Page 2
UV, UV-Self Check, and Infrared sensors, provide fast reliable scanning of most commonly burned fuels in addition Fireye Self Checking CANbus sensor may be used for simplified wiring. For exotic fuels and applications, the NX6100 is also compatible with Fireye Phoenix and Insight Integrated Flame Scanners. Seven low voltage and two-line voltage user defined auxiliary inputs provide supervision of safety critical and non-safety critical inputs.
Page 3
M20 male to ½” NPSM female adapter for NXC40 35-372 Type 2 O2 PROBES AND EXPANSION MODULE FOR NX6100 NXO2TRIM CANbus O2 interface module with Fireye and generic (4-20mA) probe inputs. NX-CAB-SET Interconnecting Cable from O2 probe to controller 33ft (10 m.) ONLY NXPK224455 O2 probe assembly (for flues 300mm to 1000mm).
Page 7
NOTE: The manufacturer of this equipment has a policy of continual product improvement and reserves the right to change the specification of the equipment and the contents of this manual without notice. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4...
Page 9
Nothing contained in this manual constitutes a warranty of any kind in respect of the machine or of the results to be achieved by its use. The only warranties given by Fireye LLC in respect of any device are those expressly given by Fireye LLC or your supplier in the contract under which it sells the device to its purchaser.
NX6220 and NX6330 OLED Display & Keypad option ..........23 The Start-up Sequence ....................29 Flame detection ......................33 Gas Safety Valve Leak Test (VPS) using FIREYE fail-safe sensors ......33 Gas Safety Valve Leak Test (VPS) using a pressure switch ........34 Modulation of the Burner .................... 35 Non-volatile lockout ....................
ON and the relays will be held in their No Alarm state, to avoid the possibility of nuisance alarms that may otherwise occur. 5 seconds after power is applied, the FIREYE splash screen (shown here) will display for 6 seconds, after which a blank white screen will show for 5 seconds.
• If you press Mute/ Reset button while the controller is in safety shutdown and the fault has cleared, the alarm will be silenced. If you press the button for more than 3 seconds, the burner will re-start. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4...
Page 19
• It will then move all drives to the P2 position of the new profile and open the appropriate main fuel valves. To exit from this operation panel and return to the overview screen, tap the Overview button. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4...
Page 26
Because you can only enter Commission mode if the burner is OFF, you cannot monitor certain safety functions such as the Fuel: Air ratio positions. For more details, see “How to go into Commission mode (Red)” in section 3, Commissioning. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-16...
Page 28
Indicates the current profile number, followed by the fuel type. Unit 1 Indicates the boiler unit address number that is used by the digital communications system and for data back-up purposes. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-18...
Page 29
The alarm Mute ‘button’ on the Touch screen is multi-functional. In normal operation, you can use this to test the alarms, by pressing the button for more than 10 seconds, after which the alarm relays will activate. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-19...
Page 31
Control panel. You can change the Set-point, PID and Limit values by tapping the value and adjusting it using the up/down arrow buttons. Tap the Menu or Home button to exit this screen. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-21...
Page 40
When the air drive(s) have reached their post purge positions then the Post Purge Time t9 is started. When t9 has elapsed, the burner motor is turned OFF and the controller returns to state 1 to wait for another startup command. 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1-30...
The NX609x Flame detectors are shuttered UV detectors, suitable for continuous operation of burner plant. Gas Safety Valve Leak Test (VPS) using FIREYE fail-safe sensors. If the gas valve leak (prove) test has been programmed and a gas profile is selected, then the controller will start the gas safety valve leak test sequence on stage 5 of the start-up sequence.
The controller has two modes of operation using the standard FIREYE modulation functions, Normal and Local. The mode of operation is set via the keypad by pushing the “Burner ON/OFF” key and selecting the mode.
– the controller does not wait for drives to position before starting the post-purge time. ——— End of Section 1 —— 1 NX6100 Fireye - Introduction V1pt4D Commissioning Manual version 1.4 1–37...
