Download Print this page

olympia electronics GR-938/30L Manual

Advertisement

Quick Links

WATERPROOF SELF TESTING MAINTAINED EMERGENCY LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Ni-Cd)
BATTERY PROTECTION
INDICATIONS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
ILLUMINATION SOURCE
ILLUMINATION (MAINS / EMERGENCY)
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used in places where
emergency luminaires are needed. Each
luminaire must be permanently connected to
mains power supply. In normal operation (L1
connected to L) the led strip lights and the
battery is charging. In
power supply failure the luminaire will light
the led strip automatically in emergency mode
(powered by
its battery). When the mains
power supply is restored the device turns to
normal operation.
INSTALLATION
To install the luminaire follow the installation
instructions on page 3.
OPERATION
Battery Charging
The battery charging is completely controlled.
Thereby,
the
maintenance is achieved, as well as the
elongation of its duration. When the battery
has completely charged, it charges with a
maintenance current.
Battery Cut-off
The luminaire enters in this operation when
the mains power supply fails and battery has
Page 1 from 4
GR-938/15L
3.4W / 3.8VA
3.6V/0.6Ah
15 white LEDs
105lm / 105lm
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
790gr.
Thank you for your trust in our products.
Olympia Electronics - European manufacturer.
case
of
a
best
possible
(for LED MODULE Specs. see page 4)
GR-938/30L
220-240V AC/50-60Hz
4.5W / 4.9VA
3.6V/1.5Ah
From overcharge and deep discharge
Charge, Lamp Fault, Battery Fault indication LED
90min
30 white LEDs
210lm / 210lm
ABS/PC, PC
363 x 145 x 73 mm
3 years (1 year for the battery)
lost its energy. During this operation the
luminaire enters the idle state and battery
consumption is negligible, in order to be
protected from deep discharge.
Manual Test
mains
The manual test can be conducted only if the
mains power supply and the battery is
connected. By pressing the TEST/RESET
button briefly (page 3) an operation test is
initiated. During this test period all indication
LEDs are OFF.
Tests
Normally the illumination source and the
autonomy tests are programmed by the
control panel and the test results are sent to
the control panel.
Automatic Operational Test
battery
This test includes all the operations that
provide the manual test and is conducted
automatically every 15 days. In order to be
performed, the mains power supply and the
battery should be connected.
Automatic Autonomous Test
The Automatic Autonomous Test is conducted
and measures the device's back up operation
GR-939/15L
3.3W / 3.7VA
24h
180min
15 white LEDs
105lm / 105lm
IP 65
o
5 to 40 C
Up to 95%
860gr.
923939100_09_013
GR-939/30L
5.3W /5.6VA
3.6V/3Ah
30 white LEDs
210lm / 210lm
930gr.

Advertisement

loading

Summary of Contents for olympia electronics GR-938/30L

  • Page 1 930gr. 3 years (1 year for the battery) GUARANTEE Thank you for your trust in our products. Olympia Electronics - European manufacturer. GENERAL lost its energy. During this operation the These luminaires are used in places where luminaire enters the idle state and battery emergency luminaires are needed.
  • Page 2 emergency duration. This test than 2 months, disconnect the battery by conducted automatically every 6 months. In pulling out the battery’s connector. order to be performed, the mains power 5. I s not allowed to discard batteries in to supply and the battery should be connected common trash bins, they must be and fully charged.
  • Page 3 INSTALLATION INSTRUCTIONS FOR WALL OR CEILING MOUNTING 1 Remove the diffusor. Place a flat blade screwdrivers and pull up gently the reflector. 2 Install the included plastic cover in to the unused hole and install the base plastic (with the included mounting screws and plugs).
  • Page 4 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.

This manual is also suitable for:

Gr-938/15lGr-939/15lGr-939/30l