olympia electronics GR-460 Quick Start Manual

olympia electronics GR-460 Quick Start Manual

Self testing maintained/non maintained emergency ceiling mounted luminaires with lens for escape route or antipanic area

Advertisement

Quick Links

Lens
GR-460
(Escape Route)
Corridor
lighting
lighting
ATTENTION!!!
During installation follow this light direction.
Autonomy Duration Selection
1
2
Dip Switch Positions
DS1
1 2
1h
(default position)
3
Autonomy duration selection
The user can select one of the 3 available minimum autonomy duration 1hour, 3hours and 8hours. The selection
must be done while the luminaire is disconnected from AC and battery supplies. The selection is achieved through
Switches 1 & 2 of DS1.
Technical label installation
Two additional labels are included in the package, one for 3 hours duration (180) and one for 8 hours duration (480).
Depending on the selected duration, the installer must cover the default 1 hour (60) printing with one that has the
required duration. Please take notice of the orientantion of the label.
Magnetic Switch Usage
Test operations with the A-1900 card (not included and available after
request).
For Manual Operational Test, you must place the card in front of the TEST
indicator and remove it immediately.
For Manual Capacity Test, you must place the card in front of TEST and
hold it for 5 to 10 seconds.
ATTENTION!!!
The light source of this luminaire is not replaceable when the light source reaches its end of life the whole
luminaire shall be replaced.
CAUTION : Do not view directly with bare eyes.
4
Battery Replacement
GR-461
It can be done only by a competent person and after the mains interruption.
(Anti-Panic Area)
1. Detach the front cover by applying pressure using a flat blade screw driver. Next, unfasten the four retaining screws
without removing them and remove the diffusor.
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type and place it in the position of the old one.
4. Replace the removed parts and power the device.
Open
area
Technical Characteristics
OPERATION VOLTAGE
MAXIMUM SUPPLY CURRENT
MAXIMUM POWER CONSUMPTION
MINIMUM POWER FACTOR (λ)
U-OUT
Prated
Irated
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT
WORKING VOLTAGE AT WHICH THE INSULATION IS DESIGNED
BATTERY (Ni-MH)
BATTERY PROTECTION
BATTERY VOLTAGE RANGE
BATTERY CHARGE CURRENT RANGE
BATTERY DISCHARGE CURRENT RANGE
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
INDICATIONS
PRODUCED IN ACCORDANCE WITH
DEGREES OF COVER PROTECTION
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
CONTROL GEAR WITH AUTOMATIC
TEST FUNCTION
Controlgear is suitable for LED module only
The controlgear has mains-connected windings of transformer
1
2
1
2
LED Characteristics
3h
8h
MANUFACTURER
MODEL NUMBER
VOLTAGE RANGE
NOMINAL POWER
CONNECTIONS
TEMPERATURE (tc)
Warranty
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is
specified in the official catalogue of Olympia Electronics and also in the technical leaflet, which accompanies
each product. This warranty ceases to exist if the buyer does not follow the technical instructions included in
official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any
repairs or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing.
Products that have been damaged can be returned to the premises of our company for repair or
replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the
buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the
buyer the transportation cost.
5
923460001_09_001
GR-460 & GR-461
220V-240V AC / 50-60Hz
25mA
5.5W / 5.6VA
0.9
10V
1h: 2.1W
3h: 0.9W
8h: 0.25W
1h: 695mA
3h: 295mA
8h: 95mA
Basic Insulation
Basic Insulation
500V
4.8V / 1.2Ah (4KRMT 15/51)
Deep discharge and overcharge protection
4-6V
100 - 130mA
1h: 460 - 645mA
3h: 190 - 280mA
8h: 70 - 115mA
23hours
1hour / 3 hours / 8 hours
1 white power LED
300lm / 1h: 320lm, 3h: 150lm, 8h: 50lm
Charge, Lamp Fault, Battery Fault, Test Magnetic Switch
EN 60598-1, EN 60598-2-22, EN 55015, EN 61547
EN 61000-3-2, EN 61000-3-3, EN62311
IP42
5 to 40°C
Up to 95%
ABS/PC, PC
158 x 158 x 60.4mm (without decorative bezel) - 195 x 195 x 60.4 (with decorative bezel)
500gr
3 years (1 year for the battery)
GR-460 & GR-461
Olympia Electronics S.A.
2806183
2.7-3.3V DC
1h: 2.1W
3h: 0.9W
8h: 0.25W
Fixed connection between main pcb and led module
65 °C max. across the board
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
info@olympia-electronics.gr
923460001_09_001
European
manufacturers
GR-460 & GR-461
SELF TESTING MAINTAINED/NON MAINTAINED
EMERGENCY CEILING MOUNTED LUMINAIRES WITH LENS
FOR ESCAPE ROUTE OR ANTIPANIC AREA
ST
Μ
NM
Light output
MAX. POWER
Duration
CONSUMPTION
SELF
Non
IP42
Maintained
1h/3h/8h
TESTING
maintained
320/150/50lm
5.5W/5.6VA
Thank you for your trust in our products
Olympia Electronics - European manufacturer
5 to
40 C
o
Ni-MH
TEMPERATURE
RANGE

Advertisement

loading

Summary of Contents for olympia electronics GR-460

  • Page 1 Test operations with the A-1900 card (not included and available after Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the request).
  • Page 2 Package Contents Installation Instructions Suspended Ceiling Luminaire Decorative Bezel Surface Mounting Mounting accessories Manual General 2. Always use in any case round mains cable, with a GENERAL These devices are used indoors (ta 40 C) in places diameter of 5-10mm (H05RN-F type 2x1mm² or where emergency luminaires are needed.

This manual is also suitable for:

Gr-461