Page 49
Mounting details for the 12 Key Display option ............6 Mounting details for the Oxygen Probe Interface option ..........7 Mounting arrangements for FIREYE Boiler and Burner Sensors ......... 8 Mounting details for the NXCBH CANbus Hub and PSU........... 14 Option Link Selection in the Main Controller ..............
• Choose the servomotors carefully to make sure they operate within their specification. • Make sure all sections of the control are earthed, to maintain electrical safety. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–2...
Allow 100 mm (4 in.) for the depth of the controller including the lid and LED window. Provide additional clearance as required. The controller MUST be earthed to maintain electrical safety and ensure reliable operation. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–3...
• The screen of the CANbus cable is NOT designed to provide the earth connection for the Touch screen display. Therefore, you must make a separate earth connection using the largest cross-section area cable possible. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–4...
The clamps are put into place like this, then the hexagon cap head clamp screws (3mm AF) are tightened evenly. until the fascia plate of the HMI is tight to the panel door forming a IP65 seal to the door front surface. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–5...
The display unit MUST be earthed to maintain electrical safety and ensure reliable operation. An earth terminal is provided on the back cover of the display unit. Connect the screen of the CANbus cable to this earth connection point. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–6...
You can mount it in any orientation, either inside or outside a control cabinet. Maintain a clearance around the conduit entries to the unit to allow sufficient space for wiring Fireye. The ambient operating temperature range is specified as 0 to 60 °C (32 to 140 °F).
Section 2: Installation 1.6 Mounting arrangements for FIREYE Boiler and Burner Sensors For full technical specifications of sensors, see “Specifications” in section 6. 1.6.1 Boiler Temperature sensors Conduit Adaptor PN 35-336 The temperature sensor has a protection level of IP65 if suitable conduit glands are used, and it can be mounted in any attitude.
• a 12mm plug and socket arrangement. Example pressure sensor • Fireye ½” Conduit Adapter P/N 35-371 1.6.3 Steam Pressure Sensors When fitting the sensor, make sure that the sensor operates within its environmental specifications. An important issue is the heating effect of the steam.
Page 58
If there is any doubt that the burner casing is not a good electrical Earth, then the clamp ring must be connected to electrical ‘Earth’ using suitable cable. FIREYE recommended that the detector is mounted in a horizontal attitude. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4...
Page 60
If there is any doubt that the burner casing is not a good electrical Earth, then the clamp ring must be connected to electrical ‘Earth’ using suitable cable. FIREYE recommended that the detector is mounted in a horizontal attitude. Electrical connection is by way of a 12mm plug and socket on the square section of the body.
Page 61
Electrical connection is by way of a 12mm plug and socket on the square section of the body. The ambient operating temperature range for this device is -20 to 60 °C . 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–13...
Page 64
• For a 4-20 mA loop-power sensor, set JP4 for +30 V and JP1 to the IN position. • For a 0-5 V modulation signal, set JP4 for +5 V and JP1 to the OUT position. • For an FIREYE 1030 or 1040 sensor, set JP4 for +30 V and JP1 to the OUT position.
Page 65
CANbus Termination Link Use JP7 to select a CANbus termination resistor in or out of circuit. • In most (if not all) applications, set this link to the IN position. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–17...
All cabling that operates at more than 50 V must be multi-strand, single core, PVC insulated, 16/0.2 mm (0.5mm ) (AWG 20) and must meet the requirements of IEC 227 or IEC 225. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–19...
Page 68
If the display unit is mounted into a burner cabinet door, make sure there is a good electrical connection between the door and the main cabinet, in addition to a good electrical contact between the display unit and the door. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–20...
Page 74
CANbus PSU Hub Neutral supply 115/230V ac 24 – 40Vac CANbus In 1 CANbus PSU Hub 24Vac Supply for Servos, Display Fireye. 24 – 40Vac CANbus In 2 CANbus PSU Hub 24Vac Supply for Servos, Display Fireye. 0 – 5V...
