Page 1
User Manual for S6 Series Grid Inverter Applicable models S6-GC25K-US S6-GC33K-US S6-GC36K-US S6-GC40K-US S6-GC50K-US S6-GC60K-US S6-GC-30K-LV-US Version 1.0, Release Date: 08,2023...
Page 2
● Airborne noise produced depending on the environment. ● Potential flammability hazards. ● Solis will not be held liable for defects or malfunctions arising from: ● Improper use of the equipment. ● Deterioration resulting from transportation or particular environmental conditions.
Page 3
Table of Contents Introduction Safety Installation Communication Commissioning Normal Operation Maintenance Troubleshooting Specifications 10 Appendix...
1. Introduction User Manual 1.1 Product Description Solis Three phase Inverters convert DC power from the photovoltaic(PV) array into alternating current(AC) power that can satisfy local loads as well as feed the power distribution grid. This manual covers the three phase inverter models listed below: S6-GC25K-US, S6-GC33K-US, S6-GC36K-US, S6-GC40K-US, S6-GC50K-US, S6-GC60K-US.
1. Introduction User Manual 1.2 Front Panel Display Figure 1.3 Front Panel Display 1.3 LED Status Indicator Lights There are three LED status indicator lights in the front panel of the inverter. POWER LED (red) indicates the power status of the inverter. OPERATION LED (green) indicates the operation status.
1. Introduction User Manual 1.4 Unpacking The inverter ships with all accessories in one carton. When unpacking, please verify all the parts listed below are included: DC connector Description Quantity Remarks Part # Inverter Mounting bracket Hex bolt M6*12 Fastening screw 12 for 25K-40K Staubli Electrical Connectors AG PV-KBT4-EVO 2/6I-UR...
Local rules in waste management shall be respected . SAVE THESE INSTRUCTIONS – This manual contains important instructions for Models S6-GC25K-US, S6-GC33K-US, S6-GC36K-US, S6-GC40K-US, S6-GC50K-US, S6-GC60K-US S6-GC30K-LV-US that shall be followed during installation and maintenance of the inverter.
2. Safety Instruction User Manual 2.1 Safety symbols Safety symbols used in this manual, which highlight potential safety risks and important safety information, are listed below: WARNING Symbol indicates important safety instructions, which if not correctly followed, could result in serious injury or death. NOTE Symbol indicates important safety instructions, which if not correctly followed, could result in damage to or the destruction of the inverter.
Switch is turned on. To stop the inverter, see power down instruction on page 40 Section 6.2. 2.4 Protection Circuitry and Controls To meet relevant codes and standards, the Solis U.S. three phase inverter line is equipped with protective circuitry and controls. These include Arc Fault Circuit Interrupter (AFCI) and Anti-Islanding Protection.
3. Installation User Manual NOTE For additional installation details, watch the installation video in the link below https://youtu.be/nkYMf-oukIw 3.1 Environmental considerations 3.1.1 Location selection for the inverter When selecting a location for the inverter, consider the following: WARNING: Risk of fire Despite careful construction, electrical devices can cause fires.
Consult the specifications section (section 9) for additional environmental conditions (protection rating, temperature, humidity, altitude, etc.). 3.1.2.2 Horizontal installation For horizontal installation, this model of Solis inverter should be mounted horizontally (upwards in more than 15 degrees off the horizontal plane). 3.1.2.3 Vertical wall installation For vertical installation, this model of Solis inverter should be mounted vertically (90 degrees or backwards in less than or equal to 15 degrees).
Page 15
3. Installation User Manual ≥20in ≥20in ≥20in ≥30in Figure 3.2 Clearance distances requirement for the inverter ≥20in ≥20in ≥30in ≥40in ≥20in Figure 3.3 Distances required between inverters when multiple inverters are installed NOTE Nothing should be stored on or placed against the inverter.
3. Installation User Manual 3.1.2.4 Avoiding direct sunlight Installation of the inverter in a location exposed to direct sunlight should to be avoided. Direct exposure to sunlight could cause: ● Power output limitation (with a resulting decreased energy production by the system). ●...
3. Installation User Manual Figure 3.5 Inverter handles WARNING Due to the weight of the inverter, contusions or bone fractures could occur when incorrectly lifting and mounting the inverter. When mounting the inverter, take the weight of the inverter into consideration.
