Advertisement
Solis S6 Single Phase Inverters integrate DRM and backflow power control function, that could suitable for smart grid requirement.
This manual covers the S6 Single Phase Inverter model listed below:
S6-GR1P7K03-NV-ND, S6-GR1P8K03-NV-ND, S6-GR1P9K03-NV-ND, S6-GR1P10K03-NV-ND
When you receive the inverter, please ensure that all the parts listed below are included:
If anything is missing, please contact your local Solis distributor.
If the inverter is not to be installed immediately, storage instructions and environmental conditions are below:
There are four indicators on the Solis S6-GR1P(2.5-6)K-S Series Inverter(Power, COM, CT/Meter and Bluetooth) which indicate the working status of the inverter.
NOTE:
NOTE:
Long press the Power button for 5 seconds to reset the bluetooth connection passwords. If the reset is successful, the Power button will be flashing in Blue color and in 0.5s interval for 3s. If the reset is failed, the Power button will be flashing in Yellow color and in 0.5s interval for 3s.
To select a location for the inverter, the following criteria should be considered:
Risk of fire
Despite careful construction, electrical devices can cause fires.
NOTE:
Nothing should be stored on or placed against the inverter.
Please see Figure 4.4 and Figure 4.5 for instruction on mounting the inverter..
The inverter shall be mounted vertically. The steps to mount the inverter are listed below.
The electrical connection of the inverter must follow the steps listed below:
Before connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter.
Maximum 550Vdc for
S6-GR1P7K03-NV-ND, S6-GR1P8K03-NV-ND,
S6-GR1P9K03-NV-ND, S6-GR1P10K03-NV-ND
Before connection, please make sure the polarity of the output voltage of PV array matches the"DC+"and"DC-"symbols.
Please don't connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter.
Cable type | Cross section(mm²) | |
Range | Recommended value | |
Industry generic PV cable (model: PV1-F) | 4.0~6.0 (12~10AWG) | 4.0(12AWG) |
The steps to assemble the DC connectors are listed as follows:
If DC inputs are accidently reversely connected or inverter is faulty or not working properly, it is NOT allowed to turn off the DC switch as it will damage the inverter and even leads to a fire disaster.
The correct actions are:
Please note that any damages due to wrong operations are not covered in the device warranty.
It is recommended to use 6-16mm2 outdoor cables with a crimp terminal range of 6-10mm2.
Installation steps are shown as below:
The terminal part must be insulated with heat shrink tubing or insulating tape.
NOTE:
If aluminum cables are used, please use copper and aluminum terminals to avoid direct contact between the copper bar and the aluminum cables. (the copper and aluminum adapters are configured according to the selected cable)
When assembling the AC terminal, be careful not to cut the insulation layer of the wire, or it might lead to poor contact.
An external ground connection is provided at the right side of inverter.
Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal.
Connect the OT terminal with ground cable to the right side of inverter.
The torque is 20 in-lbs (2N.m).
To protect the inverter's AC grid connection conductors, Solis recommends installing breakers that will protect against overcurrent. The following table defines OCPD ratings for the Solis S6 Single Phase Inverters.
The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are optional (Figure 4.21). For connection instructions, please refer to the Solis Monitoring Device installation manuals.
Refer to figure 4.22, which is a simple guidance for installing a solar system with PV inverter.
A DC isolator is required to be installed in the system between PV panels with inverter.
The inverter can work with a single phase smart meter to achieve Export Power Management function and/or 24hour consumption monitoring function.
NOTE:
To achieve Export Power Management function, the smart meter can be installed on either grid side or load side. To achieve 24hour consumption monitoring function, the smart meter can only be installed on grid side.
Two types of meters are supported:
Direct Insert Type Meter - Max input current 60A (Model: DDSD1352-C)
External CT Type Meter - 120A/40mA CT is supplied (Model: ACR10RD16TE)
Customer can place the order for a suitable meter from Solis Sales Reps.
Below are the connection diagrams of different meters connecting to different locations.
The inverter can work with a smart sensor to achieve Export Power Management function.
NOTE:
Inverters are classified as "Meter Model" and "CT Model" due to hardware difference.
Meter Model can only connect a smart meter.
CT Model can only connect a smart sensor.
Please consult Solis Sales Rep before placing the order.
