GENERAL!!
Measure the distance of the
mounting holes and after the drilling
place on these spots the mounting
plugs and fasten the base with the
mounting screws.
LED MODULE CHARACTERISTICS
Manufacturer
Model Number
Voltage Range
Nominal Power
Connections
Non reversible connection between main pcb and led module
Temperature (tc)
Battery replacement process
1
1 Power off the device
2 Dismantle the luminaire by pushing the lock/unlock hooks on each side and pull it down.
3 Remove the old battery and install the new battery's connector to the appropriate P.C.B
connector.
4 Place upwards the luminaire until the plastic hooks are securely locked.
5 Power on the device.
The light source contained in this luminaire shall only be replaced by the
manufacturer, or his agent, or a similar qualified person.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
(*) Maintained operation: The luminaire lights its illumination
X: Self contained
source, when it is powered by the mains power supply or not.
1: Maintained (*)
Non-Maintained operation: The luminaire lights its illumination
A: Including test device
source, only in power supply's failure.
G: Internally illuminated safety sign
180: 3 hour duration
Page 4 from 4
A-1130, A-1131, A-1132 SET
(OPTIONAL AFTER REQUEST)
Α
Tube
Α=1m
Α-1130
Α=0.5m
Α-1131
Α-1132
Α=0.25m
PLD-25/NiMH
olympia electronics S.A
0409153
11-14V DC
780mW
45 °C max. across the board
3
2
922502500_09_001
PLD-25/NiMH
SELF TESTING MAINTAINED EMERGENCY
TECHNICAL CHARACTERISTICS (for LED MODULE SPECS. see page 4)
Mains voltage
Maximum power consumption
Battery (Ni-MH)
Battery protection
Indications / Control
Recharging time
Minimum emergency duration
Light source intensity (230V / emerg.)
Viewing distance
Degrees of cover protection
Produced in accordance with
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3, EN 1838
Operation temperature range
Relative humidity
Construction materials
External dimensions (LxWxH)
Typical weight
Guarantee
Thank you for purchasing this product of
Olympia Electronics. A European manufacturer.
GENERAL
These luminaires are used indoors (ta 40 C)
where emergency light is needed.
E a c h l u m i n a i r e m u s t b e p e r m a n e n t l y
connected to mains power supply.
In normal operation the led strip lights and the
battery is charging.
In case of a mains power supply failure the
luminaire will light the led strip automatically in
emergency mode (powered by its battery).
When the mains power supply is restored
the device turns to normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 2,3,4.
Battery charging
The battery charging is completely controlled.
Therebuy,
the
best
possible
battery
maintenance is achieved, as well as the
elongation of its duration. When the battery has
completely
charged,
it
charges
with
maintenance current.
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost
its energy. During this operation the luminaire
enters the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Manual Test
This test can be done by pressing the test
Page 1 from 4
High Quality European based Manufacturers
LED
ILLUMINATION SIGN
220-240V AC/50-60Hz
3.5W / 4VA
3.6V/1.5Ah
Overcharging and full discharging protection
Charge LED, Lamp Fault LED, Battery Fault LED / Test button
24h
3h
90lm / 100lm
26m
IP 44
o
5
to
40 C
up to 95%
Fire retardant ABS, plexiglas
280x49x209mm
890gr.
3 years (1 year for the battery)
button. The light source and the emergency
circuit of the device is monitored. The manual
test can be conducted only if the main power
o
supply and the battery is connected. During
this test period all indication LEDs are OFF.
Automatic operational test
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the main power supply and the
battery should be connected.
Automatic Autonomous Test
The Automatic autonomous Test is conducted
and measures the device's back up operation
and emergency duration. This test is conducted
automatically every 6 months. In order to be
performed, the main power supply and the
battery should be connected and fully charged.
If the battery is not fully charged, the test is
postponed until the battery is
charged. If during this test, the autonomy is
less than nominal then the battery fault led
a
turned on continuously and the battery must be
replaced.
Back Up Operation
The autonomous duration of battery during
emergency mode is at least the one that is
stated in the list of the technical characteristics.
During emergency mode, a light source test is
also performed.
Resetting Errors
Push the Test button for more than 5 seconds,
to delete all the indicated LED errors. Then the
922502500_09_001
completely

Advertisement

loading

Summary of Contents for olympia electronics PLD-25/NiMH

  • Page 1 Thank you for purchasing this product of button. The light source and the emergency Temperature (tc) 45 °C max. across the board Olympia Electronics. A European manufacturer. circuit of the device is monitored. The manual GENERAL test can be conducted only if the main power Battery replacement process supply and the battery is connected.
  • Page 2 device enters regular operation mode. Blink (With Charge LED ON): Autonomy or MOUNTING METHODS Changing the operating mode low battery problem (the battery must be Press and hold the TEST button for more replaced). FLAG MOUNTED ON A WALL than 5 seconds. The luminaire will erase first Blink (With Charge LED Off): No charging the errors (3 LED indicators will light in current or disconnected battery.