Page 75
CANbus PSU Hub CAN + *Notes Fireye self-test sensors NX103x/NX104x Fireye self-test NX103x/NX104x and external powered 4-20mA sensors Fireye Approved Integrated scanners type: Phoenix/Insight Scanners See section 1.11.17 for details Do not use shielded wire on this circuit 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4...
Page 77
If a fuse greater than 4 A is fitted in the supply to the control panel, the burner fan output terminal must be separately fused at 4 A maximum, to protect the relay contacts from ‘welding’. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–29...
Page 79
Therefore, the cable voltage rating must exceed the maximum voltage carried by any other cable connected to the controller or run in the same conduit. • This rule applies where referred to in the text. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–31...
Page 81
Never connect the Flow input or output to Line potential. Connection of any voltage above 5 V dc to these terminals will damage the controller. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–33...
Page 82
1.10.18 Main Controller CANbus output wiring CAUTION • The total electrical load for all CANbus devices connected to the FIREYE 6000 controller MUST NOT exceed 40 VA. • Incorrect connection may damage or destroy the devices connected to the CANbus.
Page 83
‘CANbus In’ or ‘CANbus Out’. Each terminal block set has terminals 1 to 4 labelled and the ‘CANbus Out’ terminals have internal connections between the terminal numbers. The connection terminal positions are shown in the picture below. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–35...
Page 84
Section 2: Installation Connect the braided screen of each cable with the use of the screen termination clamp, at the NXCBH. The electrical scheme for the connections is shown below. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–36...
Page 87
NX6100 NX604x or NX608x Pre-assembled wiring cables. Suitable connection wires are available from FIREYE. NX224760-0050, 5m (15’) CANbus quick disconnect connection cable for pressure sensors and scanners. Refer to paragraph Error! Reference source not found. for details on CANbus wiring.
2) Clamp the braided screen between the lid and the clamp plate, with the wire tails protruding from the ‘D’ cutout as shown below. Fix the clamp plate into the sensor cap using the screws provided. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–41...
Page 90
Do NOT use shielded wire on the UV Scanner. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–42...
Page 91
NX6094/5 UVSC Pre-assembled wiring looms. Suitable connection wires are available from FIREYE. NX224760-0050, 5m (15’) CANbus quick disconnect connection cable for pressure sensors and scanners. Refer to paragraph 1.10.18 for details on CANbus wiring. 1.10.29 Photocell, I.R. Flame sensor or Volt-Free-Contact flame indication Install and wire the photocell/I.R.
Page 92
Important: There is no provision on the controller to supply power for external devices. Under no circumstances must the +30 Vdc supply be used for this purpose. Incorrect connection or application of voltage over 5 V may damage or destroy the devices being connected. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–44...
Page 93
Section 2: Installation 1.10.32 RS485 interface The RS485 interface included in the basic controller is for interconnecting several FIREYE controllers for boiler sequencing or for connecting a laptop computer during commissioning. If it is intended to make a permanent connection to a BCS or non-FIREYE equipment, then the optional daughter board should be installed, which provides communications via an isolated RS485 interface using the Modbus protocol.
Page 94
Insulation and the screen cover the conductors as much as possible. ◄── Route the screened signal cables through the clamps before terminating at connectors, as shown on the left. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–46...
• Check all metal ‘bodied’ parts of the system are correctly connected to earth. • Check that all cables where required are of the correct ‘braided screen’ specification and terminated as defined in this manual. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–50...
2.5.1 Motor requirements Only actuators supplied by FIREYE may be used with this equipment; various actuators/servomotors are available to suit different applications. The information below is intended as a general guide only. When installing or adjusting the actuators fitted to the appliance, make sure you refer to the correct instruction manual.
90°, but we recommend that it is in the range 45° to 90°. Verify that the servomotor is being stopped by the micro-switch, and not by being stalled by some mechanical limit on the valve that it is operating. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–55...
If the jumper is left in the programming position (Pins 1-2) when the controller exits to run mode, an ERR3 will be shown for the drive position, and the controller will move to Lockout. In this case you may need to repeat the Closed point setting process. 2 NX6100 Fireye - Installation V1pt4D Commissioning Manual version 1.4 2–57...
