Installation and maintenance instructions Contents Safety ..............4 Action-related warnings ......... 4 Intended use ............4 General safety information ........4 Regulations (directives, laws, standards) ....6 Notes on the documentation ......7 Observing other applicable documents ....7 Storing documents..........7 Validity of the instructions ........
Safety Any other use that is not specified in these instructions, or use beyond that specified in Action-related warnings this document, shall be considered improper use. Any direct commercial or industrial use Classification of action-related warnings is also deemed to be improper. The action-related warnings are classified in accordance with the severity of the possible Caution.
Page 5
▶ Ensure that the installation surface has 1.3.5 Risk of material damage caused by using an unsuitable tool sufficient load-bearing capacity to bear the operating weight of the product. ▶ Use the correct tool. 1.3.10 Excessive water pressure 1.3.6 Risk of material damage caused by frost Excessive water pressure may lead to dam- age to the product and, as a result, cause in-...
Regulations (directives, laws, standards) ▶ Observe the national regulations, stand- ards, directives, ordinances and laws. Installation and maintenance instructions 8000031435_01...
Product article number against moving horizontally and vertically. Products that are not installed are stored in the manufac- DT4-D 50 INT I 8000031383 turer's packaging. The products must be stored under stand- DT4-D 65 INT I...
Requirements for the installation site Drill the holes. Insert the rawl plugs into the holes and screw in the ▶ Select the installation site so that the cables can be eas- screws. ily routed. – Clearance between the screw and the wall: ≈ ▶...
– Connection pressure: ≥ 0.7 MPa Start-up – Pressure setting: 0.3 to 0.4 MPa Open the cold-water stopcock. Open the hot water taps. Wait until water flows out of the hot water taps. Electrical installation Close the hot water taps. Check the expansion relief valve by opening the drain Only qualified electricians are allowed to carry out the elec- cock on the expansion relief valve.
Maintenance Checking the inner vessel and components for scale deposition Checking the magnesium protection anode Disconnect the product from the power supply. (→ Page 10) Empty the product. (→ Page 11) Remove the flange. (→ Page 10) If necessary, clean the inner vessel with descaling agents or by carefully scraping it with a wooden spat- ula.
▶ Remove the mains connection lines. Emptying the product Close the cold water stop cock. Open a hot water valve connected to the product. Loosen the connection between the cold water pipe and the product. Drain the domestic hot water cylinder via the product's cold water pipe.
Appendix Dimensions and dimension drawing G ½ G ½ Dimensions DT4-D 50 INT I 555 mm 408 mm DT4-D 65 INT I 680 mm 533 mm DT4-D 80 INT I 805 mm 658 mm Technical data Filling volume Operating weight...
Technical data – General Heat insulation PU foam, CFC-free Inner vessel Steel, enamelled, with magnesium protection anode Fault display view Display Cause Troubleshooting Domestic hot water overheating (≥85 °C for Make sure that the temperature of the cold water at the cylinder's 2 seconds) cold water connection is <85 °C.
Page 14
Installation and maintenance instructions Contents Safety ..............15 Action-related warnings ........15 Intended use ............15 General safety information ........15 Regulations (directives, laws, standards) .... 17 Notes on the documentation ......18 Observing other applicable documents ....18 Storing documents..........18 Validity of the instructions ........
Safety Any other use that is not specified in these instructions, or use beyond that specified in Action-related warnings this document, shall be considered improper use. Any direct commercial or industrial use Classification of action-related warnings is also deemed to be improper. The action-related warnings are classified in accordance with the severity of the possible Caution.
Page 16
▶ Ensure that the installation surface has 1.3.5 Risk of material damage caused by using an unsuitable tool sufficient load-bearing capacity to bear the operating weight of the product. ▶ Use the correct tool. 1.3.10 Excessive water pressure 1.3.6 Risk of material damage caused by frost Excessive water pressure may lead to dam- age to the product and, as a result, cause in-...