NOTE:
To achieve Export Power Management function, the smart sensor must be installed on the grid side.
Below is the connection diagram of the smart sensor.
Logic interface is required by some local regulations that can be operated by a simple switch or contactor (Not available in South Africa).
When the switch is closed the inverter can operated normally. When the switch is opened, the inverter will reduce it's output power to zero within 5s.
Pin5 and Pin6 of RJ45 terminal is used for the logic interface connection.
Please follow below steps to assemble RJ45 connector.
Users need to download the APP before installing it for the first time.
There are three ways to download and install the latest APP:
Step 1: Rotate the inverter DC switch from OFF to ON.
Step 2: APP Bluetooth connection with inverter.
Turn on Bluetooth switch on your mobile phone and then open the Soliscloud APP. Click "More Tools"->"Local Operation"->"Connect with Bluetooth"
Select the Bluetooth signal from the inverter. (Bluetooth Name: INV-Inverter SN)
Step 3: Login account.
If you are the installer, please select the account type as Installer. If you are the plant owner, please select the account type as owner. Then set your own initial password for control verification. (The first log-in must be finished by installer in order to do the initial set up)
Step 4: Grid Code Setting.
Select "Settings->Grid Parameter Setting->Grid Code Setting->Grid Code", choose the applicant standard according to the installation and save.
The specific parameters can be set at Grid Code Setting page.
Mention that the grid parameters modification should be permissible by utility grid company or the power distribution supplier.
Step 5: Turn on the AC switch between the inverter and Grid, wait till the inverter start generating.
To stop the inverter, it is mandatory that the steps below are followed in the exact order outlined.
Although the inverter DC disconnect switch is in the OFF position and all the LED's are OFF, operators must wait five (5) minutes after the DC power source has been disconnected before opening the inverter cabinet. DC side capacitors can take up to five (5) minutes to dissipate all stored energy.
Bluetooth communication parameters are as follow:
The APP interface contains 4 sections:
The home page contains the power and energy data of the inverter.
The PV data and AC data are also available under this section.
Info page displays the general information of the inverter such as inverter serial number, firmware version, grid code, etc.
Alarm page contains the alarm code of the inverter and its corresponding troubleshooting methods.
Setting page contains all the setting options of the inverter.
Functions | Setting Path |
Switch on/off the inverter | Settings -> "Power ON" & "Power OFF" |
Change inverter time setting | Settings -> Inverter Setting-> Inverter Parameter Setting -> Inverter Time Setting |
Change inverter output power percentage or power factor | Settings -> Inverter Setting->Inverter Power Setting |
Set grid code and protection parameters | Settings -> Grid Parameter Setting ->Grid Code Setting |
Set Export Power control | Settings -> EPM Setting |
Set grid code related working modes | Settings -> Inverter Work Mode Setting ->Work Mode |
NOTE:
The inverter is by default setting with grid code which complies with local requirements. If there is need to modify the protection limits, please consult and approve by your local grid operator.
AFCI Setting
Setting | Description |
AFCI Protect | Set the inverter AFCI function ON/OFF. |
Arc-Fault Manual Reset |
|
Setting | Description |
MPPT Multi-peak Scanning Switch | Set the function ON/OFF. |
MPPT Multi-peak Scan Interval | The inverter will carry out Multi-peak MPPT scanning 1 time every scan interval. |
Setting | Description |
Logic Interface(DRM) Switch | Set the function ON/OFF. |
P_Limit DI 1 ~ P_Limit DI 4 | Set the AC output power under different DI. |
Setting | Description |
Time | Set the inverter time and date according to local time zone. |
Slave Address | Set the inverter address when multiple inverters are installed. |
Generation Calibration | Calibrate the inverter daily, monthly, annual and total yield. |
Setting | Description |
Output Power Setting | Set the inverter maximum AC output power. |
PF Curve | Set the inverter power factor. |
Power Limit | Set the power control slope, power rise control slope, power down control slope, EN 50549 power change gradient after fault trip restart, EN 50549 gradient limit for power-on change. |
See Local Connection via APP Chapter for details.
Built-in EPM is for PV plant with only 1 inverter, while External EPM for multiple inverters.
Select "Settings -> EPM Setting -> Built-in EPM Setting" to make the settings.
The Built-in EPM includes 2 functions related to the smart meter or smart sensor.
