Package Contents
1
Luminaire
3
Pictograms (R/L/D)
Mounting accessories
1
1
Manual
General
o
These devices are used in places
(ta 50 C)
where emergency light is needed (CBS). Each
device must be permanently connected to mains power supply.
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or testing must be done by authorized personnel
only.
2. Always use in any case round mains cable, with a diameter of 5-10mm (H05RN-F type
2x1mm² or any other type, at least equal to it's mechanical and electrical properties).
ATTENTION!! The cable must not be deformed in any way (This requirement is important to
ensure the ΙΡ rating).
Dimensional drawing:
315 x 120 x 65 mm
65
315
120
315
Installation
Α
Β
Α
To dismantle the luminaire, simply remove the difussor.
ATTENTION! If the 2 plastic latches (A) are clipped, carefully insert a flat-blade screwdriver
to unclip them. Then, gently lift the diffuser (B) upwards to detach it.
1
1
Β
Place a flat blade screwdriver to the recesses (A) and pull up gently the reflector (B) to remove it.
2
65
120
17
10
4
210
Install the two rubber gaskets to the holes of the base. Make sure that they are not deformed.
3
Wall Plug
Install the plastic base (with the included mounting accessories).
WARNING!! To preserve the IP65 rating, fit the screws with the metallic washers and rubber sealing
rings.
4
2
923192601_09_005
Α
Α
Rubber
Sealing Ring
Screw
Washer
Make a hole in the center of the rubber gasket by using a small screwdriver. Pass the
round cable through the rubber gasket. Connect the mains cable according to the
connections diagrams above. Ν for neutral, L for live wire WARNING!! Isolate the mains
power supply before making the connections.
5
6
Refit the reflector (Mind the holes of the indications).
7
8
Refit the diffusor (Mind the holes of the indications).
8
Β
The plastic latches (A) must be secured (click sound).
Fasten the 2 screws (B). (Tightening torque 1.2N*m)
9
3
923192601_09_005
N
L
N
L
Install the included tie-wrap to the adhesive
tether loop and fasten securely the power cable in
order to anchor it.
Α
Β
Α
923192601_09_005

Advertisement

loading
Need help?

Need help?

Do you have a question about the GR-1926/4P and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for olympia electronics GR-1926/4P

  • Page 1 Package Contents Luminaire Pictograms (R/L/D) Mounting accessories Manual General Α These devices are used in places (ta 50 C) where emergency light is needed (CBS). Each Make a hole in the center of the rubber gasket by using a small screwdriver. Pass the device must be permanently connected to mains power supply.
  • Page 2 Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of defection. Olympia Electronics reserves the right to charge or not the...

This manual is also suitable for:

Gr-1926/15lGr-1926/6pGr-1926/30l