Page 107
The backup process..................... 36 Restoring commission data from the HMI............. 36 5. THE SERVICE SCHEDULE SYSTEM. Introduction ......................37 Using the Service Schedule system ..............38 6. SECTION 3 UPDATE HISTORY Commissioning Manual version 1.4 3–1 3 NX6100 Fireye - Commissioning V1pt4D...
• After entering and/or adjusting any profile points for any profile, it is the responsibility of the commissioning engineer to verify that the resulting fuel: air ratio is acceptable for the application being controlled. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–2...
9. If the electrical configuration requires interlocks to digital inputs on the FIREYE6000, then set options 16.x, 18.x and 19.x to configure the response of the input and the display message. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–3...
Curve Set". You can have up to four separate Profiles stored in the Fireye system, but it is not common to use all four. For example, you might have one Profile for gas and one for oil; or you may set up a full-power profile for 10MW output, and a reduced-power profile for 6MW output.
Page 112
2: Then you can test and fine-tune the profile in Adjust Ratio mode with the burner ON. In this mode you can then go to any set point in the sequence as required. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–6...
Section 3: Commissioning How to Commission using the Touch screens The Touch Screen used on many installations of the FIREYE system. The Touch-screen option is a more advanced interface than the text display and is much easier to use. Note: never use a sharp object such as a biro, pencil or metal stylus to operate the touchscreen. This could damage the screen, which would then not be covered by warranty.
If the background is RED, then the burner is still OFF, and you are in Commission mode, not Adjust Ratio mode. • Exit from Commission mode as described above. You will then return to the main screen. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–9...
Page 118
For example, this allows you to put a boiler on Standby SP2 for scheduled time zones during the week when full output is not required, then bring it up to full output SP1 during other time zones, and OFF if you don't need output on Sundays. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–12...
Page 119
ON. To switch off, tap again. 10) When you have finished, tap the X button at the top right of the tab pane. This returns you to the Burner Settings > Drives tab. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–13...
Fine Adjust mode. After you have entered or changed the required values, you can exit to Run mode by tapping RUN followed by ENTER. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–17...
Description 'text' button On the left of the screen is the name of the Control Input, e.g. HIGH WATER, Low Water Fireye., which describes the measurement point on the plant. The text button sets the text for each on-screen indication on the left. In the screen shot above, the text for the first indicator is "HIGH WATER";...
• If a VSD (Variable Speed Drive) is controlling the combustion air fan, then increase the speed of the fan to maximum. Tap to select the VSD box (labelled FAN) and use the UP arrow to increase the speed. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–19...
Page 126
• After you have completed all the profile points to build the curve, tap RUN and then ENTER. The system exits Commission mode back to Run mode, and then the system automatically modulates the burner according to the profile. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–20...
If you entered the correct passcode, the display top line will show COM, and the next line will show which represents the Closed position set point. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3-21...
ENTER key to store the new value. • Repeat the process to select another Option parameter and set or adjust the values as necessary. When you have finished, exit from Option Set mode. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–22...
Sets the SITE Passcode – a 3-digit code that allows access to change a 00.1 0-999 limited selection of parameters. 00.2 Used to assign a unique FIREYE serial communications address if 0-15 required. 00.3 Set to 1 to reset hours run for all fuels. Hours will be reset to 0 when the burner starts to modulate.
Page 136
• If a non-volatile lockout occurs, the set points are kept in the same way as for a controlled shutdown. It will be necessary to remove all faults before moving further than step 2. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–30...
P7 is stage 5 output ON – PD4. After P8 is displayed, press [Run] and then [Enter] to exit Commission mode. DO NOT adjust the air damper position for P8. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–33...
Page 140
In Adjust Ratio mode, the controller operates in a similar manner to other NX6100 series controllers, but the number of Solenoids is fixed for each set point position. The Air Damper position can be adjusted Open or Closed at each set point position. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–34...
