PC or laptop.
  • Page 185 EK12 High voltage digital input 12. EK13 High voltage digital input 13. EK14 Burner Select Input (High Voltage) EK15 Airflow Input (Low Voltage) PB18– PB19 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–15 © 2025 Fireye...
  • Page 186 +1 = Un-muted fault alarm present (prefix: F) EK23 Oxygen Trim Enable 0 = Oxygen trim is OFF or not working. 1 = Oxygen trim is ON and working (EK46 = 0). 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–16 © 2025 Fireye...
  • Page 187 Photocell / IR sensor signal value Infra-red Signal value received from the flame sensor input. For the photocell / IR input: 0 = Fully dark (no flame). 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–17 © 2025 Fireye...
  • Page 188 +32 = CANbus error. +64 = Probe calibrating in reference gas. See option parameter 30.6. +128 = Probe calibrating in air. See option parameter 30.6. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–18 © 2025 Fireye...
  • Page 189 0 = All drives are at their set points and are not moving. Non-zero = One or more drives are not at their set point. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–19 © 2025 Fireye...
  • Page 190 The ADC counts from analog input 7. EK67 Analog input 7. 0 to 999 for 4 to 20 mA. Daughter board terminal PZ12(-) PZ13(+). Also, VSD1. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–20 © 2025 Fireye...
  • Page 191 This is the file size (in bytes) of the currently running manufacturer / user program. If a user program is selected, this should match the program size (in bytes) given by the ‘Fireye Abacus’ program. EK78 Second cell temp (ºC) The internal zirconia cell temperature of the second oxygen probe see EK72.
  • Page 192 EK95-Ek97 Spare, (not in use) EK98 Combustion air pressure error. The error between the measured pressure and the value stored during the curve commissioning process. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–22 © 2025 Fireye...
  • Page 193 Remote Set point 1 Active function is active. See option parameter 20.7. Set point 1 will come from analog input 5. 1 = Limit exceeded. EK110 Control Limit Exceeded 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–23 © 2025 Fireye...
  • Page 194 Lag in Boiler Sequencing, or via Modbus. EK139 to Not used by the standard EK150 manufacturer's program. They may be used by a custom program. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–24 © 2025 Fireye...
  • Page 195 They may be used by a custom program. Currently running manufacturers / custom (user) EK200 Prog: modulation program name and revision number (if applicable). 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–25 © 2025 Fireye...
  • Page 196: Troubleshooting

    Gas pressure not shown. Gas sensor not selected. Select sensor using option parameter 10.0 Gas pressure incorrect. Incorrect span value. Check option parameter 10.1 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–26 © 2025 Fireye...
  • Page 197: Startup Problems

    Option parameter not Another option parameter must Set option parameter (usually XX.0) to a available. be set first. non-zero value to enable other parameters. in group. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–27 © 2025 Fireye...
  • Page 198 Option 10.1 not set correctly when Set Opt 43.4 to zero/none, then set Opt CAN Bus sensor is configured. 10.0=1 Check the value of Opt 10.1is correct. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–28 © 2025 Fireye...
  • Page 199 Controller stuck at a Serial communications. Disable or change modulation slider in modulation rate. Computer software. To enter Run mode, press RUN then Controller in Commission mode. ENTER. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–29 © 2025 Fireye...
  • Page 200 In extreme cases, you may need to increase the inverter error tolerance to prevent non-volatile lockouts caused by positioning faults (set option 9.1 = 1). This must only be changed if an inverter error of 55 will not cause unsafe combustion. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–30...
  • Page 201 Check option parameters 32.X. Commissioning data missing. Check option parameters 33.X are non-zero. Check oxygen and flow values been entered for all profile points in the firing range. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–31 © 2025 Fireye...
  • Page 202: Section 5 Update History