Regulations (directives, laws, standards) ▶ Observe the national regulations, stand- ards, directives, ordinances and laws. 8000031435_01 Installation and maintenance instructions...
Product article number against moving horizontally and vertically. Products that are not installed are stored in the manufac- DT4-D 50 INT I 8000031383 turer's packaging. The products must be stored under stand- DT4-D 65 INT I...
Requirements for the installation site Drill the holes. Insert the rawl plugs into the holes and screw in the ▶ Select the installation site so that the cables can be eas- screws. ily routed. – Clearance between the screw and the wall: ≈ ▶...
– Connection pressure: ≥ 0.7 MPa Start-up – Pressure setting: 0.3 to 0.4 MPa Open the cold-water stopcock. Open the hot water taps. Wait until water flows out of the hot water taps. Electrical installation Close the hot water taps. Check the expansion relief valve by opening the drain Only qualified electricians are allowed to carry out the elec- cock on the expansion relief valve.
Maintenance Checking the inner vessel and components for scale deposition Checking the magnesium protection anode Disconnect the product from the power supply. (→ Page 21) Empty the product. (→ Page 22) Remove the flange. (→ Page 21) If necessary, clean the inner vessel with descaling agents or by carefully scraping it with a wooden spat- ula.
▶ Remove the mains connection lines. Emptying the product Close the cold water stop cock. Open a hot water valve connected to the product. Loosen the connection between the cold water pipe and the product. Drain the domestic hot water cylinder via the product's cold water pipe.
Appendix Dimensions and dimension drawing G ½ G ½ Dimensions DT4-D 50 INT I 555 mm 408 mm DT4-D 65 INT I 680 mm 533 mm DT4-D 80 INT I 805 mm 658 mm Technical data Filling volume Operating weight...
Technical data – General Heat insulation PU foam, CFC-free Inner vessel Steel, enamelled, with magnesium protection anode Fault display view Display Cause Troubleshooting Domestic hot water overheating (≥85 °C for Make sure that the temperature of the cold water at the cylinder's 2 seconds) cold water connection is <85 °C.
Page 25
Installation and maintenance instructions Contents Safety ..............26 Action-related warnings ........26 Intended use ............26 General safety information ........26 Regulations (directives, laws, standards) .... 28 Notes on the documentation ......29 Observing other applicable documents ....29 Storing documents..........29 Validity of the instructions ........
Safety Any other use that is not specified in these instructions, or use beyond that specified in Action-related warnings this document, shall be considered improper use. Any direct commercial or industrial use Classification of action-related warnings is also deemed to be improper. The action-related warnings are classified in accordance with the severity of the possible Caution.
Page 27
▶ Ensure that the installation surface has 1.3.5 Risk of material damage caused by using an unsuitable tool sufficient load-bearing capacity to bear the operating weight of the product. ▶ Use the correct tool. 1.3.10 Excessive water pressure 1.3.6 Risk of material damage caused by frost Excessive water pressure may lead to dam- age to the product and, as a result, cause in-...
Regulations (directives, laws, standards) ▶ Observe the national regulations, stand- ards, directives, ordinances and laws. Installation and maintenance instructions 8000031435_01...
Product article number against moving horizontally and vertically. Products that are not installed are stored in the manufac- DT4-D 50 INT I 8000031383 turer's packaging. The products must be stored under stand- DT4-D 65 INT I...
Requirements for the installation site Drill the holes. Insert the rawl plugs into the holes and screw in the ▶ Select the installation site so that the cables can be eas- screws. ily routed. – Clearance between the screw and the wall: ≈ ▶...
– Connection pressure: ≥ 0.7 MPa Start-up – Pressure setting: 0.3 to 0.4 MPa Open the cold-water stopcock. Open the hot water taps. Wait until water flows out of the hot water taps. Electrical installation Close the hot water taps. Check the expansion relief valve by opening the drain Only qualified electricians are allowed to carry out the elec- cock on the expansion relief valve.