3. Installation User Manual 3.3.1 Wall mounting 1. Use the suitable mounting screws to attach the bracket on the wall. Torque:22.1-25.8 ft.lbs Bracket Suitable mounting screws Figure 3.7 Inverter wall mounting 2. Take off the Protective cover on the back of AC wiring box. Figure 3.8 3.
Page 19
3. Installation User Manual 4. Use the Connecting plate with screws to fix the AC wiring box on the bracket. Figure 3.10 5. Lift the inverter and hang it on the bracket, and slide down to make sure they match perfectly.
Page 20
3. Installation User Manual 6. Fix the AC wiring box to the inverter by screws. Figure 3.12...
3. Installation User Manual 3.3.2 Rack mounting The steps to mounting to the rack are listed below: 1. Select a location for the inverter With a NEMA 4X protection rating, the inverter can be installed both outdoors and indoors. When the inverter is running, the temperature of the chassis and heat sink will be higher than the ambient .
Page 22
3. Installation User Manual 3. Install mounting plate a. Remove the bracket and fasteners from the packaging. Mark the position for hole drilling according to the hole positions of the bracket. Figure 3.15 Mark the position for hole b. Drill the marked holes. It is recommended to apply anti-corrosive paint at the hole for corrosion protection.
Page 23
3. Installation User Manual c. Align the mounting plate with the holes, Insert the combination bolt (M10X40)through the mounting plate into the hole. Secure the bracket to the metal frame firmly with the supplied fastener. Torque the nut to 25.8 ft.lbs. Figure 3.17 Combination bolt d.
3. Installation User Manual 3.4 Electrical Connections Inverter design uses PV style quick-connect terminal. The inverter cover does not need to be opened during DC electrical connection. The labels located on the bottom of the inverter are described below in table 3.1. All electrical connections must be in accordance with local or national standard.
3. Installation User Manual 3.4.1 Grounding The inverter must be grounded for safety. Two methods are provided. 1. Connect the AC grounding cable. (See Section 3.4.3) 2. Connect the equipment grounding terminal on the heatsink described below. To connect the grounding terminal on the heat sink, please follow the steps below: 1.
Page 26
3. Installation User Manual NOTE B (insulation stripping length) is 2mm-3mm longer than A (OT cable terminal crimping area). 4. Insert the stripped wire into the OT terminal crimping area and crimp with a hydraulic crimp tool. (see Figure 3.18) NOTE After crimping the terminal to the wire, inspect the connection to ensure the terminal is solidly crimped to the wire.
3. Installation User Manual 3.4.2 Connect PV side of inverter WARNING Before connecting the inverter, make sure the PV array open circuit voltage is within the limit of the inverter. Otherwise, the inverter could be damaged. WARNING DO NOT connect the PV array positive or PV array negative cable to ground. This can cause serious damage to the inverter! WARNING MAKE SURE the polarity of the PV array output conductors matches...
Page 28
3. Installation User Manual Figure 3.25 Connect the DC Figure 3.24 Multimeter measurement Connectors to the Inverter Traverse area(mm²) Outside diameter of Cable type Recommended cable(mm) Range value 4.0~6.0 PV Wire 5.5~9.0 (12~10AWG) (12AWG) UL 4703 Listed Caution If DC inputs are accidently reversely connected or inverter is faulty or not working properly, it is NOT allowed to turn off the DC switch.
3. Installation User Manual 3.4.2.1 DC connection high voltage danger notice CAUTION RISK OF ELECTRIC SHOCK Do not touch an energized DC conductor. There is high voltages present when PV modules are exposed to light causing a risk of death due to an electric shock from touching a DC conductors! Only connect the DC cables from the PV module to the inverter as described in this manual.
Page 30
ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. Operating ambient temperature and humidity must be factored and considered when selecting OCPD for the inverter output. Recommended current Rated Max. output Inverter range for OCPD (A) voltage(Vac) current (Amps) S6-GC25K-US 33.1 S6-GC33K-US 43.7 S6-GC36K-US 47.6 S6-GC40K-US 52.9 S6-GC50K-US 66.2...
Page 31
3. Installation User Manual 3.4.3.2 Wiring procedure All electrical installations must be carried out in accordance with the local standards and the National Electrical Code® ANSI/NFPA 70 or the Canadian Electrical Code® CSA C22.1. The AC and DC electric circuits are isolated from the enclosure. If required by section 250 of the National Electrical Code®, ANSI/NFPA 70, the installer is responsible for grounding the system.