    Updates to F33 and F66 descriptions and EK45 description. Description for L89 added. Update to Oxygen system fault finding chart 1pt4D June 2024 Update Fireye Version ——— End of Section 5 —— 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–32 © 2025 Fireye...
  • Page 203 NXIATS Ambient Air Temperature Sensor ..............16 1.21 NXDBVSD and NXDBMB Daughter Boards .............. 17 1.22 Approvals ........................18 2. 6000 SERIES TERMINAL CONNECTIONS 3. SECTION 6 UPDATE HISTORY 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–1 © 2035 Fireye...
  • Page 204: Technical Specifications

    Unit dimensions Controller 2.13 kg (4 pd.11 oz.) Weight Display options Either the Touch screen graphical display. OLED display with 12 key membrane keypad. 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–2 © 2025 Fireye...
  • Page 205: Servo Motor Control

    Maximum current (per output) Maximum voltage 250 Vac rms * Maximum total simultaneous current for these groups of outputs is 8 A rms for each group. 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–3 © 2025 Fireye...
  • Page 206: Digital Inputs

    4-20 mA Maximum current 25 mA maximum 220 Ω nominal Burden resistor  1.1% Input accuracy (typical)  1.1% Input accuracy (as specified by EN12067) 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–4 © 2025 Fireye...
  • Page 207: Gas Pressure Analog Input

    First safety time Selectable Response time to flame failure 1 - 3 seconds, selectable Continuous operation Ionization or UV when used with a shutter device. 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–5 © 2025 Fireye...
  • Page 208 11 k First safety time Selectable Response time to flame failure 1 - 3 seconds selectable Continuous operation Only if set for a.c. response. 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–6 © 2025 Fireye...
  • Page 209: Communications Interface

    148h x 218w x 56d (mm) (5.83 x 8.58 x 2.2 in.) Weight: 2.65kg (5 pd.13 oz) TSD104 TSD007 1.3kg (2 pd 14 oz.) 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–7 © 2025 Fireye...
  • Page 210: Nx6Xx0 12 Key Display

    44 mm dia. x 85 mm long (1.73 x 3.25 in.) (excluding 12mm (0.472 in.) CANbus connector) Weight 600 g (1 pd 5 oz.) 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–8 © 2025 Fireye...
  • Page 211: 45Uv5 Shuttered Uv Flame-Detector

    50 mm (2 in.) Terminal and control box 79 x 74 x 52 mm (3.11 x 2.91 x 2.05 in.) Weight: 0.65 kg (1 pd 7 oz.) 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–9 © 2025 Fireye...
  • Page 212: Nx6043 Gas Pressure Sensor

    44 mm (1.73 in) dia. x 85 mm (3.25 in.) long (excluding 12mm (0.472 in.) CANbus connector) Weight 600 g (1 pd 5 oz.) 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–10 © 2025 Fireye...
  • Page 213: Nx6045 Boiler Steam Pressure Sensor

    Burst pressure 1 bar (15 PSI)  0.1% of span Accuracy (typical)  0.3% of span Accuracy (as specified by EN12067)  0.9% of value 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–11 © 2025 Fireye...
  • Page 214: Nx1030 Steam Pressure Sensors

    Burst pressure 12 bar (174 pd)  0.1% of span Accuracy (typical) Accuracy (as specified by EN12067)  0.3% of span  0.9% of value 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–12 © 2025 Fireye...
  • Page 215: Nx1040 And Nx1044 Boiler Temperature Sensors

    NXC40 = 31 Nm (23 Ft/Lb) (driving), 41 Nm 29.0 FT/LB) (holding) NXC40 = 18 VA VA rating NXC40 = IP65 Protection Category ± 0.6 Typical accuracy (as specified by EN12067) 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–13 © 2025 Fireye...
  • Page 216: Nxc04, Nxc12 & Nxc20 Actuators

    Controller 176 x 114 x 95 mm deep. Unit dimensions (6.93 x 4.49 x 3.74 in deep) 1.3 kg (2 pd 14 oz) Weight 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–14 © 2025 Fireye...
  • Page 217: Nxo2Trim Oxygen Probe Interface