Maintenance Checking the inner vessel and components for scale deposition Checking the magnesium protection anode Disconnect the product from the power supply. (→ Page 32) Empty the product. (→ Page 33) Remove the flange. (→ Page 32) If necessary, clean the inner vessel with descaling agents or by carefully scraping it with a wooden spat- ula.
▶ Remove the mains connection lines. Emptying the product Close the cold water stop cock. Open a hot water valve connected to the product. Loosen the connection between the cold water pipe and the product. Drain the domestic hot water cylinder via the product's cold water pipe.
Appendix Dimensions and dimension drawing G ½ G ½ Dimensions DT4-D 50 INT I 555 mm 408 mm DT4-D 65 INT I 680 mm 533 mm DT4-D 80 INT I 805 mm 658 mm Technical data Filling volume Operating weight...
Technical data – General Heat insulation PU foam, CFC-free Inner vessel Steel, enamelled, with magnesium protection anode Fault display view Display Cause Troubleshooting Domestic hot water overheating (≥85 °C for Make sure that the temperature of the cold water at the cylinder's 2 seconds) cold water connection is <85 °C.
Page 36
Installation and maintenance instructions Contents Safety ..............37 Action-related warnings ........37 Intended use ............37 General safety information ........37 Regulations (directives, laws, standards) .... 39 Notes on the documentation ......40 Observing other applicable documents ....40 Storing documents..........40 Validity of the instructions ........
Safety Any other use that is not specified in these instructions, or use beyond that specified in Action-related warnings this document, shall be considered improper use. Any direct commercial or industrial use Classification of action-related warnings is also deemed to be improper. The action-related warnings are classified in accordance with the severity of the possible Caution.
Page 38
▶ Ensure that the installation surface has 1.3.5 Risk of material damage caused by using an unsuitable tool sufficient load-bearing capacity to bear the operating weight of the product. ▶ Use the correct tool. 1.3.10 Excessive water pressure 1.3.6 Risk of material damage caused by frost Excessive water pressure may lead to dam- age to the product and, as a result, cause in-...
Regulations (directives, laws, standards) ▶ Observe the national regulations, stand- ards, directives, ordinances and laws. 8000031435_01 Installation and maintenance instructions...
The cylinder is equipped with external heat insulation. The Product article number cylinder vessel is made of enamelled steel. The heating ele- DT4-D 50 INT I 8000031383 ments that transfer the heat are located inside the vessel. As additional corrosion protection, the vessel has a magnesium...
Requirements for the installation site Drill the holes. Insert the rawl plugs into the holes and screw in the ▶ Select the installation site so that the cables can be eas- screws. ily routed. – Clearance between the screw and the wall: ≈ ▶...
– Connection pressure: ≥ 0.7 MPa Start-up – Pressure setting: 0.3 to 0.4 MPa Open the cold-water stopcock. Open the hot water taps. Wait until water flows out of the hot water taps. Electrical installation Close the hot water taps. Check the expansion relief valve by opening the drain Only qualified electricians are allowed to carry out the elec- cock on the expansion relief valve.
Maintenance Checking the inner vessel and components for scale deposition Checking the magnesium protection anode Disconnect the product from the power supply. (→ Page 43) Empty the product. (→ Page 44) Remove the flange. (→ Page 43) If necessary, clean the inner vessel with descaling agents or by carefully scraping it with a wooden spat- ula.
▶ Remove the mains connection lines. Emptying the product Close the cold water stop cock. Open a hot water valve connected to the product. Loosen the connection between the cold water pipe and the product. Drain the domestic hot water cylinder via the product's cold water pipe.
Appendix Dimensions and dimension drawing G ½ G ½ Dimensions DT4-D 50 INT I 555 mm 408 mm DT4-D 65 INT I 680 mm 533 mm DT4-D 80 INT I 805 mm 658 mm Technical data Filling volume Operating weight...
