SOLIS S6, S6-GR1P(7-10)K03-NV-ND - Inverter Manual

SOLIS S6, S6-GR1P(7-10)K03-NV-ND - Inverter Manual

Also See for S6:

Advertisement

SOLIS S6, S6-GR1P(7-10)K03-NV-ND - Inverter Manual

Introduction

Product Description

Solis S6 Single Phase Inverters integrate DRM and backflow power control function, that could suitable for smart grid requirement.

This manual covers the S6 Single Phase Inverter model listed below:
S6-GR1P7K03-NV-ND, S6-GR1P8K03-NV-ND, S6-GR1P9K03-NV-ND, S6-GR1P10K03-NV-ND

Front side view
Bottom side view

Packaging

When you receive the inverter, please ensure that all the parts listed below are included:

If anything is missing, please contact your local Solis distributor.

Product Storage

If the inverter is not to be installed immediately, storage instructions and environmental conditions are below:

  • Use the original box to repackage the inverter, seal with adhesive tape with the desiccant inside the box.
  • Store the inverter(s) in a clean and dry place, free of dust and dirt.
  • Storage temperature must be between -40℃ and 70℃ and the humidity should be between 0 and 95% non-condensing.
  • Stack no more than four (4) inverters high.
  • Keep box(es) away from corrosive materials to avoid damage to the inverter enclosure.
  • Inspect packaging regularly. If packaging is damaged(wet, pest damage, etc), repackage the inverter immediately.
  • Store the inverter(s) on a flat, hard surface - not inclined or upside down.
  • After long-term storage, the inverter needs to be fully examined and tested by qualified service or technical personnel before using.
  • Restarting after a long period of non-use requires the equipment to be inspected and, in some cases, the removal of oxidation and dust that has settled inside the equipment will be required.

Overview

Front Panel Display

There are four indicators on the Solis S6-GR1P(2.5-6)K-S Series Inverter(Power, COM, CT/Meter and Bluetooth) which indicate the working status of the inverter.

Front Panel Display

information NOTE:

information NOTE:
Long press the Power button for 5 seconds to reset the bluetooth connection passwords. If the reset is successful, the Power button will be flashing in Blue color and in 0.5s interval for 3s. If the reset is failed, the Power button will be flashing in Yellow color and in 0.5s interval for 3s.

Select a Location for the Inverter

To select a location for the inverter, the following criteria should be considered:


Risk of fire
Despite careful construction, electrical devices can cause fires.

  • Do not install the inverter in areas containing highly flammable materials or gases.
  • Do not install the inverter in potentially explosive atmospheres.
  • The mounting structure where the inverter is installed must be fireproof.
  • Do not install in small closed spaces where air can not circulate freely. To avoid overheating, always make sure the flow of air around the inverter is not blocked.
  • Exposure to direct sunlight will increase the operational temperature of the inverter and may cause output power limiting. Recommends inverter installed to avoid direct sunlight or raining.
  • To avoid over heating ambient air temperature must be considered when choosing the inverter installation location. Recommends using a sun shade minimizing direct sunlight when the ambient air temperature around the unit exceeds 104°F/40°C.
    Select a Location for the Inverter

Installation

  • Install on a wall or strong structure capable of bearing the weight.
  • Install vertically with a maximum incline of +/- 5°.If the mounted inverter is tilted to an angle greater than the maximum noted, heat dissipation can be inhibited, and may result in less than expected output power.
  • When 1 or more inverters are installed in one location, a minimum 12 inches clearance should be kept between each inverter or other object. The bottom of the inverter should be 20 inches clearance to the ground
    Mounting clearance
  • Visibility of the LED status indicator lights and the LCD located at the front panel of the inverter should be considered.
  • Adequate ventilation must be provided if the inverter is to be installed in a confined space.

information NOTE:
Nothing should be stored on or placed against the inverter.

Mounting the Inverter

Please see Figure 4.4 and Figure 4.5 for instruction on mounting the inverter..

The inverter shall be mounted vertically. The steps to mount the inverter are listed below.

  1. According to the figure 4.2, select the mounting height of the bracket and mark the mounting holes. For brick walls, the position of the holes should be suitable for the expansion bolts.
    Mounting the Inverter - Step 1

    The inverter must be mounted vertically.
  2. Lift up the inverter (be careful to avoid body strain), and align the back bracket on the inverter with the convex section of the mounting bracket. Hang the inverter on the mounting bracket and make sure the inverter is secure (see Figure 4.5).
    Mounting the Inverter - Step 2

Electrical Connections

Connect PV side of inverter

The electrical connection of the inverter must follow the steps listed below:

  1. Switch the Grid Supply Main Switch (AC) OFF.
  2. Switch the DC Isolator OFF.
  3. Assemble PV input connector to the Inverter.

cautionBefore connecting inverter, please make sure the PV array open circuit voltage is within the limit of the inverter.
Maximum 550Vdc for
S6-GR1P7K03-NV-ND, S6-GR1P8K03-NV-ND,
S6-GR1P9K03-NV-ND, S6-GR1P10K03-NV-ND

information Before connection, please make sure the polarity of the output voltage of PV array matches the"DC+"and"DC-"symbols.

cautionPlease don't connect PV array positive or negative pole to the ground, it could cause serious damages to the inverter.