    O2, CO Flue gas temperature input: Type Type-K thermocouple. Measurement range 0-540 °C (1000 °F). Flue temperature accuracy ± 2 °C (± 2 °F) 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–15 © 2025 Fireye...
  • Page 218: Nx6083-X Flue Gas Oxygen Probe

    63 x 58 x 36 mm deep (2.48 x 2.28 x 1.42 in deep) Weight 0.2 kg Temperature measurement accuracy E± 2 °C (2 °F) 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–16 © 2025 Fireye...
  • Page 219: Nxdbvsd And Nxdbmb Daughter Boards

    Selectable - 4800, 9600, 19200 baud Isolation Voltage 50 Vdc Auxiliary relays Type ON-OFF relay, de-energize for OFF. Maximum current 100 mA Maximum voltage 50 Vdc 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–17 © 2025 Fireye...
  • Page 220: Approvals

    TRD 411:02.97 – Compliance (TÜV Rheinland) TRD 412:06.98 – Compliance (TÜV Rheinland) Australian Gas Association certified product. Relevant standards: EN298:2012, AS 4625-2008, AS 4630-2005. 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–18 © 2025 Fireye...
  • Page 221: Series Terminal Connections

    Section 6 – Technical Specifications and Connections 6000 Series Terminal Connections These are the wiring terminal connections for the 6000 controller, inside the box. 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–19 © 2025 Fireye...
  • Page 222 PZ13 [4-20 mA] Feedback Ch1 +ve PZ14 [4-20 mA] Feedback Ch2 +ve PZ15 Relay Output 2 PZ16 Relay Output 2 PZ17 Relay Output 1 PZ18 Relay Output 1 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–20 © 2025 Fireye...
  • Page 223 Section 6 – Technical Specifications and Connections Section 6 Update History Date Changes in brief version Jan 2019 General update for V1.4 Firmware. V1PT4C July 2024 North American Version 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–21 © 2025 Fireye...
  • Page 224 Section 6 – Technical Specifications and Connections ——— End of Section 6 —— 6 NX6100 Fireye - Specification and Connections V1pt4D Commissioning Manual version 1.4 6–22 © 2025 Fireye...
  • Page 225 Section 7: Appendix CONTENTS Section 7 page: 1. OPTION PARAMETERS IN DETAIL 2. GLOSSARY OF TERMS 3. NOTICE, WARRANTIES, EXCLUSIVE REMEDIES, AND LIMITATION OF DAMAGES 4. UPDATE HISTORY 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–1 © 2025 Fireye...
  • Page 226: Option Parameters In Detail

