motortronics VMX-agility Quick Start Manual

Solid state ac motor control
Hide thumbs Also See for VMX-agility:

Advertisement

Quick Links

MO T O R T R O N I C S
V M X - a g i l i t y
Q U I C K S T A R T G U I D E
MO T O R T R O N I C S
S o l i d S t a t e A C Mo t o r C o n t r o l
V MX - a g i l i t y
T M
S o l i d S t a t e A C Mo t o r C o n t r o l
A p p l i c a t i o n
C o n v e y o r
2 0 0 - 6 0 0 V , 1 7 - 3 6 1 A mp s , 3 - 3 5 0 H P
O L E D
D i s p l a y
E v e n t H i s t o r y
6
w i t h r e a l - t i m e
c l o c k
O p e r a t i o n
L a n g u a g e s
t o c h o o s e f r o m
O L
M o t o r P r o t e c t i o n
w i t h T h e r m a l
M e m o r y F e a t u r e
A P P S
2 3 P r e - l o a d e d
A p p l i c a t i o n s
t o c h o o s e f r o m
F i r e M o d e
C o n t i n u e r u n n i n g
t o d e s t r u c t i o n
i n E m e r g e n c y
S i t u a t i o n s
T M
T M
3 S
S m o o t h s t a r t a n d
s t o p w i t h s t a b l e
a c c e l e r a t i o n
a n d d e c e l e r a t i o n
C o n n e c t
2 D I / 2 D O
M o d b u s R T U
U S B
B y p a s s
I n t e r n a l B y p a s s
i s S t a n d a r d o n
a l l S i z e s

Advertisement

loading
Need help?

Need help?

Do you have a question about the VMX-agility and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for motortronics VMX-agility

  • Page 1 MO T O R T R O N I C S S o l i d S t a t e A C Mo t o r C o n t r o l V M X - a g i l i t y Q U I C K S T A R T G U I D E 2 0 0 - 6 0 0 V , 1 7 - 3 6 1 A mp s , 3 - 3 5 0 H P O L E D...
  • Page 2: Dangerous Voltage

    • VMX-agility soft starts contain dangerous voltages when connected to the mains supply. Only qualified personnel that have been completely trained and authorised, should carry out installation, operation and maintenance of this equipment.
  • Page 3: Installation

    Altitude above sea level 1000m (3281ft). Above 1000m de rate by 1% of VMX-agility i.e. per 100m (328ft) to a maximum altitude of 2000m (6562ft) Ambient Temperature Derate -20°C (-4°F) to 40°C (104°F). Above 40°C de-rate linearly by 2% of VMX-agility i.e. per °C to a maximum of 60°C (140°F). VMX-agility™ - Quick Start Guide...
  • Page 4 The VMX-agility soft start range comprises 3 frame sizes, with various weights and dimensions. See pages 5-7 for further information. Prior to installing the VMX-agility unit, the installer should carry out a risk assessment. If considered appropriate, a suitable handling device should be used.
  • Page 5 Installation (continued) Dimensions VMX-AGY-101 to VMX-AGY-113 [ ] = inch [4.25] [5.83] [3.54] Note: VMX-agility may be horizontally mounted with deration. Weight 1.97kg (3.75lb) See Horizontal Mounting Rating Fitting Tables Air Flow VMX-agility™ - Quick Start Guide P a g e...
  • Page 6 Installation (continued) Dimensions VMX-AGY-201 to VMX-AGY-209 [5.8] [9.3] [ ] = inch [3.0] Weight 6 kg [13.22LB] Fitting 100mm [3.93] 25mm [0.98] 100mm [3.93] 100mm [3.93] Air Flow VMX-agility™ - Quick Start Guide P a g e...
  • Page 7 Installation (continued) Dimensions VMX-AGY-301 to VMX-AGY-305 VMX-agility™ - Quick Start Guide P a g e...
  • Page 8: Electrical Installation

    Semiconductor fuses can be supplied as an option for short-circuit protection of the semiconductors. These fuses must be fitted externally to the VMX-agility chassis to comply with certain standards. It is the responsibility of the installer and system designer/specifier to ensure that the required standards or regulations are not affected by so doing.
  • Page 9 Electrical Installation (continued) Electrical Connections 3-Phase Electrical Supply Connections Connector (L1, L2, L3) RJ45 connector (Modbus RTU) Control Terminals AC Induction Motor Connections Mains Circuit Wiring Diagram (T1, T2, T3) VMX-agility™ - Quick Start Guide P a g e...
  • Page 10: Electrical Connection