Cable type Cross section(mm²)
Range Recommended value
Industry generic PV cable
(model: PV1-F)
4.0~6.0
(12~10AWG)
4.0(12AWG)

The steps to assemble the DC connectors are listed as follows:

  1. Strip off the DC wire for about 7mm, Disassemble the connector cap nut. (see Figure 4.8)
  2. Insert the wire into the connector cap nut and contact pin. (see Figure 4.9)
    Connect PV side of inverter - Step 1
  3. Crimp the contact pin to the wire using a proper wirecrimper. (see Figure 4.10)
  4. Insert the contact pin to the top part of the connector and screw up the cap nut to the top part of the connector.(see figure 4.11).
  5. Then connect the DC connectors to the inverter. Small click will confirm connection. (see figure 4.12)
    Connect PV side of inverter - Step 2


If DC inputs are accidently reversely connected or inverter is faulty or not working properly, it is NOT allowed to turn off the DC switch as it will damage the inverter and even leads to a fire disaster.
The correct actions are:

  • Use a clip-on ammeter to measure the DC string current.
  • If it is above 0.5A, please wait for the solar irradiance reduces until the current decreases to below 0.5A.
  • Only after the current is below 0.5A, you are allowed to turn off the DC switches and disconnect the PV strings.

Please note that any damages due to wrong operations are not covered in the device warranty.

AC output connections

It is recommended to use 6-16mm2 outdoor cables with a crimp terminal range of 6-10mm2.

Installation steps are shown as below:

  1. Strip the end of the AC cable insulation sleeve about 55mm then strip a short bit (S2) on the end of each wire.
     AC output connections - Step 1
    information NOTE:
    S2 (the length to strip the wire is about 8mm) which is 2-3mm longer than S1.
  2. Insert the stripped cable into the crimping area of the OT terminal then use crimping tool to crimp the cable terminal.

The terminal part must be insulated with heat shrink tubing or insulating tape.

information NOTE:
If aluminum cables are used, please use copper and aluminum terminals to avoid direct contact between the copper bar and the aluminum cables. (the copper and aluminum adapters are configured according to the selected cable)

  1. Dissemble the 4 screws on the AC terminal cover and take out the cover.
     AC output connections - Step 2
  2. Insert the cable through cap nut, tubing and AC terminal, Insert the 3 cables into AC terminal and use the slotted screwdriver to tighten the screws with torque of 2-3Nm.
     AC output connections - Step 3


When assembling the AC terminal, be careful not to cut the insulation layer of the wire, or it might lead to poor contact.

  1. Push the AC terminal along the rail to the inside of the inverter then tighten the screws.
    Lock the 4 screws of the AC terminal then tighten the cap nut.

External ground connection

An external ground connection is provided at the right side of inverter.

Prepare OT terminals: M4. Use proper tooling to crimp the lug to the terminal.

Connect the OT terminal with ground cable to the right side of inverter.

The torque is 20 in-lbs (2N.m).

External ground connection

Max. over current protection device (OCPD)

To protect the inverter's AC grid connection conductors, Solis recommends installing breakers that will protect against overcurrent. The following table defines OCPD ratings for the Solis S6 Single Phase Inverters.

Inverter monitoring connection

The inverter can be monitored via Wi-Fi or GPRS. All Solis communication devices are optional (Figure 4.21). For connection instructions, please refer to the Solis Monitoring Device installation manuals.
 Inverter monitoring connection

Electrical connection diagram

Refer to figure 4.22, which is a simple guidance for installing a solar system with PV inverter.

A DC isolator is required to be installed in the system between PV panels with inverter.
Electrical connection diagram

  1. The RCD should be in parallel connection between the consumers mains and the solar supply.
  2. More than one RCD may be used. Each RCD can protect one or more circuits.

Meter Connection(optional)

The inverter can work with a single phase smart meter to achieve Export Power Management function and/or 24hour consumption monitoring function.

information NOTE:
To achieve Export Power Management function, the smart meter can be installed on either grid side or load side. To achieve 24hour consumption monitoring function, the smart meter can only be installed on grid side.

Two types of meters are supported:
Direct Insert Type Meter - Max input current 60A (Model: DDSD1352-C)
External CT Type Meter - 120A/40mA CT is supplied (Model: ACR10RD16TE)
Customer can place the order for a suitable meter from Solis Sales Reps.

Below are the connection diagrams of different meters connecting to different locations.

Meter Connection - Method 1
Meter Connection - Method 2
Meter Connection - Method 3
Meter Connection - Method 4

CT connections(optional)

The inverter can work with a smart sensor to achieve Export Power Management function.

information NOTE:
Inverters are classified as "Meter Model" and "CT Model" due to hardware difference.
Meter Model can only connect a smart meter.
CT Model can only connect a smart sensor.
Please consult Solis Sales Rep before placing the order.

information NOTE:
To achieve Export Power Management function, the smart sensor must be installed on the grid side.

Below is the connection diagram of the smart sensor.
CT connections

Logic interface connection

Logic interface is required by some local regulations that can be operated by a simple switch or contactor (Not available in South Africa).

When the switch is closed the inverter can operated normally. When the switch is opened, the inverter will reduce it's output power to zero within 5s.

Pin5 and Pin6 of RJ45 terminal is used for the logic interface connection.

Please follow below steps to assemble RJ45 connector.

  1. Insert the network cable into the communication connection terminal of RJ45.
    Logic interface connection - Step 1
  2. Use the network wire stripper to strip the insulation layer of the communication cable.
    According to the standard line sequence of figure 4.26 connect the wire to the plug of RJ45, and then use a network cable crimping tool to make it tight.
    Logic interface connection - Step 2
  3. Connect RJ45 to DRM (logic interface).