Page 141
16.9 Oil Valve Switch Point is set to zero). 7) Confirm the combustion is safe and reliable. 8) Repeat steps 3 to 7 for all stages including High Fire. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–35...
If the CAN addresses of all devices on the bus match those in the restored backup, then the controller will allow the burner to start and run without further intervention. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–36...
With the Service System activated and an item due date reached a ‘Service Due’ message will appear in the banner line at the top of the screen. This is a prompt to the user to call for a service visit. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–37...
In the Setup screen the service items are shown along with the service due date and the time period in which the item should be checked. These can only be adjusted if the Commission or Adjust passcode has been entered in the burner adjust screen. 3 NX6100 Fireye - Commissioning V1pt4D Commissioning Manual version 1.4 3–38...
If the values do not match those stored in memory, a positioning fault is given, and the controller performs a non-volatile lockout. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–2...
The inverter drive unit has a closed position (4 mA), a maximum position (20 mA), a pre-purge position, an ignition position and up to 20 profile positions. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–4...
There is a calibration port located in the back of the probe, which is sealed with a screw. You must keep this port sealed during normal operation, for safe and accurate performance. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–6...
Mounting the probe with the flange horizontal (2) is acceptable. Inverted probe mounting is not acceptable. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–8...
Page 157
100 °C. (212 °F) The maximum flue gas temperature rating is 540 ºC. (1,004 °F) 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–9...
Page 158
It can also provide closed loop oxygen trim control if required. The cabling between the NXO2TRIM oxygen probe interface and the NX6083-X probe consists of the following:- 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–10...
7. When the value displayed for option 30.1 (42.1) has settled to a value within range, scroll back to Option 30.6 (42.6), change the display to zero and then press Enter. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–11...
• The only customer-replaceable items are the flue thermocouple and the oxygen filter. • Refitting is the reverse of the removal procedure. Make sure that the screws are tightened sequentially and evenly. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–13...
• When the screws and washers have been removed, pull the sample tube away from the body to allow the captive filter assembly to be removed. • You can now insert the new filter assembly (Fireye number 19-117) into the sample tube, with the beveled side to the probe body.
• The flow for each profile position must be programmed to ensure correct operation. The flow value can either be measured for each profile position or calculated as a percentage of the flow at High Fire. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–15...
Page 164
Go into Adjust Ratio mode with oxygen trim disabled as outlined above. 1. Select the High Fire position. The display will then show A(n), where n is the number of the High Fire profile point. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–16...
Page 167
Fire) is stored in Option 30.7. Also, Option parameter 30.5 (oxygen trim enable) is set to zero. IMPORTANT: BEFORE ENABLING TRIM, USE ADJUST RATIO MODE TO MANUALLY CHECK THE CALCULATED FLOW VALUES, OXYGEN SET POINTS AND TRANSPORT DELAY. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–19...
Page 168
Fire set point as a value of 99.9(%). ● Typically, the transport delay will be 15 to 40s depending upon the size of the boiler. 4 NX6100 Fireye - VSD, Oxygen and CO Trim V1pt4D Commissioning Manual version 1.4 4–20...
If power is removed from the controller while a fault is still present, the fault will be stored in non-volatile memory. When power is restored to the controller, the fault number will still be present, and you will need to clear the fault before restarting the burner. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–2...
128 events/faults and the associated status data. However, the Touch screen display will store thousands of events. You can see the full set using the Fireye ComFire2 software interface to a Windows PC or laptop.
Page 191
This is the file size (in bytes) of the currently running manufacturer / user program. If a user program is selected, this should match the program size (in bytes) given by the ‘Fireye Abacus’ program. EK78 Second cell temp (ºC) The internal zirconia cell temperature of the second oxygen probe see EK72.
Page 200
In extreme cases, you may need to increase the inverter error tolerance to prevent non-volatile lockouts caused by positioning faults (set option 9.1 = 1). This must only be changed if an inverter error of 55 will not cause unsafe combustion. 5 NX6100 Fireye - Fault Finding V1pt4D Commissioning Manual version 1.4 5–30...