NOTE:
Function 1: Export Power Management Function
Function 2: 24-Hour Load Monitoring Function
NOTE:
Please refer to below instructions for different user scenarios.
Scenario 1. Only Function 1 is required Using a Smart Meter:
Step 1: Refer to Meter Connection Section to connect the smart meter on the grid side or load side.
Step 2: Select the corresponding meter model in the Meter Selection.
Step 3: Choose Meter in Grid Mode or Meter in Load Mode in the Built-in EPM mode selection accordingly.
Step 4: Configure the System Export Power Limit Value to set the allowed backflow power.
Step 5: Configure the Built-in EPM Failsafe Switch to enable the failsafe function (If necessary).
Using a Smart Sensor:
Step 1: Refer to CT connections Section to connect the smart sensor on the grid side.
Step 2: Select the CT Sensor Mode in the Built-in EPM mode selection.
Step 3: Configure the CT Ratio and CT Direction at the "Settings -> EPM Setting -> CT Setting". (If necessary).
Step 4: Configure the System Export Power Limit Value to set the allowed backflow power.
Step 5: Configure the Built-in EPM Failsafe Switch to enable the failsafe function (If necessary).
NOTE:
Please refer to below instructions for different user scenarios.
Scenario 2. Only Function 2 is required Using a Smart Meter:
Step 1: Refer to Meter Connection Section to connect the smart meter on the grid side or load side.
Step 2: Select the corresponding meter model in the Meter Selection.
Step 3: Choose Meter 24-Hour Monitoring Mode in the Built-in EPM mode selection accordingly.
Step 4: Enable the 24-Hour Load Monitoring function at "Settings -> Inverter Setting -> Inverter Function Setting".
Using a Smart Sensor:
Step 1: Refer to CT connections Section to connect the smart sensor on the grid side.
Step 2: Select the CT load Monitoring Mode in the Built-in EPM mode selection.
Step 3: Configure the CT Ratio and CT Direction at the "Settings -> EPM Setting -> CT Setting". (If necessary).
Step 4: Enable the 24-Hour Load Monitoring function at "Settings -> Inverter Setting -> Inverter Function Setting".
NOTE:
Please refer to below instructions for different user scenarios.
Scenario 3. Both Function 1 and 2 are required Using a Smart Meter:
Step 1: Refer to Meter Connection Section to connect the smart meter on the grid side or load side.
Step 2: Select the corresponding meter model in the Meter Selection. Step 3: Choose Meter in Grid Mode or Meter in Load Mode in the Built-in EPM mode selection accordingly.
Step 4: Configure the System Export Power Limit Value to set the allowed backflow power.
Step 5: Configure the Built-in EPM Failsafe Switch to enable the failsafe function (If necessary).
Step 6: Enable the 24-Hour Load Monitoring function at "Settings -> Inverter Setting -> Inverter Function Setting".
Using a Smart Sensor:
Step 1: Refer to CT connections Section to connect the smart sensor on the grid side.
Step 2: Select the CT Sensor Mode in the Built-in EPM mode selection.
Step 3: Configure the CT Ratio and CT Direction at the "Settings -> EPM Setting -> CT Setting". (If necessary).
Step 4: Configure the System Export Power Limit Value to set the allowed backflow power.
Step 5: Configure the Built-in EPM Failsafe Switch to enable the failsafe function (If necessary).
Step 6: Enable the 24-Hour Load Monitoring function at "Settings -> Inverter Setting -> Inverter Function Setting".
Setting | Description |
Built-in EPM mode | 6 built-in EPM mode is optional. Choose the appropriate mode needed. |
System Export Power Limit Value | Set the permissible PV plant export power to the gird. |
Built-in EPM Failsafe Switch | When G100 standard is used, this switch is enabled by default. |
Meter Selection | Select the meter model according to the actual installation. |
G100V2 Control Switch | When new G100 standard is used, enable this switch. Select the meter or CT mode according to the actual installation. |
G100V2 Backflow Current | Set the backflow current of the PV plant to the grid. Only meaningful when G100V2 switch is on. |
G100V2 Alarm Clear | Use this function to clear a fault status according to new G100 standard. Only meaningful when G100V2 switch is on. |
G100V2 Alarm Clear Type | Select the Domestic or Non-domestic according to the actual installation. Only meaningful when G100V2 switch is on. |
There are 6 modes for Built-in EPM.
