ADDRESSABLE WATERPROOF SELF TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places where
emergency luminaires are needed. Each
luminaire must be permanently connected to
mains power supply. In normal operation (L1
connected to L) the led strip lights and the battery
is charging. In case of a mains power supply
failure the luminaire will light the led strip
automatically in emergency mode (powered by its
battery). When the mains power supply is
restored the device turns to normal operation.
Address Operation
The luminaires can be connected to a GR-6500
address panel. For address operations refer to
the installation manual of the panel.
For address module connections see page 3.
For dip-switch addressing selection see page 4, 5
and 6.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
Battery Charging
The battery charging is completely controlled. In
this case, the best possible battery maintenance
is achieved, as well as the elongation of its
duration. When the battery has completely
charged, it charges with a maintenance current.
Page 1 from 5
GR-938/4P/ADR GR-939/4P/ADR GR-938/6P/ADR GR-939/6P/ADR
4W/7.5VA
4.8V/1.5Ah
90min
4 white power LEDs
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
940gr.
Thank you for your trust in our products
Olympia Electronics - European manufacturer
(for LED MODULE Specifications see page ) 5
220-240V AC/50-60Hz
5W/7.7VA
4.8V/3Ah
From overcharge and deep discharge
Charge, lamp fault, fault indication LED
24h
180min
175/350lm
IP65
5 to 40 C
Up to 95%
Bayblend FR3010, transparent polycarbonate
363 x 145 x 73 mm
1030gr.
3 years (1 year for the battery)
Battery Cut-off
The luminaire enters in this operation when the
mains power supply fails and battery has lost its
energy. During this operation the luminaire enters
the idle state and battery consumption is
negligible, in order to be protected from deep
discharge.
Manual Test
This test can be done by pressing the
TEST/RESET button briefly (page 3). The light
source and the emergency circuit of the device is
monitored. The manual test can be conducted only
if the mains power supply and the battery is
connected. During this test period all indication
LEDs are OFF.
Tests
Normally the illumination source and the autonomy
tests are programmed by the control panel and the
test results are sent to the control panel.
If the luminaire is not connected to GR-6500
panel, the following automatic tests executed:
Automatic operational test
This test includes all the operations that provide
the manual test and is conducted automatically
every 15 days. In order to be performed, the mains
power supply and the battery should be
connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted and
5.9W/8.4VA
6W/8.5VA
4.8V/4Ah(Ni-MH)
90min
180min
6 white power LEDs
245/480lm
o
1080gr.
923939013_09_004

Advertisement

loading

Summary of Contents for olympia electronics GR-938/4P/ADR

  • Page 1 ADDRESSABLE WATERPROOF SELF TESTING MAINTAINED EMERGENCY LUMINAIRES WITH WHITE LEDs TECHNICAL CHARACTERISTICS (for LED MODULE Specifications see page ) 5 GR-938/4P/ADR GR-939/4P/ADR GR-938/6P/ADR GR-939/6P/ADR OPERATION VOLTAGE 220-240V AC/50-60Hz MAXIMUM POWER CONSUMPTION 4W/7.5VA 5W/7.7VA 5.9W/8.4VA 6W/8.5VA BATTERIES (Ni-Cd) 4.8V/1.5Ah 4.8V/3Ah 4.8V/4Ah(Ni-MH)
  • Page 2: Labeling Explanation

    measures the device’s back up operation and Blink (With Charge LED Off): No charging emergency duration. This test is conducted current or disconnected battery. automatically every 6 months. In order to be performed, the mains power supply and the ΑΤΤΕΝΤΙΟΝ!!! battery should be connected and fully charged.
  • Page 3 INSTALLATION INSTRUCTIONS FOR WALL OR CEILING MOUNTING 1 Remove the diffusor. Place a flat blade screwdriver and pull up gently the reflector. 2 Install the included plastic cover in to the unused hole and install the base plastic (with the included mounting screws and plugs).
  • Page 4 Address Dipswitch Address Dipswitch Address Dipswitch Address Dipswitch Address Dipswitch Address Dipswitch setting setting setting setting setting setting 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8 2 3 4 5 6 7 8...
  • Page 5: Warranty

    Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-938/6p/adrGr-939/6p/adrGr-939/4p/adr