olympia electronics LLB-26/90/WL Manual

Advertisement

SELF TESTING MAINTAINED EMERGENCY LUMINAIRIES WITH WIRELESS COMMUNICATION
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
TX/RX FREQUENCY RANGE
TX POWER
BATTERY (Ni-MH)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
LIGHT SOURCE INTENSITY (Mains/emerg.)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
VIEWING DISTANCE
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS (LxHxW)
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places
where emergency luminaires are needed.
Each luminaire must be permanently
connected to mains power supply. In
normal operation the led strip lights and
the battery is charging. In
m a i n s
p o w e r
l u m i n a i r e
w i l l
automatically in emergency mode. When
the mains power supply is restored the
device turns to normal operation.
Manual Operational Test
By pressing the test button briefly (less
than 5 seconds) an emergency operation
test is performed. The white LEDs will be
lit for approx. 3 seconds, the red LED will
flash during this test sequence.
Page 1 from 7
LLB-26/90/WL LLB-26/180/WL
6W/6.4VA (PF=0.94)
4.8V/1.2Ah
Charge LED, Lamp fault LED, Battery Fault LED, TEST button
90 min
230lm/300lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3,
EN 1838, ETSI EN 303 446-1 V1.1.0, ETSI EN 300 220-2 V3.1.1
26m
287 x 205 x 55 mm
876gr.
Thank you for your trust in our products
Olympia Electronics - European manufacturer
case
of
s u p p l y f a i l u r e
l i g h t t h e l e d s t r i p
(for
LED MODULE Specs. see page 4)
LLB-40/90/WL
220-240V AC/50-60Hz
7W/7.4VA (PF=0.94)
868.150-868.450MHz
11dBm
4.8V/1.2Ah 4.8V/2.4Ah
From overcharge and deep discharge
180 min
90 min
White LEDs
230lm/123lm
370lm / 300lm
5 to 40 C
Up to 95%
Aluminum, ABS/PC, PC, Plexiglass
435 x 280 x 55 mm
1396gr.
3 years (1 year for the battery)
Automatic Operational Test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
a
t h e
Manual Autonomous Test
By pressing the test button for between 5
and 10 seconds a battery condition test is
performed. This test will last for the stated
duration and can only be performed when
the battery is fully charged (steady green
LED). The white LEDs will be lit and the red
LED will flash during this test sequence.
LLB-40/180/WL
LLB-64/90/WL
9.3W/9.8VA (PF=0.94)
4.8V/2Ah
24 h
180 min
90 min
600lm / 500lm
IP44
o
40m
673 x 400 x 55 mm
1503gr.
1650gr.
923026009_09_001
LLB-64/180/WL
4.8V/4Ah
180 min
64m
2777gr.

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the LLB-26/90/WL and is the answer not in the manual?

Questions and answers

Summary of Contents for olympia electronics LLB-26/90/WL

  • Page 1 TYPICAL WEIGHT 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products Olympia Electronics - European manufacturer GENERAL Automatic Operational Test These luminaires are used in places This test includes all the operations that where emergency luminaires are needed.
  • Page 2 Automatic Autonomous Test INSTALLATION The Automatic Autonomous Test measures install luminaire follow the device’s back up operation and installation instructions on page 4. emergency duration. This test is conducted automatically every 6 months. In order to ΑΤΤΕΝΤΙΟΝ!!! be performed, the mains power supply and 1.
  • Page 3 Button functionality: Wireless Communication The on-board button has the two following indications (interior) functions: The top LED (LD3-green) indicates the 1. Short press (<2"): a status message will network connection status. be sent to the Gateway device of the wireless network. This LED may blink according to the 2.
  • Page 4: Installation Instructions

    Non-maintained (*) First, hand tighten it and then, operation use pliers to tighten it little bit more (not all the way). LED MODULE CHARACTERISTICS LLB-26/90/WL-LLB-26/180/WL LLB-40/90/WL-LLB-40/180/WL LLB-64/90/WL-LLB-64/180/WL Olympia Electronics S.A Manufacturer Model Number 2405185 0204185 2605185+2705185 Voltage Range 14 - 16.5VDC...
  • Page 5: Mounting Methods

    MOUNTING METHODS SURFACE MOUNTING ON A WALL (single side luminaire) 2 Mounting screws Bolt Place the included mounting screws in these holes of the plastic bracket Aluminum bracket Figure 1 Plastic bracket Figure 2. Side view Figure 3. Front view GENERAL!! Measure the distance of the mounting holes and after the drilling place on these spots the mounting plugs...
  • Page 6: Alternative Mounting Methods

    ALTERNATIVE MOUNTING METHODS FLAG MOUNTED ON A WALL (double side luminaire) A-1135 SET, ONLY FOR LLB-26 (OPTIONAL AFTER REQUEST) HANGING INSTALLATION (double side luminaire) A-1136 SET, ONLY FOR LLB-26 & LLB-40 (OPTIONAL AFTER REQUEST) INSTALLATION PICTOGRAMMS 1. Unfasten the two screws of the luminaire 2.Insert the pictogramm after removing and remove the top part of the luminaire.
  • Page 7: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Llb-26/180/wlLlb-40/90/wlLlb-40/180/wlLlb-64/90/wlLlb-64/180/wl

Table of Contents