Page 32
3. Installation User Manual The steps to assemble the AC grid terminals are listed as follows: 1. Strip the end of AC cable insulating jacket about 11.8 inch then strip the end of each wire. Figure 3.27 Strip AC cable NOTE S2 (insulation stripping length) is 2mm-3mm longer than S1.
Page 33
3. Installation User Manual 3. LOTO the AC breaker disconnect to ensure it does not close unexpectedly. 4. Remove the 2 screws on the inverter junction box and remove the junction box cover. (See figure 3.29) Figure 3.29 Remove the junction box cover 5.
4. Comm. & Monitoring User Manual 4.1 RS485 Communication The inverter package will include a 12-Pin connector. The Pin definition is shown below. Facing the connector, Pin 1 is on the left of the first row. The rest polarity is showing in below diagram. Definition Description RS485 A IN...
Page 35
Multiple inverters can be monitored through RS-485 and Ethernet daisy chain configuration. Inverter1 PC monitoring PV Strings Inverter2 PV Strings Datalogger Rs485 PV Strings Inverter32 Internet Figure 4.2 Multiple inverter monitoring system Inverter1 Inverter2 Inverter10 •••• Rs485 Figure 4.3 Inverter monitoring with Solis 4G & WIFI stick...
5.1 Selecting the appropriate grid standard 5.1.1 Verifying grid standard for country of installation Solis inverters are used worldwide and feature preset standards for operating on any grid. Although the grid standard is set at the factory, it is essential the grid standard be verified for the country of installation before commissioning.
5. Commissioning User Manual 3. Use the UP/DOWN keys to highlight the SELECT STANDARD option. Press enter to select. Select Standard Grid ON/OFF Figure 5.3 4. Select the grid standard for the country of installation. YES=<ENT> NO=<ESC> Standard:UL-480V-A Figure 5.4 Press the UP or DOWN key to select the standard.
Input voltages higher than the maximum value accepted by the inverter (see “Specifications” in Section 9) may damage the inverter. Although Solis inverters feature reverse polarity protection, prolonged connection in reverse polarity may damage these protection circuits and/or the inverter.
User Manual 5.4.1.2.1 Detection of leakage to ground Solis inverters are transformer-less and do not have an array connection to ground. Any measurement of a fixed voltage between ground and either the positive or negative string wiring indicates a leakage (ground fault) to ground and must be corrected prior to energizing the inverter or damage to the inverter may result.
The red DC POWER LED and LCD will be continuously lit. 4. Solis inverters are powered from the DC side. When the inverter detects DC voltage that is within start-up and operating ranges, the inverter will turn on. After turn- on, the inverter will check internal parameters, sense and monitor AC voltage, frequency rate and the stability of the supply grid.
2. Settings 3. Advanced Info. 4. Advanced Settings 6.4 Information The Solis three Phase Inverter main menu provides access to operational data and information. The information is displayed by selecting "Information" from the menu and then by scrolling up or down.
Page 42
6. Normal operation User Manual Display Description Duration VPV_Total: Shows input voltage total. VPV_Total: 1000.0V 5 sec IPV_Total: +99.0A IPV_Total: Shows input current total. V_A: Shows the grid's voltage value. V_A: 345.7V 5 sec I_ A: 109.0A I_A: Shows the grid's current value. V_C: Shows the grid's voltage value.
This function is used to set the address when muti inverters are connected to three monitoring. The address number can be assigned from “01”to “99”(see Figure 6.4). The default address number of Solis Three Phase Inverter is “01”. YES=<ENT> NO=<ESC>...
6. Normal operation User Manual 6.6 Advanced Info - Technicians Only NOTE To access to this area is for fully qualified and accredited technicians only. Enter menu “Advanced Info.” and “Advanced settings” (need password). Select “Advanced Info.” from the Main Menu. The screen will require the password as below: YES=<ENT>...
6. Normal operation User Manual 6.6.3 Version The screen shows the model version of the inverter. And the screen will show the software ver by pressing the UP and DOWN at the same time.(see Figure 6.7). Model: 08 Software Version: D20001 Figure 6.7 Model Version and Software Version 6.6.4 Daily Energy The function is for checking the energy generation for selected day.