    HOURS RUN display will be reset and the option parameter automatically returns to 0. Additionally, the counters of burner cycles and burner lockouts will be cleared (see Engineer's Key Data numbers 90 and 91). 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–2...
  • Page 227 Option 00.8 – Modbus communications speed (0 – 3) DEFAULT: 0 This option sets the Modbus communications speed as follows: Option 00.8 Speed value bits/s 9600 4800 9600 19200 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–3 © 2025 Fireye...
  • Page 228 Input 6, PB14 to PB16 Low Voltage Input 7, PB14 to PB17 Low Voltage Input 8, PB5 to PB6 Low Voltage Input 9, PB5 to PB7 Low Voltage No physical terminal DO NOT USE 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–4 © 2025 Fireye...
  • Page 229 Input 1, PB9 to PB10 Low Voltage Input 2, PB9 to PB11 Low Voltage Input 3, PB9 to PB12 Low Voltage Input 4, PB9 to PB13 Low Voltage 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–5 © 2025 Fireye...
  • Page 230 Input 9, PB5 to PB7 Low Voltage No physical terminal. DO NOT USE No physical terminal. DO NOT USE Input 12, PE7 to live. High Voltage Input 13, PE8 to live. High Voltage 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–6 © 2025 Fireye...
  • Page 231 Option 7.6 (T6 Option 14.6 entered in Pilot ignition) Pilot hold) Main ignition) (spark parameter 01.7 forced to: forced to: forced to: termination) forced to: Adjustable Adjustable Adjustable Adjustable 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–7 © 2025 Fireye...
  • Page 232 . 08.1 Parameter 07.1 07.2 07.3 07.4 07.5 07.6 NX6300 Default EP113 Cfg1 EP113 Cfg3 EP160 10/15 EP161 10/301 EP163 EP165 EP166 EP170 Required YP100 YP102 YP138 YP113 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–8 © 2025 Fireye...
  • Page 233 Input 8, PB5 to PB6 Low Voltage Input 9, PB5 to PB7 Low Voltage Input 12, PE7 to live. High Voltage Input 13, PE8 to live. High Voltage Permanently ON 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–9 © 2025 Fireye...
  • Page 234 This is important when oxygen trim is enabled for a particular drive, because it determines the trim direction. Selection of fuel trim or air trim is made with option parameters 31.1 to 31.4. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–10...
  • Page 235 The profile can be re-commissioned by using the NEXT / ENTER keys in Commission Ratio mode to verify all points on the combustion curve. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–11...
  • Page 236 • If a drive has been added or removed from a profile, then it is recommended that the specified profile is erased (using option parameter 45.X) before an attempt is made to re-commission it. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–12...
  • Page 237 If the air pressure switch doesn’t register air pressure after this time, the burner will perform a safety shutdown. If the air pressure is proved during this time, and the drives have moved successfully to their pre-purge (P1) positions, then the pre-purge time will start. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–13 © 2025 Fireye...
  • Page 238 Valve’ may be open during this time. The Pilot Ignition Time will not start until the pre-ignition time has elapsed. The controller does not monitor if a flame is present during the pilot ignition time t4. Also see option 10.9. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–14 © 2025 Fireye...
  • Page 239 At the end of the ignition hold time, the burner will move to Low Fire. The ignition hold time will not start until the main ignition time has elapsed. A flame must be detected, or a safety shutdown will occur. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–15...
  • Page 240 PE3 and PE8 (input 13). Make sure that input 13 is not selected for any other function in options 01.x, and 16.x. Number entered in parameter Ignition Output Digital inputs used 08.0 Monitored NONE i/p 13, PE8 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–16 © 2025 Fireye...
  • Page 241 The number entered is the number of re-tries (maximum of 2), before a flame failure will ‘Lockout’ the burner. CAUTION • Make sure that the setting of this option does not allow an unsafe condition to occur and is acceptable for the application being controlled. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–17 © 2025 Fireye...
  • Page 242 The inverter should also be able to move from maximum to zero speed in the same time. If this is not the case, adjust the time settings in the inverter to ensure the times to accelerate and decelerate are the same. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–18...
  • Page 243 Set this parameter if the controller is required to control the speed of a VSD driven oil pump and there is a requirement to keep the oil circulating when the burner is OFF, in order to maintain the correct oil temperature in preparation for a call for heat. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–19...
  • Page 244 Option 10.0 - Gas pressure select (0 - 4) If an Fireye gas pressure sensor is connected to the system, its type and units must be entered here. Be sure to set these options before setting the value of Opt 43.4.
  • Page 245 No vent valve fitted. Use main valve 2 to vent into the boiler. Vent valve fitted, output energized to open valve. Vent valve fitted, output energized to close valve. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–21 © 2025 Fireye...
  • Page 246 The gas valves will be energized for just under 4 seconds. The gas valves will be energized for just under 5 seconds. The gas valves will be energized for just under 6 seconds. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–22...
  • Page 247 If in any doubt about the flame threshold being set, please consult with the burner supplier, as a very low threshold may increase the possibility of a hazardous condition. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–23...