Select "Settings -> EPM Setting -> External EPM Setting".
External EPM Failsafe Swtich should be turned ON when external EPM device is used.
Select "Settings -> Inverter Work Mode Setting".
Solis S6 Single Phase Inverter does not require any regular maintenance.
However, cleaning the dust on heat-sink will help the inverter to dissipate the heat and increase its life time. The dust can be removed with a soft brush.
Do not touch the inverter's surface when it is operating. Some parts of the inverter may be hot and cause burns. Turn off the inverter and wait for a cool-down period before any maintenance or cleaning operation.
The Screen and the LED status indicator lights can be cleaned with cloth if they are too dirty to be read.
NOTE:
Never use any solvents, abrasives or corrosive materials to clean the inverter.
The inverter is designed in accordance with the most important international grid-tied standards and safety and electromagnetic compatibility requirements. Before delivering to the customer, the inverter has been subjected to several tests to ensure its optimal operation and reliability.
In case of failure, the APP will display an alarm message. In this case, the inverter may stop feeding into the grid. The failure descriptions and their corresponding alarm messages are listed in Table 8.1:
Message Name | Information Description | Troubleshooting Suggestion |
Grid Over Voltage 01 (1010 DATA:0001) | Over grid voltage |
|
Grid Over Voltage 02 (1010 DATA:0002) | ||
Grid Over Voltage 03 (1010 DATA:0003) | ||
Grid Over Voltage 04 (1010 DATA:0004) | ||
Grid Over Voltage 05 (1010 DATA:0005) | ||
Grid Under Voltage 01 (1011 DATA:0001) | Under grid voltage |
|
Grid Under Voltage 02 (1011 DATA:0002) | ||
Grid Over Frequency 01 (1012 DATA:0001) | Over grid frequency | |
Grid Over Frequency 02 (1012 DATA:0001) | ||
Grid under Frequency 01 (1013 DATA:0001) | Under grid frequency | |
Grid under Frequency 02 (1013 DATA:0002) | ||
NO-Grid (1015 DATA:0000) | No grid voltage |
|
OV-G-I (1018 DATA:0000) | Over grid current | |
IGFOL-F (1019 DATA:0000) | Grid current tracking fail |
|
OV-DC (1020 DATA:0001) | Over DC voltage |
|
OV-DC (1020 DATA:0002) | ||
OV-BUS (1021 DATA:0000) | Over DC bus voltage |
|
UNB-BUS (1022 DATA:0000) | Under DC bus voltage | |
DC Bus Under Voltage 01 (1023 DATA:0001) | DC bus undervoltage |
|
DC Bus Under Voltage 02 (1023 DATA:0002) | Abnormal detection of DC bus voltage | |
OV-DCA-I (1025 DATA:0000) | DC 1 average overcurrent |
|
OV-DCB-I (1026 DATA:0000) | DC 2 average overcurrent |
|
DC-INTF. (1027 DATA:0000) | DC hardware overcurrent |
|
Reverse-DC (1028 DATA:0000) | Reverse DC polarity |
|
GRID-INTF. (1030 DATA:0000) | AC hardware overcurrent |
|
INI-FAULT (1031 DATA:0000) | Initialization system fault |
|
OV-TEM (1032 DATA:0000) | Over Temperature |
|
PV Isolation Protection 01 (1033 DATA:0001) | DC bus undervoltage |
|
PV Isolation Protection 02 (1033 DATA:0002) | PV negative ground fault | |
Leakage Current Protection 01 (1034 DATA:0001) | Leakage current protection |
|
Leakage Current Protection 02(1034 DATA:0002) | ||
Leakage Current Protection 03 (1034 DATA:0003) | ||
Leakage Current Protection 04 (1034 DATA:0004) | ||
ILeak-Check (1039 DATA:0000) | Leakage current sensor failure |
|
UN-TEM (103A DATA:0000) | Under Temperature |
|
Message Name | Information Description | Troubleshooting Suggestion | |
Relay-FAULT (1035 DATA:0000) | Relay check fail |
| |
DSP-B-Com-Fau (1036 DATA:0000) | Comm. failure between main and slave DSP | ||
DCInj-FAULT (1037 DATA:0000) | High DC injection current | ||
12Power-FAULT (1038 DATA:0000) | 12V power supply fault | ||
AFCI-Check (1040 DATA:0000) | AFCI module self-detect fault |
| |
ARC-FAULT (1041 DATA:0000) | Detect arc in DC circuit |
| |
GRID-INTF02 (1046 DATA:0000) | Power grid disturbance 02 |
| |
IG-AD (1047 DATA:0000) | Grid current sampling fail |
| |
IGBT-OV-I (1048 DATA:0000) | Over IGBT current | ||
State 2 excursion (2043H) | G100 State 2 excursion | The alarm appears when the current flow exceeds "G100V2 Backflow Current" under scenarios stipulated by G100 standard. As required by G100, "State 2 excursion" alarm should be manually reset. Please select the "Settings -> EPM Setting -> Built-in EPM Setting->G100V2 Alarm Clear" to reset. | |
Fail Safe 2010H | Meter Communication Fail |
| |
MET_SEL_FAIL 2019H | Meter type select fail | Please select the correct smart meter type in inverter setting based on the smart meter actually connected to the inverter. | |
CT Fault 201AH | CT Fault | The alarm occurs when the CT connected to the inverter or the CT connected to the smart meter loses connection.