    Electrical Installation (continued) Single Phase Operation VMX-agility soft starts may be operated with a single-phase supply and motor. The base rating of the unit is unchanged. Electrical Connection For single phase operation the mode of the soft start must be set correctly in the Advanced menu: VMX-agility™...
  • Page 11 In Fire Mode all trips are disabled. Digital Outputs13,14, 21,22 Selectable Functions The outputs may be mapped to Run, Auto Reset Pending, Auto Reset Exceeded, Breaker, PH/SCR, End of Start and Fault. VMX-agility™ - Quick Start Guide 10 | P a g e...
  • Page 12 Note: 110 – 230V control supply possible with optional control supply module (VMX-AGY-021) 2-Wire Control Wiring Diagram Note: 110 – 230V control supply possible with optional control supply module (VMX-AGY-021) VMX-agility™ - Quick Start Guide 11 | P a g e...
  • Page 13: Motor Overload

    VMX-agility provides full motor overload protection, configurable through the user interface. Overload trip settings are determined by the Motor Current setting and the Trip Class setting. Trip class choices are Class 10, Class 20, and Class 30. The VMX-agility soft starters are protected using full I T motor overload with memory.
  • Page 14: Configuration & Parameters

    All keys active Left & Right keys active Right, Down & Centre keys active Note: A flashing centre button indicates that a menu item may be selected or saved. VMX-agility™ - Quick Start Guide 13 | P a g e...
  • Page 15: Operation Local Motor Start

    Application Application Application Application Application Woodchipper (Centre button to adjust) Cntrl Funct Motor Amps Application Cntrl Mode Application Auto Setup 22 A Pump 1 Pump 1 Two Wire Remote VMX-agility™ - Quick Start Guide 14 | P a g e...
  • Page 16 Shredder Wood Chipper Compressor 1 = Centrifugal, Reciprocating, Rotary Screw Compressor 2 = Rotary Vane, Scroll Pump 1 = Submersible: Centrifugal, Rotodynamic Pump 2 = Positive Displacement: Reciprocating, Rotary VMX-agility™ - Quick Start Guide 15 | P a g e...
  • Page 17 Rated conditional short-circuit current and type of co- See Short Circuit Protection Tables for rated ordination with associated short circuit protective conditional short-circuit current and required device (SCPD) current rating and characteristics of the associated SCPD VMX-agility™ - Quick Start Guide 16 | P a g e...
  • Page 18 (normally open) Form B – Single gap break-contact 21, 22 (normally closed) Auxiliary Circuit Resistive load, 250Vac, 2A. Utilization category, voltage rating, current rating Cosø =0.5, 250Vac, 2A Continued over VMX-agility™ - Quick Start Guide 17 | P a g e...
  • Page 19: Type Designation

    The current limiting function and phase loss protection is limited to the ramping period only. Electronic Overload Relay Current Settings Frame Size Size 1 Size 2 Size 3 Type Designation Min A Max A VMX-agility™ - Quick Start Guide 18 | P a g e...
  • Page 20 Main Supply Voltage 4 – 200 Vac to 480 Vac, Ui 480 Vac 6 – 200 Vac to 600 Vac, Ui 600 Vac VMX-Agility™ model rating designation See Rating Table VMX-agility™ - Quick Start Guide 19 | P a g e...
  • Page 21: Environmental Specifications

    Humidity max 85% non-condensing, not exceeding 50% @ 40°C [104°F] Maximum Altitude 1,000m [3281ft]; above 1000m derate by 1% of VMX-agility I e per 100m (328ft) to a maximum altitude of 2,000m (6562ft) Environmental Rating Main Circuit: IP00 (IP20 with optional finger guards);...
  • Page 22 ___ or by a Circuit Breaker with a Maximum Rating of ___Z ___. # 2. Correctly selected semiconductor fuses can provide additional protection against damage to the VMX-agility unit (This is sometimes referred to as type 2 co-ordination). These semiconductor fuses are recommended to provide this increased protection.
  • Page 23 Maximum fuse rating Z UL Listed inverse- Maximum time delay circuit rating Z breaker Short Circuit Protection for 65kA Fault Current – VMX-agility Frame Size 2 & 3 Type designation (VMX-AGY-) Rated operational current Rated conditional short circuit current at 200 –...
  • Page 24 For VMX-AGY-101 to VMX-AGY-209, duty cycle F-S = 90-5, however more cycles per hour are possible with optional fan fitted as indicated in Fan option table. For VMX-AGY-301 to VMX-AGY-305, duty cycle F-S = 90-3 for more cycles consult Motortronics or supplier. VMX-agility™ - Quick Start Guide...
  • Page 25 WARNING: this product and associated accessories may contain chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm. For more information visit https://p65warnings.ca.gov VMX-agility™ - Quick Start Guide 24 | P a g e...
  • Page 26 MO T O R T R O N I C S S o l i d S t a t e A C Mo t o r C o n t r o l V M X - a g i l i t y A p p l i c a t i o n D r i v e n C o m p a c t S o f t S t a r t e r P h a s e t r o n i c s , I n c .