6. Normal operation User Manual 6.6.6 Yearly Energy The function is for checking the energy generation for selected year. YES=<ENT> NO=<ESC> Select: 2019 Figure 6.12 Select year for yearly energy Press DOWN key to move the cursor to day and year, press UP key to change the digit. Press Enter after the date is fixed.
6. Normal operation User Manual 6.7 Advanced Settings - Technicians Only NOTE To access to this area is for fully qualified and accredited technicians only. Please follow 6.4 to enter password to access this menu. Select Advanced Settings from the Main Menu to access the following options: 1.
Page 48
6. Normal operation User Manual OV-G-F1: 61-66Hz OV-G-V1: 304.8---332.6V OV-G-F1-T: 180---1000S OV-G-V1-T: 1---13S OV-G-F2: 61.8-66Hz OV-G-V2: 304.8---360.3V OV-G-F2-T: 0.16---1000S OV-G-V2-T: 0.12S UN-G-F1: 50-59Hz UN-G-V1: 14---243.9V UN-G-F1-T: 180---1000S UN-G-V1-T: 2---50S UN-G-F2: 50-57Hz UN-G-V2: 14---138.6V UN-G-V2-T: 0.16---21S UN-G-F2-T: 0.16---1000S Startup-T: 10-600S Restore-T: 10-600S Table 6.2 Setting ranges for User-Def NOTE The initial value of the User-Def standard is for reference only.
6. Normal operation User Manual 6.7.2 Grid ON/OFF This function is used to start up or stop the power generation of Solis Three Phase Inverter (see Figure 6.18). Grid ON Grid OFF Figure 6.18 Set Grid ON/OFF Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key to save the setting.
6. Normal operation User Manual 6.7.5 Power Control Active and reactive power can be set through power setting button. There are 5 item for this sub menu: 1. Set output power 2. Set Reactive Power 3. Out_P With Restore 4. Rea_P With Restore 5.
6.7.8.1 Working Mode Set There are TWO situations with different grid standards selected. 6.7.8.1.1 With UL Standard selected NOTE The following modes are for "UL-480V-18”. Solis US version inverters have Seven working modes: 1. NULL 2. Volt-watt 3. Volt-Var 4. Fixed-PF 5.
Page 52
6. Normal operation User Manual 1.NULL Description: Inverter is not under any working mode. 2. Volt-Watt (Not Required) Description: Inverter will change the active output power based on voltage change. Note: This Setting is NOT required by UL1741SA Standards. NOTE This function is for maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.
Page 53
6. Normal operation User Manual 4.Fixed-PF Description: Inverter will output power with fixed power factor. Setting Range: -0.8 to +0.8 Default value is PF = 1 YES=<ENT> NO=<ESC> Power Factor:+1.00 Figure 6.23 Fixed-PF Figure 6.24 PF Range 5. Reac-power (Not Required) Description: Inverter will generate reactive power based on changing output power.
Page 54
6. Normal operation User Manual 7.VgWatt-UL Description: Inverter will change the active output power based on voltage change. Note: This is the Volt-Watt Setting for UL1741SA Standards. 100% of Input Power AC Volt Vmin Vnom Vstart Vstop Vmax Figure 6.25 Volt-Watt characteristic Default Settings for UL1741SA: Rated 480V Grid V1:less than V2...
Page 55
6. Normal operation User Manual 6.7.8.1.2 With Rule21 Standard selected NOTE The following modes are for "R21P3-48A". Solis US version inverters have ten working modes: 1. NULL 6. Power -PF 2. Volt-watt 7. VgWatt-UL 3. Volt-Var 8. Volt-Var and Volt Watt enabled 4.
Page 56
6. Normal operation User Manual Default Settings for Rule21 Standards: Rated 480V Grid V1:less than Vstart V2: less than Vstart V3 (Vstart): (480-576V) Default 508.8V V4: (Vstop): (480-576V) Default 528V P1:100% P2:100% P3: 100% P4:0% 3. Volt-Var Description: Inverter will change the reactive output power based on voltage change. Q1,cap Q2=Q3=0 Vnom...
Page 57
6. Normal operation User Manual YES=<ENT> NO=<ESC> Power Factor:+1.00 Figure 6.30 Fixed-PF Figure 6.31 PF Range 5. Reac-power (Not Required) Description: Inverter will generate reactive power based on changing output power. Note: This Setting is NOT required by Rule21 Standards. NOTE This function is for maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power.