| |
DRM_LINK_FAIL 2018H | DRM link fail | Please check if your DRM control device/ logic interface or its wiring is normal. If there is actually no DRM control device/ logic interface connected, please disable the DRM function in inverter settings. | |
DRM_CTL_Off 201BH | DRM control inverter to stop | Please check if the DRM function is enabled. This alarm indicates the DRM function controls the inverter to stop. If this is not expected, please disable the DRM function. | |
AFCI-Comm-Fail 2041H | AFCI communication fail |
| |
AFCI-CTModule-Fail 2042H | AFCI CT module fail |
Table 8.1 Fault message and description
NOTE:
If the inverter displays any alarm message as listed in Table 8.1; please turn off the inverter and wait for 5 minutes before restarting it.
If the failure persists, please contact your local distributor or the service center.
Model | S6-GR1P7K03-NV-ND |
Max. DC input voltage (Volts) | 550 |
Rated DC voltage (Volts) | 330 |
Startup voltage (Volts) | 60 |
MPPT voltage range (Volts) | 50-500 |
Max. input current (Amps) | 20/20/20 |
Max short circuit input current (Amps) | 25/25/25 |
MPPT number/Max input strings number | 3/3 |
Classification | AFCI Type: F-l-AFPE-1-3-1 |
No.of monitored strings per input port | 1 |
No.of input ports per channel | 3 |
No.of monitored channels | 1 |
Rated channel curente (Amps) | 20+20+20 |
Maximum current per input port (Amps) | 20 |
Rated interruption current (Amps) | 20 |
Rated output power (Watts) | 7000 |
Max. output power (Watts) | 7000 |
Max. apparent output power (VA) | 7000 |
Rated grid voltage (Volts) | 1/N/PE, 220/230 |
Rated output current (Amps) | 31.8/30.4 |
Max. output current (Amps) | 31.8 |
Power Factor (at rated output power) | >0.99 (0.8 leading - 0.8 lagging) |
THDi (at rated output power) | <3% |
Rated grid frequency (Hertz) | 50/60 |
Operating frequency range (Hertz) | 45-55 or 55-65 |
Max.efficiency | 98.0% |
EU efficiency | 97.1% |
Dimensions | 338W*512H*220D (mm) |
Weight | 16.3kg |
Topology | Transformerless |
Self consumption (night) | |
Operating ambient temperature range | -25℃~+60℃ |
Relative humidity | 0-100% |
Ingress protection | IP66 |
Noise emission (typical) | <40 dB(A) |
Cooling concept | Natural convection |
Max.operation altitude | 4000m |
Grid connection standard | G99, IEC 62116, IEC 61727, EN 50530,MEA,PEA |
Safety/EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4 |
DC connection | MC4 connector |
AC connection | OT Terminal |
Display | LED, BLUETOOTH+APP |
Communication connections | RS485, Optional: Wi-Fi, GPRS |
Warranty Terms | 5 Years (Extend to 20 Years) |
Model | S6-GR1P8K03-NV-ND |
Max. DC input voltage (Volts) | 550 |
Rated DC voltage (Volts) | 330 |
Startup voltage (Volts) | 60 |
MPPT voltage range (Volts) | 50-500 |
Max. input current (Amps) | 20/20/20 |
Max short circuit input current (Amps) | 25/25/25 |
MPPT number/Max input strings number | 3/3 |
Classification | AFCI Type: F-l-AFPE-1-3-1 |
No.of monitored strings per input port | 1 |
No.of input ports per channel | 3 |
No.of monitored channels | 1 |
Rated channel curente (Amps) | 20+20+20 |
Maximum current per input port (Amps) | 20 |
Rated interruption current (Amps) | 20 |
Rated output power (Watts) | 8000 |
Max. output power (Watts) | 8000 |
Max. apparent output power (VA) | 8000 |
Rated grid voltage (Volts) | 1/N/PE, 220/230 |
Rated output current (Amps) | 36.4/34.8 |
Max. output current (Amps) | 36.4 |
Power Factor (at rated output power) | >0.99 (0.8 leading - 0.8 lagging) |
THDi (at rated output power) | <3% |
Rated grid frequency (Hertz) | 50/60 |