  • Page 248 Alternatively, when both flame inputs are active, you can set a pilot or zero threshold for either device to ignore the flame, provided that a flame is detected on the other device. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–24...
  • Page 249 This type of flame monitoring is suitable for continuous operation (>24 hours) when a suitable flame-sensing device is used. Set hardware jumper JP6 to the ‘IN’ position. NX6094/NX6095 CAN Bus device selected by option 13.4. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–25 © 2025 Fireye...
  • Page 250 The Flame2 Photocell / IR input is monitored for all profiles. The Flame2 Photocell / IR input is monitored for Gas profiles only. The Flame2 Photocell / IR input is monitored for Oil profiles only. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–26...
  • Page 251 Alternatively, when both flame inputs are active, you can set a pilot or zero threshold for either device to ignore the flame, provided that a flame is detected on the other device. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–27...
  • Page 252 When used for an alarm function, the relay will de-energize when in the fault condition, so you need to wire an alarm bell in series with the normally closed contacts. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–28...
  • Page 253 When used for an alarm function, the relay will de-energize when in the fault condition, so you need to wire an alarm bell in series with the normally closed contacts. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–29...
  • Page 254 Option parameter Meaning 14.3 value Non-permanent pilot Permanent pilot operation, when firing on gas. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–30 © 2025 Fireye...
  • Page 255 Install an electrical link between terminals PE11 (MV2 output) and PE12 (Pilot output). Set option 14.4 to a value of 1, which ensures that MV1 is energized at the same time as the Pilot. Set option 14.5 to a value of 2. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–31...
  • Page 256 This parameter affects all profiles whether they fire gas or oil. Option 14.7 – Aux / Oil Pump Relay Function. (0 - 6) Setting this parameter as shown in the table below configures the function of output PE6. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–32...
  • Page 257 FAN output be used to open the electrical connection between the air pressure/flow switch and the control, since this would not verify the correct operation of the air pressure/flow switch. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–33...
  • Page 258 This value will normally be left at zero. It is the measured value to be displayed when the sensor connected is at its minimum value. For NX1030 and NX1034 fail-safe sensors, this value must be left at zero. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–34...
  • Page 259 Bumpless transfer allows the controller to switch from Manual to Automatic mode or vice versa, without the control output suddenly 'bumping' to a different value. This parameter only affects the burner operation while in Manual mode. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–35...
  • Page 260 You can use this function to prevent the burner from having to go OFF when the demand is low, meaning that it is ready to respond immediately to a sudden increase in demand; no pre-purge is required. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–36...
  • Page 261 Option 16.4 – High voltage Input 13 Alarm / Lockout Function (0 - 360) This option parameter works identically to option parameters 18.1 to 18.9, except that it relates to the high voltage input 13, PE8. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–37...
  • Page 262 Option 16.7 – Oil Gun Blow-out time (0 - 30 s) This option defines the length of time that the PE6 terminal is ON when Option 14.7 = 3 - Steam purge valve for Oil gun. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–38...
  • Page 263 Digital Input 9 (PB5 – PB7) Profile 2 select (PB8 – PB6) Profile 4 select (PB8 – PB7) Digital input 12 (PE7) Digital input 13 (PE8) Burner Select Input (PE9) 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–39 © 2025 Fireye...
  • Page 264 ‘Local’ or ‘Off’ mode. OFF when controller loses power. The Relay is ON if the controller is powered up. Draft/Ventilation control – ON if controller status value is 3 through to 18. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–40 © 2025 Fireye...
  • Page 265 Display - PR1(NO), PR2(NC), PR3(COM). Low or Line voltage 17.2 Display - PR5(NO), PR6(NC), PR7(COM). Low or Line voltage. 17.3 Display - PR7(COM), PR8(NC), PR9(NO). Low or Line voltage. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–41 © 2025 Fireye...
  • Page 266 This mode of firing GAS or OIL). active during post purge. operation must not be used for any safety function because if the wire breaks, it cannot be detected. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–42 © 2025 Fireye...
  • Page 267 18.9 F9 or L9 16.3 Input 12 - PE7 to live, HIGH VOLTAGE F8 or L8 16.4 Input 13 - PE8 to live, HIGH VOLTAGE F9 or L9 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–43 © 2025 Fireye...
  • Page 268 High Pressure Low Pressure Panel Switch Open High Stack Temp. Fan Interlock End Switch Open Oil Interlock Gas Interlock Forced Lockout Extra High Water Oil Gun Interlock Low Draft 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–44 © 2025 Fireye...
  • Page 269 Dunk Failed Rise W/D Timer Fault Low Pilot Press High Pilot Press Fan VSD Tripped Pmp1 VSD Tripped Pmp2 VSD Tripped High BioGas Press Low BioGas Press BioGas Bster Tripped 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–45 © 2025 Fireye...
  • Page 270 A closed contact or high level on the input specified here will cause the boiler to go OFF and stay OFF until it is removed. No fault / alarm is generated. The input numbers are as specified in option parameter 20.0 above. Values 21 to 36 invert the function. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–46 © 2025 Fireye...
  • Page 271 The input numbers are as specified in option parameter 20.0 above. Values 21 to 36 invert the function. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–47...