HOURS RUN display will be reset and the option parameter automatically returns to 0. Additionally, the counters of burner cycles and burner lockouts will be cleared (see Engineer's Key Data numbers 90 and 91). 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–2...
Page 234
This is important when oxygen trim is enabled for a particular drive, because it determines the trim direction. Selection of fuel trim or air trim is made with option parameters 31.1 to 31.4. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–10...
Page 235
The profile can be re-commissioned by using the NEXT / ENTER keys in Commission Ratio mode to verify all points on the combustion curve. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–11...
Page 236
• If a drive has been added or removed from a profile, then it is recommended that the specified profile is erased (using option parameter 45.X) before an attempt is made to re-commission it. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–12...
Page 239
At the end of the ignition hold time, the burner will move to Low Fire. The ignition hold time will not start until the main ignition time has elapsed. A flame must be detected, or a safety shutdown will occur. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–15...
Page 242
The inverter should also be able to move from maximum to zero speed in the same time. If this is not the case, adjust the time settings in the inverter to ensure the times to accelerate and decelerate are the same. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–18...
Page 243
Set this parameter if the controller is required to control the speed of a VSD driven oil pump and there is a requirement to keep the oil circulating when the burner is OFF, in order to maintain the correct oil temperature in preparation for a call for heat. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–19...
Page 244
Option 10.0 - Gas pressure select (0 - 4) If an Fireye gas pressure sensor is connected to the system, its type and units must be entered here. Be sure to set these options before setting the value of Opt 43.4.
Page 246
The gas valves will be energized for just under 4 seconds. The gas valves will be energized for just under 5 seconds. The gas valves will be energized for just under 6 seconds. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–22...
Page 247
If in any doubt about the flame threshold being set, please consult with the burner supplier, as a very low threshold may increase the possibility of a hazardous condition. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–23...
Page 248
Alternatively, when both flame inputs are active, you can set a pilot or zero threshold for either device to ignore the flame, provided that a flame is detected on the other device. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–24...
Page 250
The Flame2 Photocell / IR input is monitored for all profiles. The Flame2 Photocell / IR input is monitored for Gas profiles only. The Flame2 Photocell / IR input is monitored for Oil profiles only. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–26...
Page 251
Alternatively, when both flame inputs are active, you can set a pilot or zero threshold for either device to ignore the flame, provided that a flame is detected on the other device. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–27...
Page 252
When used for an alarm function, the relay will de-energize when in the fault condition, so you need to wire an alarm bell in series with the normally closed contacts. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–28...
Page 253
When used for an alarm function, the relay will de-energize when in the fault condition, so you need to wire an alarm bell in series with the normally closed contacts. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–29...
Page 255
Install an electrical link between terminals PE11 (MV2 output) and PE12 (Pilot output). Set option 14.4 to a value of 1, which ensures that MV1 is energized at the same time as the Pilot. Set option 14.5 to a value of 2. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–31...
Page 256
This parameter affects all profiles whether they fire gas or oil. Option 14.7 – Aux / Oil Pump Relay Function. (0 - 6) Setting this parameter as shown in the table below configures the function of output PE6. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–32...
Page 257
FAN output be used to open the electrical connection between the air pressure/flow switch and the control, since this would not verify the correct operation of the air pressure/flow switch. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–33...
Page 258
This value will normally be left at zero. It is the measured value to be displayed when the sensor connected is at its minimum value. For NX1030 and NX1034 fail-safe sensors, this value must be left at zero. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–34...
Page 259
Bumpless transfer allows the controller to switch from Manual to Automatic mode or vice versa, without the control output suddenly 'bumping' to a different value. This parameter only affects the burner operation while in Manual mode. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–35...
Page 260
You can use this function to prevent the burner from having to go OFF when the demand is low, meaning that it is ready to respond immediately to a sudden increase in demand; no pre-purge is required. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–36...
Page 261
Option 16.4 – High voltage Input 13 Alarm / Lockout Function (0 - 360) This option parameter works identically to option parameters 18.1 to 18.9, except that it relates to the high voltage input 13, PE8. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–37...