Operating frequency range (Hertz) | 45-55 or 55-65 |
Max.efficiency | 98.0% |
EU efficiency | 97.1% |
Dimensions | 338W*512H*220D (mm) |
Weight | 16.3kg |
Topology | Transformerless |
Self consumption (night) | |
Operating ambient temperature range | -25℃~+60℃ |
Relative humidity | 0-100% |
Ingress protection | IP66 |
Noise emission (typical) | <40 dB(A) |
Cooling concept | Natural convection |
Max.operation altitude | 4000m |
Grid connection standard | G99, IEC 62116, IEC 61727, EN 50530,MEA,PEA |
Safety/EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4 |
DC connection | MC4 connector |
AC connection | OT Terminal |
Display | LED, BLUETOOTH+APP |
Communication connections | RS485, Optional: Wi-Fi, GPRS |
Warranty Terms | 5 Years (Extend to 20 Years) |
Model | S6-GR1P9K03-NV-ND |
Max. DC input voltage (Volts) | 550 |
Rated DC voltage (Volts) | 330 |
Startup voltage (Volts) | 60 |
MPPT voltage range (Volts) | 50-500 |
Max. input current (Amps) | 20/20/20 |
Max short circuit input current (Amps) | 25/25/25 |
MPPT number/Max input strings number | 3/3 |
Classification | AFCI Type: F-l-AFPE-1-3-1 |
No.of monitored strings per input port | 1 |
No.of input ports per channel | 3 |
No.of monitored channels | 1 |
Rated channel curente (Amps) | 20+20+20 |
Maximum current per input port (Amps) | 20 |
Rated interruption current (Amps) | 20 |
Rated output power (Watts) | 9000 |
Max. output power (Watts) | 9000 |
Max. apparent output power (VA) | 9000 |
Rated grid voltage (Volts) | 1/N/PE, 220/230 |
Rated output current (Amps) | 40.9/39.1 |
Max. output current (Amps) | 40.9 |
Power Factor (at rated output power) | >0.99 (0.8 leading - 0.8 lagging) |
THDi (at rated output power) | <3% |
Rated grid frequency (Hertz) | 50/60 |
Operating frequency range (Hertz) | 45-55 or 55-65 |
Max.efficiency | 98.0% |
EU efficiency | 97.1% |
Dimensions | 338W*512H*220D (mm) |
Weight | 16.3kg |
Topology | Transformerless |
Self consumption (night) | |
Operating ambient temperature range | -25℃~+60℃ |
Relative humidity | 0-100% |
Ingress protection | IP66 |
Noise emission (typical) | <40 dB(A) |
Cooling concept | Natural convection |
Max.operation altitude | 4000m |
Grid connection standard | G99, IEC 62116, IEC 61727, EN 50530,MEA,PEA |
Safety/EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4 |
DC connection | MC4 connector |
AC connection | OT Terminal |
Display | LED, BLUETOOTH+APP |
Communication connections | RS485, Optional: Wi-Fi, GPRS |
Warranty Terms | 5 Years (Extend to 20 Years) |
Model | S6-GR1P10K03-NV-ND |
Max. DC input voltage (Volts) | 550 |
Rated DC voltage (Volts) | 330 |
Startup voltage (Volts) | 60 |
MPPT voltage range (Volts) | 50-500 |
Max. input current (Amps) | 20/20/20 |
Max short circuit input current (Amps) | 25/25/25 |
MPPT number/Max input strings number | 3/3 |
Classification | AFCI Type: F-l-AFPE-1-3-1 |
No.of monitored strings per input port | 1 |
No.of input ports per channel | 3 |
No.of monitored channels | 1 |
Rated channel curente (Amps) | 20+20+20 |
Maximum current per input port (Amps) | 20 |
Rated interruption current (Amps) | 20 |
Rated output power (Watts) | 10000 |
Max. output power (Watts) | 10000 |
Max. apparent output power (VA) | 10000 |
Rated grid voltage (Volts) | 1/N/PE, 220/230 |
Rated output current (Amps) | 45.5/43.5 |
Max. output current (Amps) | 45.5 |
Power Factor (at rated output power) | >0.99 (0.8 leading - 0.8 lagging) |
THDi (at rated output power) | <3% |
Rated grid frequency (Hertz) | 50/60 |
Operating frequency range (Hertz) | 45-55 or 55-65 |
Max.efficiency | 98.0% |