  • Page 272 A value of 0 means no proportional band – the burner would stay at High Fire until the set point is reached, then drop to Low Fire. Proportional control is therefore needed to prevent the measured value from overshooting the set point. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–48...
  • Page 273 This is the zero value for the remote set point function specified by option parameter 20.7. Option 21.9 – Remote Set point 1 span (20 mA) value (0 - 999 / 00.0 - 99.9 / 0.00 - 9.99) 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–49...
  • Page 274 22.6 and 22.7 represent a deviation (i.e., offset) from the set point 1 control value. This means that if the set point control value is changed, the limits are automatically changed correspondingly. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–50 © 2025 Fireye...
  • Page 275 This defines the address of the first Lag to be selected if this controller is the Lead. Option 24.2 - 2nd Lag communications address (0 – 15) This defines the address of the second Lag to be selected if this controller is the Lead. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–51...
  • Page 276 For example, a value of 100 may be better suited for a minimum Gas Flow to ensure best resolution. Option 28.2 – Analog input 1 span value (20 mA input) Set this option to the value that a 20mA input current will represent. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–52 © 2025 Fireye...
  • Page 277 Option 28.8 – Analog input 3 span value (20 mA input) Set this option to the value that a 20mA input current will represent. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–53 © 2025 Fireye...
  • Page 278 Set this option to the value that a 20mA output will represent. For example, value of 200 may be better suited for a maximum Flue Gas Temperature to ensure best resolution. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–54...
  • Page 279 Set this option to the value that a 4mA output will represent. Often this will be zero, but non-zero values can be used. Option 29.8 – span value (20 mA output) Set this option to the value that a 20mA output will represent. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–55 © 2025 Fireye...
  • Page 280 °C. The temperature value will be displayed in °C. F. The temperature value will be displayed in F. Please note that temperature limits MUST be set in the correct units. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–56 © 2025 Fireye...
  • Page 281 As soon as the measured oxygen reading begins to change, stop the timer. Set the option parameter to the recorded timer value in seconds. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–57...
  • Page 282 High Fire, or Low Fire – depending on trim direction. The burner always modulates to the desired modulation rate, which may limit the system’s ability to maintain the desired oxygen value. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–58 © 2025 Fireye...
  • Page 283 When a second oxygen monitoring system is used, the oxygen can be considered fail-safe, and the trim limits can be set up to 50% instead of 25%, provided the maximum time between probe calibrations does not exceed six months. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–59...
  • Page 284 The accuracy of the calculated efficiency and the ‘Automatic Trim commissioning’ procedure will be adversely affected by this. It maybe that these functions should not be used, in which case these values should be entered as zero. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–60...
  • Page 285 If the burner is firing, you can only adjust the option parameter that relates to the selected profile. If the burner is not firing, you can adjust the low alarm value for any profile selection. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–61...
  • Page 286 Options 38.1 to 38.4 - Oxygen low alarm values at Low Fire (0.0 – 99.9%) Options 39.1 to 39.4 - Oxygen low alarm values at High Fire (0.0 – 99.9%) 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–62...
  • Page 287 CANbus, as for option parameter 30.0. In applications where CO monitoring and trim are a requirement, enter the serial number for the oxygen probe controller entered in option 30.0. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–63 © 2025 Fireye...
  • Page 288 Option 42.6 – Second oxygen probe calibration enable (0 to 2) This option is identical to option 30.6, except that it relates to the second oxygen probe. Note, the calibration gas concentration used must be as entered in option parameter 30.3. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–64...
  • Page 289 Option 42.2 – CO trim gain (0 – 250) CO trim gain sets the rate at which the CO trim acts – modifies the O2 Set point. Fireye recommends setting this parameter to a value of 10% initially, and then adjusting to suit the application response.
  • Page 290 Where a CANbus gas pressure sensor is used for the VPS and operating limits select the serial number of the device from those offered, in a similar way to selecting actuator serial numbers for Option 3.x. Options 11.x set the span and VPS test characteristics. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–66...
  • Page 291 This option clears the current the fault history. Set the option parameter to 1 then press RUN then ENTER. The controller will erase the fault history and return to Run mode. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–67...
  • Page 292 IMPORTANT: If you select 5, all profile set points will be deleted and all option parameters will reset to default values. The controller will be initialized to the factory default settings. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–68...
  • Page 293 If the non-standard passcode is forgotten then a ‘master passcode’ will need to be obtained, based on the unit serial number. This can be obtained using an on-line passcode system maintained by Fireye. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4...
  • Page 294: Glossary Of Terms