Commissioning

Preparation

  • Ensure all the devices are accessible for operation, maintenance and service.
  • Check and confirm that the inverter is firmly installed.
  • Space for ventilation is sufficient for one inverter or multiple inverters.
  • Nothing is left on the top of the inverter.
  • Inverter and accessories are correctly connected.
  • Cables are routed in safe place or protected against mechanical damage.
  • Warning signs and labels are suitably affixed and durable.
  • An Android or IOS mobile phone with Bluetooth function is available.
  • Measure DC voltage of PV strings and ensure the polarity is correct.
  • Measure AC voltage and frequency and ensure they are within local standard.
    Commissioning - Preparation

APP Download

Users need to download the APP before installing it for the first time.

There are three ways to download and install the latest APP:

  1. You can visitwww.soliscloud.com to download the latest version APP.
  2. You can search "Soliscloud" in Google Play or App Store.
    www.apple.com
    play.google.com
  3. You can scan this QR code below to download "Soliscloud".

Local Connection via APP

Step 1: Rotate the inverter DC switch from OFF to ON.

Step 2: APP Bluetooth connection with inverter.

Turn on Bluetooth switch on your mobile phone and then open the Soliscloud APP. Click "More Tools"->"Local Operation"->"Connect with Bluetooth"
Local Connection via APP - Step 1

Select the Bluetooth signal from the inverter. (Bluetooth Name: INV-Inverter SN)

Step 3: Login account.
If you are the installer, please select the account type as Installer. If you are the plant owner, please select the account type as owner. Then set your own initial password for control verification. (The first log-in must be finished by installer in order to do the initial set up)
Local Connection via APP - Step 2

Step 4: Grid Code Setting.
Select "Settings->Grid Parameter Setting->Grid Code Setting->Grid Code", choose the applicant standard according to the installation and save.

The specific parameters can be set at Grid Code Setting page.

Mention that the grid parameters modification should be permissible by utility grid company or the power distribution supplier.
Local Connection via APP - Step 3

Step 5: Turn on the AC switch between the inverter and Grid, wait till the inverter start generating.

Stop the Inverter

To stop the inverter, it is mandatory that the steps below are followed in the exact order outlined.

  1. Select "Power OFF" in the APP.
  2. Turn off the AC Switch between Solis inverter and Grid.
  3. Wait approximately 30 seconds (during this time, the AC side capacitors are dissipating energy). If the inverter has DC voltage above the start-up threshold, the red POWER LED will be lit. Switch the DC switch OFF.
  4. Confirm all LED's switch OFF (~one (1) minute).


Although the inverter DC disconnect switch is in the OFF position and all the LED's are OFF, operators must wait five (5) minutes after the DC power source has been disconnected before opening the inverter cabinet. DC side capacitors can take up to five (5) minutes to dissipate all stored energy.

Bluetooth communication parameters are as follow:

  1. RF operating frequency range: 2402~2480MHz (BLE, TX/RX)
  2. Maximum e.i.r.p.: 7.22dBm

Operation

The APP interface contains 4 sections:

  1. Home
  2. Info
  3. Alarm
  4. Settings

Home Page

The home page contains the power and energy data of the inverter.

The PV data and AC data are also available under this section.

Info Page

Info page displays the general information of the inverter such as inverter serial number, firmware version, grid code, etc.

Alarm Page

Alarm page contains the alarm code of the inverter and its corresponding troubleshooting methods.

Setting Page

Setting page contains all the setting options of the inverter.

Functions Setting Path
Switch on/off the inverter Settings -> "Power ON" & "Power OFF"
Change inverter time setting Settings -> Inverter Setting-> Inverter Parameter
Setting -> Inverter Time Setting
Change inverter output power percentage or power factor Settings -> Inverter Setting->Inverter Power Setting
Set grid code and protection parameters Settings -> Grid Parameter Setting ->Grid Code Setting
Set Export Power control Settings -> EPM Setting
Set grid code related working modes Settings -> Inverter Work Mode Setting ->Work Mode

information NOTE:
The inverter is by default setting with grid code which complies with local requirements. If there is need to modify the protection limits, please consult and approve by your local grid operator.

Start up and Stop the inverter

  1. Select "Settings -> Power ON" to start up the inverter.
  2. Select "Settings -> Power OFF" to stop the inverter.

Inverter Setting

Inverter Function Setting
  1. AFCI Setting

Setting Description
AFCI Protect Set the inverter AFCI function ON/OFF.
Arc-Fault Manual Reset
  1. Within 24 hours, if an Arc-Fault alarm occurs for the 1st-4th times, the inverter will stop operating and automatically reconnect to the grid after a 5-minute delay.
  2. Upon the 5th occurrence of an Arc-Fault alarm, the inverter will stop operating and will only reconnect to the grid automatically after the Arc-Fault alarm is manually cleared. Installer needs to thoroughly inspect the DC circuit to ensure all the cables are correctly fastened. Once the DC circuit issue has bean fixed or it is confirmed to be OK, using this setting to make a manual reset and wait for the inverter to reconnect.
  1. 24-Hour Load Monitoring
    Turn on this switch to enable 24-Hour Load Monitoring function. Please refer to 6.4.4.1 Built-in EPM Setting for details.
  2. MPPT Multi-peak Scanning Setting
Setting Description
MPPT Multi-peak Scanning Switch Set the function ON/OFF.
MPPT Multi-peak Scan Interval The inverter will carry out Multi-peak MPPT scanning 1 time every scan interval.
  1. Logical Interface Setup
Setting Description
Logic Interface(DRM) Switch Set the function ON/OFF.
P_Limit DI 1 ~ P_Limit DI 4 Set the AC output power under different DI.
Inverter Parameter Setting
Setting Description
Time Set the inverter time and date according to local time zone.
Slave Address Set the inverter address when multiple inverters are installed.
Generation Calibration Calibrate the inverter daily, monthly, annual and total yield.
Inverter Power Setting
Setting Description
Output Power Setting Set the inverter maximum AC output power.
PF Curve Set the inverter power factor.
Power Limit Set the power control slope, power rise control slope, power down control slope, EN 50549 power change gradient after fault trip restart, EN 50549 gradient limit for power-on change.

