Daikin EWYA006D2V3P Installer's Reference Manual page 97

Packaged air-cooled water chillers and packaged air to water heat pumps
Hide thumbs Also See for EWYA006D2V3P:

Advertisement

9.3.10 To connect the power consumption digital inputs
EWAA004~008D + EWYA004~008D
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688013-1C – 2023.05
180°
a Installation of EKRP1HBAA is required.
3 Fix the cable with cable ties to the cable tie mountings.
Wires: 2 (per input signal)×0.75 mm²
Power limitation digital inputs: 12 V DC / 12 mA detection (voltage
supplied by PCB)
[9.9] Power consumption control.
1 Open the service cover. See
2 Connect the power consumption digital inputs cable to the appropriate
terminals as shown in the illustration below.
180°
a Installation of EKRP1AHTA is required.
3 Fix the cable with cable ties to the cable tie mountings.
9
A4P
X2M
a
"7.3.2 To open the outdoor
S6S (DI4)
A8P.1
S7S (DI3)
A8P.2
S8S (DI2)
A8P.3
S9S (DI1)
A8P.4
A8P.5
a
5 4 3 2 1
X801M
A8P
Electrical installation
|
4
unit" [
 56].
Installer reference guide
97