Technical data – General Heat insulation PU foam, CFC-free Inner vessel Steel, enamelled, with magnesium protection anode Fault display view Display Cause Troubleshooting Domestic hot water overheating (≥85 °C for Make sure that the temperature of the cold water at the cylinder's 2 seconds) cold water connection is <85 °C.
Page 47
Installation and maintenance instructions Contents Safety ..............48 Action-related warnings ........48 Intended use ............48 General safety information ........48 Regulations (directives, laws, standards) .... 50 Notes on the documentation ......51 Observing other applicable documents ....51 Storing documents..........51 Validity of the instructions ........
Safety Any other use that is not specified in these instructions, or use beyond that specified in Action-related warnings this document, shall be considered improper use. Any direct commercial or industrial use Classification of action-related warnings is also deemed to be improper. The action-related warnings are classified in accordance with the severity of the possible Caution.
Page 49
▶ Ensure that the installation surface has 1.3.5 Risk of material damage caused by using an unsuitable tool sufficient load-bearing capacity to bear the operating weight of the product. ▶ Use the correct tool. 1.3.10 Excessive water pressure 1.3.6 Risk of material damage caused by frost Excessive water pressure may lead to dam- age to the product and, as a result, cause in-...
Regulations (directives, laws, standards) ▶ Observe the national regulations, stand- ards, directives, ordinances and laws. Installation and maintenance instructions 8000031435_01...
The cylinder is equipped with external heat insulation. The Product article number cylinder vessel is made of enamelled steel. The heating ele- DT4-D 50 INT I 8000031383 ments that transfer the heat are located inside the vessel. As additional corrosion protection, the vessel has a magnesium...
Requirements for the installation site Drill the holes. Insert the rawl plugs into the holes and screw in the ▶ Select the installation site so that the cables can be eas- screws. ily routed. – Clearance between the screw and the wall: ≈ ▶...
– Connection pressure: ≥ 0.7 MPa Start-up – Pressure setting: 0.3 to 0.4 MPa Open the cold-water stopcock. Open the hot water taps. Wait until water flows out of the hot water taps. Electrical installation Close the hot water taps. Check the expansion relief valve by opening the drain Only qualified electricians are allowed to carry out the elec- cock on the expansion relief valve.
Maintenance Checking the inner vessel and components for scale deposition Checking the magnesium protection anode Disconnect the product from the power supply. (→ Page 54) Empty the product. (→ Page 55) Remove the flange. (→ Page 54) If necessary, clean the inner vessel with descaling agents or by carefully scraping it with a wooden spat- ula.
▶ Remove the mains connection lines. Emptying the product Close the cold water stop cock. Open a hot water valve connected to the product. Loosen the connection between the cold water pipe and the product. Drain the domestic hot water cylinder via the product's cold water pipe.
Appendix Dimensions and dimension drawing G ½ G ½ Dimensions DT4-D 50 INT I 555 mm 408 mm DT4-D 65 INT I 680 mm 533 mm DT4-D 80 INT I 805 mm 658 mm Technical data Filling volume Operating weight...
Technical data – General Heat insulation PU foam, CFC-free Inner vessel Steel, enamelled, with magnesium protection anode Fault display view Display Cause Troubleshooting Domestic hot water overheating (≥85 °C for Make sure that the temperature of the cold water at the cylinder's 2 seconds) cold water connection is <85 °C.
Page 60
Supplier Türk DemirDöküm Fabrikaları A.Ş. Atatürk Mahallesi Meriç Caddesi No: 1/4 34758 / Ataşehir ‒ İstanbul Türkiye Tel. 0216 516 2000 Faks 0216 516 2007 Müşteri iletişim merkezi 0850 2221833 8000031435_01 info@demirdokum.com.tr www.demirdokum.com.tr Publisher/manufacturer TÜRK DEMIRDÖKÜM FABRIKALARI A.S. 4 Eylül Mah. Osman Rusçuk Cad. No: 5 11300 / Bozüyük ‒...