Grid Parameter Setting

See Local Connection via APP Chapter for details.

EPM Setting

Built-in EPM is for PV plant with only 1 inverter, while External EPM for multiple inverters.

Built-in EPM Setting

Select "Settings -> EPM Setting -> Built-in EPM Setting" to make the settings.

The Built-in EPM includes 2 functions related to the smart meter or smart sensor.

information NOTE:
Function 1: Export Power Management Function

  1. Inverters can work with a smart meter OR a smart sensor to dynamically limit the export power of the system.
  2. Zero injection can be achieved.
  3. Smart meter can be installed either on the grid side OR the load side.
    Smart sensor can only be installed on the grid side.

Function 2: 24-Hour Load Monitoring Function

  1. Only applicable if Solis monitoring system is used.
  2. Inverters can work with a smart meter OR smart sensor to monitor the load consumption data for the whole day and the data will be displayed on the Solis monitoring system.
  3. Smart meter or smart sensor can only be installed on the grid side.

information NOTE:
Please refer to below instructions for different user scenarios.

Scenario 1. Only Function 1 is required Using a Smart Meter:
Step 1: Refer to Meter Connection Section to connect the smart meter on the grid side or load side.

Step 2: Select the corresponding meter model in the Meter Selection.

Step 3: Choose Meter in Grid Mode or Meter in Load Mode in the Built-in EPM mode selection accordingly.

Step 4: Configure the System Export Power Limit Value to set the allowed backflow power.

Step 5: Configure the Built-in EPM Failsafe Switch to enable the failsafe function (If necessary).

Using a Smart Sensor:
Step 1: Refer to CT connections Section to connect the smart sensor on the grid side.

Step 2: Select the CT Sensor Mode in the Built-in EPM mode selection.

Step 3: Configure the CT Ratio and CT Direction at the "Settings -> EPM Setting -> CT Setting". (If necessary).

Step 4: Configure the System Export Power Limit Value to set the allowed backflow power.

Step 5: Configure the Built-in EPM Failsafe Switch to enable the failsafe function (If necessary).

information NOTE:
Please refer to below instructions for different user scenarios.

Scenario 2. Only Function 2 is required Using a Smart Meter:
Step 1: Refer to Meter Connection Section to connect the smart meter on the grid side or load side.

Step 2: Select the corresponding meter model in the Meter Selection.

Step 3: Choose Meter 24-Hour Monitoring Mode in the Built-in EPM mode selection accordingly.

Step 4: Enable the 24-Hour Load Monitoring function at "Settings -> Inverter Setting -> Inverter Function Setting".

Using a Smart Sensor:
Step 1: Refer to CT connections Section to connect the smart sensor on the grid side.

Step 2: Select the CT load Monitoring Mode in the Built-in EPM mode selection.

Step 3: Configure the CT Ratio and CT Direction at the "Settings -> EPM Setting -> CT Setting". (If necessary).

Step 4: Enable the 24-Hour Load Monitoring function at "Settings -> Inverter Setting -> Inverter Function Setting".

information NOTE:
Please refer to below instructions for different user scenarios.

Scenario 3. Both Function 1 and 2 are required Using a Smart Meter:
Step 1: Refer to Meter Connection Section to connect the smart meter on the grid side or load side.

Step 2: Select the corresponding meter model in the Meter Selection. Step 3: Choose Meter in Grid Mode or Meter in Load Mode in the Built-in EPM mode selection accordingly.

Step 4: Configure the System Export Power Limit Value to set the allowed backflow power.

Step 5: Configure the Built-in EPM Failsafe Switch to enable the failsafe function (If necessary).

Step 6: Enable the 24-Hour Load Monitoring function at "Settings -> Inverter Setting -> Inverter Function Setting".

Using a Smart Sensor:
Step 1: Refer to CT connections Section to connect the smart sensor on the grid side.

Step 2: Select the CT Sensor Mode in the Built-in EPM mode selection.

Step 3: Configure the CT Ratio and CT Direction at the "Settings -> EPM Setting -> CT Setting". (If necessary).

Step 4: Configure the System Export Power Limit Value to set the allowed backflow power.

Step 5: Configure the Built-in EPM Failsafe Switch to enable the failsafe function (If necessary).

Step 6: Enable the 24-Hour Load Monitoring function at "Settings -> Inverter Setting -> Inverter Function Setting".

Setting Description
Built-in EPM mode 6 built-in EPM mode is optional. Choose the appropriate mode needed.
System Export Power Limit Value Set the permissible PV plant export power to the gird.
Built-in EPM Failsafe Switch When G100 standard is used, this switch is enabled by default.
Meter Selection Select the meter model according to the actual installation.
G100V2 Control Switch When new G100 standard is used, enable this switch. Select the meter or CT mode according to the actual installation.
G100V2 Backflow Current Set the backflow current of the PV plant to the grid.
Only meaningful when G100V2 switch is on.
G100V2 Alarm Clear Use this function to clear a fault status according to new G100 standard. Only meaningful when G100V2 switch is on.
G100V2 Alarm Clear Type Select the Domestic or Non-domestic according to the actual installation. Only meaningful when G100V2 switch is on.

There are 6 modes for Built-in EPM.