EU efficiency | 97.1% |
Dimensions | 338W*512H*220D (mm) |
Weight | 16.3kg |
Topology | Transformerless |
Self consumption (night) | |
Operating ambient temperature range | -25℃~+60℃ |
Relative humidity | 0-100% |
Ingress protection | IP66 |
Noise emission (typical) | <40 dB(A) |
Cooling concept | Natural convection |
Max.operation altitude | 4000m |
Grid connection standard | G99, IEC 62116, IEC 61727, EN 50530,MEA,PEA |
Safety/EMC standard | IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4 |
DC connection | MC4 connector |
AC connection | OT Terminal |
Display | LED, BLUETOOTH+APP |
Communication connections | RS485, Optional: Wi-Fi, GPRS |
Warranty Terms | 5 Years (Extend to 20 Years) |
Ginlong Technologies Co., Ltd.
No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,
Zhejiang, 315712, P.R.China.
Tel: +86 (0)574 6578 1806
Fax: +86 (0)574 6578 1606
Email: info@ginlong.com
Web: www.ginlong.com
Please adhere to the actual products in case of any discrepancies in this user manual.
If you encounter any problem on the inverter, please find out the inverter S/N and contact us, we will try to respond to your question ASAP.
Safety symbols used in this manual, which highlight potential safety risks and important safety information, are listed as follows:
WARNING symbol indicates important safety instructions, which if not correctly followed, could result in serious injury or death.
NOTE:
NOTE symbol indicates important safety instructions, which if not correctly followed, could result in some damage or the destruction of the inverter.
CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety instructions, which if not correctly followed, could result in electric shock.
CAUTION, HOT SURFACE symbol indicates safety instructions, which if not correctly followed, could result in burns.
Only devices in compliance with SELV (EN 69050) may be connected to the RS485 and USB interfaces.
Please don't connect PV array positive(+) or negative(-) to ground, it could cause serious damage to the inverter.
NOTE:
PV module used with inverter must have an IEC 61730 Class A rating.
Electrical installations must be done in accordance with the local and national electrical safety standards.
Risk of electric shock from energy stored in capacitors of the Inverter.
Do not remove cover for 5 minutes after disconnecting all power sources (service technician only). Warranty may be voided if the cover is removed without unauthorized.
The surface temperature of the inverter can exceed 75℃ (167F).
To avoid risk of burns, DO NOT touch the surface when inverter is operating.
The inverter must be installed out of reach of children.
The PV array (Solar panels) supplies a DC voltage when they are exposed to sunlight.
To reduce the risk of fire, over-current protective devices (OCPD) are required for circuits connected to the Inverter.
The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC Article 690, Part II. All Solis S6 Single Phase Inverters feature an integrated
DC switch.
Risk of electric shock. Do not remove cover. There is no user serviceable parts inside. Refer servicing to qualified and accredited service technicians.
Do not touch any inner live parts until 5 minutes after disconnection from the utility grid and the PV input
The inverter has been constructed according to the applicable safety and technical guidelines. Use the inverter in installations that meet the following specifications only:
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the S6 and is the answer not in the manual?
Questions and answers