Page 262
Option 16.7 – Oil Gun Blow-out time (0 - 30 s) This option defines the length of time that the PE6 terminal is ON when Option 14.7 = 3 - Steam purge valve for Oil gun. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–38...
Page 271
The input numbers are as specified in option parameter 20.0 above. Values 21 to 36 invert the function. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–47...
Page 272
A value of 0 means no proportional band – the burner would stay at High Fire until the set point is reached, then drop to Low Fire. Proportional control is therefore needed to prevent the measured value from overshooting the set point. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–48...
Page 273
This is the zero value for the remote set point function specified by option parameter 20.7. Option 21.9 – Remote Set point 1 span (20 mA) value (0 - 999 / 00.0 - 99.9 / 0.00 - 9.99) 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–49...
Page 275
This defines the address of the first Lag to be selected if this controller is the Lead. Option 24.2 - 2nd Lag communications address (0 – 15) This defines the address of the second Lag to be selected if this controller is the Lead. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–51...
Page 278
Set this option to the value that a 20mA output will represent. For example, value of 200 may be better suited for a maximum Flue Gas Temperature to ensure best resolution. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–54...
Page 281
As soon as the measured oxygen reading begins to change, stop the timer. Set the option parameter to the recorded timer value in seconds. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–57...
Page 283
When a second oxygen monitoring system is used, the oxygen can be considered fail-safe, and the trim limits can be set up to 50% instead of 25%, provided the maximum time between probe calibrations does not exceed six months. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–59...
Page 284
The accuracy of the calculated efficiency and the ‘Automatic Trim commissioning’ procedure will be adversely affected by this. It maybe that these functions should not be used, in which case these values should be entered as zero. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–60...
Page 285
If the burner is firing, you can only adjust the option parameter that relates to the selected profile. If the burner is not firing, you can adjust the low alarm value for any profile selection. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–61...
Page 286
Options 38.1 to 38.4 - Oxygen low alarm values at Low Fire (0.0 – 99.9%) Options 39.1 to 39.4 - Oxygen low alarm values at High Fire (0.0 – 99.9%) 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–62...
Page 288
Option 42.6 – Second oxygen probe calibration enable (0 to 2) This option is identical to option 30.6, except that it relates to the second oxygen probe. Note, the calibration gas concentration used must be as entered in option parameter 30.3. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–64...
Page 289
Option 42.2 – CO trim gain (0 – 250) CO trim gain sets the rate at which the CO trim acts – modifies the O2 Set point. Fireye recommends setting this parameter to a value of 10% initially, and then adjusting to suit the application response.
Page 290
Where a CANbus gas pressure sensor is used for the VPS and operating limits select the serial number of the device from those offered, in a similar way to selecting actuator serial numbers for Option 3.x. Options 11.x set the span and VPS test characteristics. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–66...
Page 291
This option clears the current the fault history. Set the option parameter to 1 then press RUN then ENTER. The controller will erase the fault history and return to Run mode. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–67...
Page 292
IMPORTANT: If you select 5, all profile set points will be deleted and all option parameters will reset to default values. The controller will be initialized to the factory default settings. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–68...
Page 293
If the non-standard passcode is forgotten then a ‘master passcode’ will need to be obtained, based on the unit serial number. This can be obtained using an on-line passcode system maintained by Fireye. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4...
A closed vessel in which water is heated, steam is generated, steam is superheated, or any combination thereof, under pressure or vacuum by the application of heat from combustible fuels, electricity, or nuclear energy. 7 NX6100 Fireye- Appendix V1pt4D Firmware issue 1.4 7–70...
Page 296
A general term to cover Commission Ratio and Option Set modes - with a red touch screen background. ComFire2 ComView is a software tool from Fireye, used for viewing and handling the NX6000 controller settings by means of a PC or laptop, via a USB interface cable.
Fireye warranty, as stated in its General Terms & Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance.
Need help?
Do you have a question about the NEXUS NX6100 and is the answer not in the manual?
Questions and answers