  1. EPM ALL OFF. Built-in EPM function is disabled.
  2. CT Sensor Mode. Solis Smart Sensor is connected in the grid connection point (The System Export Power Limit Value setting is applicable, default value is 0W).
  3. Meter in Grid Mode. Solis Smart Meter is connected in the grid connection point (The System Export Power Limit Value setting is applicable, default value is 0W).
  4. Meter in Load Mode. Solis Smart Meter is connected in the load branch circuit (The System Export Power Limit Value setting is applicable, default value is 0W).
  5. Meter 24-Hour Monitoring Mode. Solis Smart Meter is connected in the grid connection point(used for 24h load monitoring only, the System Export Power Limit Value setting is not applicable).
  6. CT load Monitoring Mode. Solis Smart Sensor is connected in the grid connection point (used for 24h load monitoring only, the System Export Power Limit Value setting is not applicable).
External EPM Setting

Select "Settings -> EPM Setting -> External EPM Setting".

External EPM Failsafe Swtich should be turned ON when external EPM device is used.

Inverter Work Mode Setting

Select "Settings -> Inverter Work Mode Setting".

  1. No response mode
    Use this switch to close all response mode.
  2. Volt-watt Mode
    The volt-watt mode varies the active power output level of the inverter in response to the voltage at its grid-interactive port.
  3. Volt-var Mode
    The volt-var mode varies the reactive power absorbed or supplied by the inverter in response to the voltage at its grid-interactive port.
  4. Fixed power factor Mode
    The fixed power factor mode is for control of power factor over the range of inverter output.
  5. Fixed reactive power Mode
    The fixed reactive power mode is for control of reactive power over the range of inverter output.
  6. Power-PF Mode
    The Power-PF mode varies the active power output level of the inverter in response to its power factor.

Maintenance

Solis S6 Single Phase Inverter does not require any regular maintenance.

However, cleaning the dust on heat-sink will help the inverter to dissipate the heat and increase its life time. The dust can be removed with a soft brush.

burn hazard
Do not touch the inverter's surface when it is operating. Some parts of the inverter may be hot and cause burns. Turn off the inverter and wait for a cool-down period before any maintenance or cleaning operation.

The Screen and the LED status indicator lights can be cleaned with cloth if they are too dirty to be read.

information NOTE:
Never use any solvents, abrasives or corrosive materials to clean the inverter.

Troubleshooting

The inverter is designed in accordance with the most important international grid-tied standards and safety and electromagnetic compatibility requirements. Before delivering to the customer, the inverter has been subjected to several tests to ensure its optimal operation and reliability.

In case of failure, the APP will display an alarm message. In this case, the inverter may stop feeding into the grid. The failure descriptions and their corresponding alarm messages are listed in Table 8.1:

Message Name Information Description Troubleshooting Suggestion
Grid Over Voltage 01 (1010 DATA:0001) Over grid voltage
  1. If it occurs by accident, it may be short-term abnormality of the power grid. The inverter will resume normal work after detecting the normal power grid, and no manual intervention is required.
Grid Over Voltage 02 (1010 DATA:0002)
Grid Over Voltage 03 (1010 DATA:0003)
Grid Over Voltage 04 (1010 DATA:0004)
Grid Over Voltage 05 (1010 DATA:0005)
Grid Under Voltage 01 (1011 DATA:0001) Under grid voltage
  1. If it occurs by accident, it may be short-term abnormality of the power grid. The inverter will resume normal work after detecting the normal power grid, and no manual intervention is required.
  2. If it occurs frequently, check the grid voltage and check whether the grid frequency is in the inverter. Within the allowable range, if not, please contact customer service; if yes, please check if the AC side breaker and output cable are connected properly.
  3. If the grid voltage, grid frequency is within the allowable range of the inverter, and the AC side wiring confirmation It is true that this alarm still occurs frequently. After obtaining the consent of the local power operator, please contact customer service to modify the over-voltage and under-frequency protection points of the inverter power grid.
Grid Under Voltage 02 (1011 DATA:0002)
Grid Over Frequency 01 (1012 DATA:0001) Over grid frequency
Grid Over Frequency 02 (1012 DATA:0001)
Grid under Frequency 01 (1013 DATA:0001) Under grid frequency
Grid under Frequency 02 (1013 DATA:0002)
NO-Grid
(1015 DATA:0000)
No grid voltage
  1. Verify that the grid is properly connected.
  2. Check if the connected power grid is normal.
  3. If the mains connection is normal, you need to contact our maintenance staff member.
OV-G-I
(1018 DATA:0000)
Over grid current
IGFOL-F
(1019 DATA:0000)
Grid current tracking fail
  1. Restart the inverter or contact our service personnel.
OV-DC
(1020 DATA:0001)
Over DC voltage
  1. Check whether the series configuration of the PV strings is excessive, resulting in the open circuit voltage of the PV array being higher than the maximum input voltage of the inverter. If so, reduce the number of strings and make the string open voltage fall within the inverter specification range.
OV-DC
(1020 DATA:0002)
OV-BUS
(1021 DATA:0000)
Over DC bus voltage
  1. Check if the input voltage exceeds the maximum input voltage of the inverter.
  2. Restart the inverter.
  3. If it is still not resolved, contact the factory's customer service.
UNB-BUS
(1022 DATA:0000)
Under DC bus voltage
DC Bus Under Voltage 01 (1023 DATA:0001) DC bus undervoltage
  1. Check if the input voltage is too low.
  2. Restart the inverter.
  3. If it has not been eliminated, contact the factory's customer service.
DC Bus Under Voltage 02 (1023 DATA:0002) Abnormal detection of DC bus voltage
OV-DCA-I
(1025 DATA:0000)
DC 1 average overcurrent
  1. Check whether theMPPT of the A-way is reversed polarity.
  2. Restart the inverter.
  3. If it has not been eliminated, contact the factory's customer service.
OV-DCB-I
(1026 DATA:0000)
DC 2 average overcurrent
  1. Check whether theMPPT of the B-way is reversed polarity.
  2. Restart the inverter.
  3. If it has not been eliminated, contact the factory's customer service.
DC-INTF.
(1027 DATA:0000)
DC hardware overcurrent
  1. Check whether the DC connection is broken or damaged.
  2. Restart the inverter.
  3. If it has not been removed, contact the factory's customer service.
Reverse-DC
(1028 DATA:0000)
Reverse DC polarity
  1. Check if the DC line is reversed.
  2. Restart the inverter.
  3. If it is still not excluded, please contact the factory customer service.
GRID-INTF.
(1030 DATA:0000)
AC hardware overcurrent
  1. Check whether the AC connection is virtual.
  2. Restart the inverter.
  3. If it has not been eliminated, contact the factory's customer service.
INI-FAULT
(1031 DATA:0000)
Initialization system fault
  1. Restart the inverter.
  2. If it is still not resolved, contact the factory's customer service.
OV-TEM
(1032 DATA:0000)
Over Temperature
  1. Check whether the inverter installation position meets the requirements of the user manual.
  2. Try to reduce the ambient temperature.
  3. Restart the inverter after fifteen minutes.
  4. If the error persists, please contact the factory's customer service.
PV Isolation Protection 01 (1033 DATA:0001) DC bus undervoltage
  1. Check whether the PV strings have insulation problems.
  2. Check whether the PV cable is damaged.
PV Isolation Protection 02 (1033 DATA:0002) PV negative ground fault
Leakage Current Protection 01
(1034 DATA:0001)
Leakage current protection
  1. Connect each string component individually to determine if it is caused by a component problem. If there is no error when inserting one of the string components, it can be determined that it is a string problem. Check whether the string in question is broken or not.
  2. If this error is only caused by a rainy day or a certain time of the morning, it is because the aging of the module causes the leakage current to be too large. When the weather is fine or the air humidity is reduced, the error will be cleared automatically. Can be resolved through remote upgrade software.
Leakage Current Protection 02(1034 DATA:0002)
Leakage Current Protection 03
(1034 DATA:0003)
Leakage Current Protection 04
(1034 DATA:0004)
ILeak-Check
(1039 DATA:0000)
Leakage current sensor failure
  1. Upgrade software to the latest version. 2. If the fault persists, please contact the factory's customer service.
UN-TEM
(103A DATA:0000)
Under Temperature
  1. Check if the ambient temperature is too low and restart the inverter. If it has not been eliminated, contact the factory's customer service.
Message Name Information Description Troubleshooting Suggestion
Relay-FAULT
(1035 DATA:0000)
Relay check fail
  1. Restart the inverter
  2. If it is still not resolved, contact the factory's customer service.
DSP-B-Com-Fau (1036 DATA:0000) Comm. failure between main and slave DSP
DCInj-FAULT
(1037 DATA:0000)
High DC injection current
12Power-FAULT
(1038 DATA:0000)
12V power supply fault
AFCI-Check
(1040 DATA:0000)
AFCI module self-detect fault
  1. Restart the inverter.
  2. If it is still not resolved, contact the factory's customer service.
ARC-FAULT
(1041 DATA:0000)
Detect arc in DC circuit
  1. Check for arc in the inverter connection and restart the inverter.
GRID-INTF02
(1046 DATA:0000)
Power grid disturbance 02
  1. Check if the grid side is not healthy.
  2. Restart the inverter. If it is still not removed, contact the factory's customer service.
IG-AD
(1047 DATA:0000)
Grid current sampling fail
  1. Restart the inverter
  2. If it is still not resolved, contact the factory's customer service.
IGBT-OV-I
(1048 DATA:0000)
Over IGBT current
State 2 excursion (2043H) G100 State 2 excursion The alarm appears when the current flow exceeds "G100V2 Backflow Current" under scenarios stipulated by G100 standard. As required by G100, "State 2 excursion" alarm should be manually reset. Please select the "Settings -> EPM Setting -> Built-in EPM Setting->G100V2 Alarm Clear" to reset.
Fail Safe
2010H
Meter Communication Fail
  1. Check the meter communication and restart the inverter.
  2. If it is still not resolved, contact the factory's customer service.
MET_SEL_FAIL 2019H Meter type select fail Please select the correct smart meter type in inverter setting based on the smart meter actually connected to the inverter.
CT Fault 201AH CT Fault The alarm occurs when the CT connected to the inverter or the CT connected to the smart meter loses connection.
  1. When the alarm occurs with the "G100V2 Control Switch" on, please check and repair the CT wiring first, then select "Settings -> EPM Setting -> Built-in EPM Setting-> G100V2 Alarm Clear" to reset the alarm.
  2. When the alarm occurs with the "G100V2 Control Switch" off, please check and repair the CT wiring and restart the inverter.
  3. If it is still not resolved, contact the factory's customer service.
DRM_LINK_FAIL 2018H DRM link fail Please check if your DRM control device/ logic interface or its wiring is normal. If there is actually no DRM control device/ logic interface connected, please disable the DRM function in inverter settings.
DRM_CTL_Off 201BH DRM control inverter to stop Please check if the DRM function is enabled. This alarm indicates the DRM function controls the inverter to stop. If this is not expected, please disable the DRM function.
AFCI-Comm-Fail 2041H AFCI communication fail
  1. Restart the inverter.
  2. If it is still not resolved, contact the factory's customer service.
AFCI-CTModule-Fail 2042H AFCI CT module fail

Table 8.1 Fault message and description

information NOTE:
If the inverter displays any alarm message as listed in Table 8.1; please turn off the inverter and wait for 5 minutes before restarting it.
If the failure persists, please contact your local distributor or the service center.