    A closed vessel in which water is heated, steam is generated, steam is superheated, or any combination thereof, under pressure or vacuum by the application of heat from combustible fuels, electricity, or nuclear energy. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–70...
  • Page 295 Calorific value The energy available from burning a fixed quantity of fuel. Mechanical device that converts rotary motion to linear motion. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–71 © 2025 Fireye...
  • Page 296 A general term to cover Commission Ratio and Option Set modes - with a red touch screen background. ComFire2 ComView is a software tool from Fireye, used for viewing and handling the NX6000 controller settings by means of a PC or laptop, via a USB interface cable.
  • Page 297 Monitoring the presence of the flame at the correct time and also for no flame at the correct time. Flue A passage for products of combustion. Flue gas The gaseous products of combustion in the flue to the stack. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–73 © 2025 Fireye...
  • Page 298 The master boiler which controls the sequence in which the boilers are (lead/lag). started and shutdown in a multi-boiler sequenced system Lag boiler A boiler that responds to the commands of the Lead boiler in a sequence. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–74 © 2025 Fireye...
  • Page 299 Gaseous fuel occurring in nature. Noise An undesirable sound, electrical or electromagnetic disturbance. Non-safety critical Procedures or components that are not critical to the safety of the boiler/burner. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–75 © 2025 Fireye...
  • Page 300 Proof of Closure used, for example, for gas valves and oil valves. Post-purge The process of clearing combustion gases from the boiler after the boiler has been shut down. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–76 © 2025 Fireye...
  • Page 301 A motor controlling the position of a valve or damper. Set point A preset value such as a specific speed or position that the controller is supposed to reach. Also known as the target value. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–77 © 2025 Fireye...
  • Page 302 Information that shows the operation of equipment over a time interval. Turndown The ratio of maximum boiler output to minimum boiler output. Ultraviolet, usually referring to the type of flame sensor. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–78 © 2025 Fireye...
  • Page 303 Zero adjustment refers to the output value when the input is at 0%, its lowest possible range value (LRV) Span Adjustment refers to the full output range between the lowest and highest possible output. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–79 © 2025 Fireye...
  • Page 304: Notice, Warranties, Exclusive Remedies, And Limitation Of Damages

    Fireye warranty, as stated in its General Terms & Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance.
  • Page 305: Update History

    Section 7: Appendix Update History Date Changes in brief version Jan 2019 General update for V1.4 Firmware. 1pt4C July 2024 North American Version 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–81 © 2025 Fireye...
  • Page 306 Section 7: Appendix ——— End of Section 7 —— 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–82 © 2025 Fireye...