  1. Serial number of Solis Single Phase Inverter;
  2. The distributor/dealer of Solis Single Phase Inverter (if available);
  3. Installation date.
  4. The description of problem (i.e. the alarm message displayed on the LCD and the status of the LED status indicator lights. Other readings obtained from the Information submenu will also be helpful.);
  5. The PV array configuration (e.g. number of panels, capacity of panels, number of strings, etc.);
  6. Your contact details.

Specifications

Model S6-GR1P7K03-NV-ND
Max. DC input voltage (Volts) 550
Rated DC voltage (Volts) 330
Startup voltage (Volts) 60
MPPT voltage range (Volts) 50-500
Max. input current (Amps) 20/20/20
Max short circuit input current (Amps) 25/25/25
MPPT number/Max input strings number 3/3
Classification AFCI Type: F-l-AFPE-1-3-1
No.of monitored strings per input port 1
No.of input ports per channel 3
No.of monitored channels 1
Rated channel curente (Amps) 20+20+20
Maximum current per input port (Amps) 20
Rated interruption current (Amps) 20
Rated output power (Watts) 7000
Max. output power (Watts) 7000
Max. apparent output power (VA) 7000
Rated grid voltage (Volts) 1/N/PE, 220/230
Rated output current (Amps) 31.8/30.4
Max. output current (Amps) 31.8
Power Factor (at rated output power) >0.99 (0.8 leading - 0.8 lagging)
THDi (at rated output power) <3%
Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 45-55 or 55-65
Max.efficiency 98.0%
EU efficiency 97.1%
Dimensions 338W*512H*220D (mm)
Weight 16.3kg
Topology Transformerless
Self consumption (night)
Operating ambient temperature range -25℃~+60℃
Relative humidity 0-100%
Ingress protection IP66
Noise emission (typical) <40 dB(A)
Cooling concept Natural convection
Max.operation altitude 4000m
Grid connection standard G99, IEC 62116, IEC 61727, EN 50530,MEA,PEA
Safety/EMC standard IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4
DC connection MC4 connector
AC connection OT Terminal
Display LED, BLUETOOTH+APP
Communication connections RS485, Optional: Wi-Fi, GPRS
Warranty Terms 5 Years (Extend to 20 Years)
Model S6-GR1P8K03-NV-ND
Max. DC input voltage (Volts) 550
Rated DC voltage (Volts) 330
Startup voltage (Volts) 60
MPPT voltage range (Volts) 50-500
Max. input current (Amps) 20/20/20
Max short circuit input current (Amps) 25/25/25
MPPT number/Max input strings number 3/3
Classification AFCI Type: F-l-AFPE-1-3-1
No.of monitored strings per input port 1
No.of input ports per channel 3
No.of monitored channels 1
Rated channel curente (Amps) 20+20+20
Maximum current per input port (Amps) 20
Rated interruption current (Amps) 20
Rated output power (Watts) 8000
Max. output power (Watts) 8000
Max. apparent output power (VA) 8000
Rated grid voltage (Volts) 1/N/PE, 220/230
Rated output current (Amps) 36.4/34.8
Max. output current (Amps) 36.4
Power Factor (at rated output power) >0.99 (0.8 leading - 0.8 lagging)
THDi (at rated output power) <3%
Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 45-55 or 55-65
Max.efficiency 98.0%
EU efficiency 97.1%
Dimensions 338W*512H*220D (mm)
Weight 16.3kg
Topology Transformerless
Self consumption (night)
Operating ambient temperature range -25℃~+60℃
Relative humidity 0-100%
Ingress protection IP66
Noise emission (typical) <40 dB(A)
Cooling concept Natural convection
Max.operation altitude 4000m
Grid connection standard G99, IEC 62116, IEC 61727, EN 50530,MEA,PEA
Safety/EMC standard IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4
DC connection MC4 connector
AC connection OT Terminal
Display LED, BLUETOOTH+APP
Communication connections RS485, Optional: Wi-Fi, GPRS
Warranty Terms 5 Years (Extend to 20 Years)
Model S6-GR1P9K03-NV-ND
Max. DC input voltage (Volts) 550
Rated DC voltage (Volts) 330
Startup voltage (Volts) 60
MPPT voltage range (Volts) 50-500
Max. input current (Amps) 20/20/20
Max short circuit input current (Amps) 25/25/25
MPPT number/Max input strings number 3/3
Classification AFCI Type: F-l-AFPE-1-3-1
No.of monitored strings per input port 1
No.of input ports per channel 3
No.of monitored channels 1
Rated channel curente (Amps) 20+20+20
Maximum current per input port (Amps) 20
Rated interruption current (Amps) 20
Rated output power (Watts) 9000
Max. output power (Watts) 9000
Max. apparent output power (VA) 9000
Rated grid voltage (Volts) 1/N/PE, 220/230
Rated output current (Amps) 40.9/39.1
Max. output current (Amps) 40.9
Power Factor (at rated output power) >0.99 (0.8 leading - 0.8 lagging)
THDi (at rated output power) <3%
Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 45-55 or 55-65
Max.efficiency 98.0%
EU efficiency 97.1%
Dimensions 338W*512H*220D (mm)
Weight 16.3kg
Topology Transformerless
Self consumption (night)
Operating ambient temperature range -25℃~+60℃
Relative humidity 0-100%
Ingress protection IP66
Noise emission (typical) <40 dB(A)
Cooling concept Natural convection
Max.operation altitude 4000m
Grid connection standard G99, IEC 62116, IEC 61727, EN 50530,MEA,PEA
Safety/EMC standard IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4
DC connection MC4 connector
AC connection OT Terminal
Display LED, BLUETOOTH+APP
Communication connections RS485, Optional: Wi-Fi, GPRS
Warranty Terms 5 Years (Extend to 20 Years)
Model S6-GR1P10K03-NV-ND
Max. DC input voltage (Volts) 550
Rated DC voltage (Volts) 330
Startup voltage (Volts) 60
MPPT voltage range (Volts) 50-500
Max. input current (Amps) 20/20/20
Max short circuit input current (Amps) 25/25/25
MPPT number/Max input strings number 3/3
Classification AFCI Type: F-l-AFPE-1-3-1
No.of monitored strings per input port 1
No.of input ports per channel 3
No.of monitored channels 1
Rated channel curente (Amps) 20+20+20
Maximum current per input port (Amps) 20
Rated interruption current (Amps) 20
Rated output power (Watts) 10000
Max. output power (Watts) 10000
Max. apparent output power (VA) 10000
Rated grid voltage (Volts) 1/N/PE, 220/230
Rated output current (Amps) 45.5/43.5
Max. output current (Amps) 45.5
Power Factor (at rated output power) >0.99 (0.8 leading - 0.8 lagging)
THDi (at rated output power) <3%
Rated grid frequency (Hertz) 50/60
Operating frequency range (Hertz) 45-55 or 55-65
Max.efficiency 98.0%
EU efficiency 97.1%
Dimensions 338W*512H*220D (mm)
Weight 16.3kg
Topology Transformerless
Self consumption (night)
Operating ambient temperature range -25℃~+60℃
Relative humidity 0-100%
Ingress protection IP66
Noise emission (typical) <40 dB(A)
Cooling concept Natural convection
Max.operation altitude 4000m
Grid connection standard G99, IEC 62116, IEC 61727, EN 50530,MEA,PEA
Safety/EMC standard IEC/EN 62109-1/-2, IEC/EN 61000-6-1/-2/-3/-4
DC connection MC4 connector
AC connection OT Terminal
Display LED, BLUETOOTH+APP
Communication connections RS485, Optional: Wi-Fi, GPRS
Warranty Terms 5 Years (Extend to 20 Years)

Ginlong Technologies Co., Ltd.
No. 57 Jintong Road, Binhai Industrial Park, Xiangshan, Ningbo,
Zhejiang, 315712, P.R.China.

Tel: +86 (0)574 6578 1806
Fax: +86 (0)574 6578 1606

Email: info@ginlong.com
Web: www.ginlong.com

Please adhere to the actual products in case of any discrepancies in this user manual.

If you encounter any problem on the inverter, please find out the inverter S/N and contact us, we will try to respond to your question ASAP.

Safety Instructions

Safety Symbols

Safety symbols used in this manual, which highlight potential safety risks and important safety information, are listed as follows:


WARNING symbol indicates important safety instructions, which if not correctly followed, could result in serious injury or death.

information NOTE:
NOTE symbol indicates important safety instructions, which if not correctly followed, could result in some damage or the destruction of the inverter.


CAUTION, RISK OF ELECTRIC SHOCK symbol indicates important safety instructions, which if not correctly followed, could result in electric shock.

burn hazard
CAUTION, HOT SURFACE symbol indicates safety instructions, which if not correctly followed, could result in burns.

General Safety Instructions


Only devices in compliance with SELV (EN 69050) may be connected to the RS485 and USB interfaces.


Please don't connect PV array positive(+) or negative(-) to ground, it could cause serious damage to the inverter.

information NOTE:
PV module used with inverter must have an IEC 61730 Class A rating.


Electrical installations must be done in accordance with the local and national electrical safety standards.


Risk of electric shock from energy stored in capacitors of the Inverter.
Do not remove cover for 5 minutes after disconnecting all power sources (service technician only). Warranty may be voided if the cover is removed without unauthorized.

burn hazard
The surface temperature of the inverter can exceed 75℃ (167F).
To avoid risk of burns, DO NOT touch the surface when inverter is operating.
The inverter must be installed out of reach of children.


The PV array (Solar panels) supplies a DC voltage when they are exposed to sunlight.


To reduce the risk of fire, over-current protective devices (OCPD) are required for circuits connected to the Inverter.
The DC OCPD shall be installed per local requirements. All photovoltaic source and output circuit conductors shall have disconnects that comply with the NEC Article 690, Part II. All Solis S6 Single Phase Inverters feature an integrated
DC switch.


Risk of electric shock. Do not remove cover. There is no user serviceable parts inside. Refer servicing to qualified and accredited service technicians.


Do not touch any inner live parts until 5 minutes after disconnection from the utility grid and the PV input

Notice For Use

The inverter has been constructed according to the applicable safety and technical guidelines. Use the inverter in installations that meet the following specifications only:

  • Permanent installation is required.
  • The electrical installation must meet all the applicable regulations and standards.
  • The inverter must be installed according to the instructions stated in this manual.
  • The inverter must be installed according to the correct technical specifications.
  • To startup the inverter, the Grid Supply Main Switch (AC) must be switched on, before the solar panel's DC isolator shall be switched on. To stop the inverter, the Grid Supply Main Switch (AC) must be switched off before the solar panel's DC isolator shall be switched off.

Documents / Resources

References

Download manual

Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.

Download SOLIS S6, S6-GR1P(7-10)K03-NV-ND - Inverter Manual

Advertisement

Need help?

Need help?

Do you have a question about the S6 and is the answer not in the manual?

Questions and answers

Table of Contents