Page 58
6. Normal operation User Manual 8. Enable both Volt-Var and Volt-Watt modes Description: Rule21 requires both Volt-var and Volt-watt modes can be enabled. To set both modes (Volt-var in high priority) Step 1: Select and set Volt-watt mode at first. Step 2: Enter "Working Mode"...
Page 59
6. Normal operation User Manual 6.7.8.2 Power Rate Limit This function is used for change Power Ramp-up rate. When inverter start up or input string MPPT changes, inverter power ramp-up rate is limited in this menu. The default setting is stop (disable). The setting range from 1% to 100%, means inverter power change rate per minute.
Page 60
6. Normal operation User Manual 6.7.8.4 10mins Voltage Set This function is disabled and not used for the US. NOTE This function is for maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power. 6.7.8.5 Power Priority This setting is used to set the priority between Active Power Control (Watt) and Reactive Power Control (Var).
6. Normal operation User Manual 6.7.8.8 Freq-Watt This setting is used to control real power based on the frequency excursion This setting is applicable when Rule21 Standards are selected. → Start Freq: 60.50Hz WGradient: 040% Figure 6.39 Freq-Watt (1) Start Freq: This is the frequency that active power reduction starts. WGradient: This is the active power reduction rate in terms of the frequency.
6. Normal operation User Manual 6.7.10 HMI Updater NOTE This section is applicable to maintenance personnel only. Selecting “Updater” displays the sub-menu shown below: HMI Current Ver.: 02 YES=<ENT> NO=<ESC> Figure 6.42 Updater is for updating LCD firmware. Press the ENTER key to start the process. Press the ESC key to return to the previous menu.
6. Normal operation User Manual 6.7.13 Debug Parameter NOTE This section is applicable to maintenance personnel only. Debug Parameter as shown as below: → S16DAT1: +0000 S16DAT2: +0000 S16DAT3: +0000 S16DAT4: +0000 S16DAT5: +0000 S16DAT6: +0000 S16DAT7: +0000 S16DAT8: +0000 Figure 6.44 Press the UP/DOWN keys to scroll through items.
6. Normal operation User Manual 6.7.14 DSP Update The function is used for updating the DSP. NOTE This function is applicable by maintenance personnel only, wrong operation will prevent the inverter from reaching maximum power. 6.7.15 Compensation Set This function is used to calibrate inverter output energy and voltage. It will not impact the energy count for inverter with RGM.
6. Normal operation User Manual 6.7.16 I/V Curve This function is used to scan the I/V characteristic curves of each PV strings. Set I/V Curve I/V Curve Scan Figure 6.47 I/V Curve 6.7.16.1 Set I/V Curve This setting can set the scanning voltage start point and the voltage interval. 850V 010V Figure 6.48 Set I/V Curve...
6. Normal operation User Manual 6.8 AFCI function Solis inverters have the built-in AFCI function which can detect the arc fault on the DC circuit and shut down the inverter to prevent a fire disaster. 6.8.1 Enable the AFCI function The AFCI function can be enabled in the following.
NOTE Never use any solvents, abrasives or corrosive materials to clean the inverter. 7.1 Anti-PID Function Solis inverter integrates optional Anti-PID module and it can recover the PID effect during night thus protect the PV system from degradation. Inverter Figure 7.1 The Anti-PID module repairs the PID effect of the PV module at night.
7. Maintenance User Manual NOTE If you need to maintain the inverter at night, please turn off the AC switch first, then turn off the DC switch, and wait 5 minutes before you do other operations. 7.2 Fan Maintenance If the fan does not work properly, the inverter will not be cooled effectively and it will affect inverter operation.
(5) minutes before restarting it (refer to Section 6.1). If the failure persists, please first contact your local distributor and then Solis Support Service. If you need to contact Solis Support Service, please go to http://www.ginlong.com/us Please have the following information available when contacting technical support: 1.
Page 70
8. Troubleshooting User Manual Alarms Cause Solution Test – DC switch OFF • Check PV connections • Input voltage low/missing • Check polarity No Information • Polarity reversed • Check voltage >200V (Blank Screen) • Main board damaged Test – DC Switch ON •...
Page 71
8. Troubleshooting User Manual Alarms Cause Solution Test – DC switch OFF • Check frequency at the inverter test points • If Frequency measures high, adjust upper limit with permission from utility OV-G-F: Over • Inverter detects grid • Check LCD reading, may be a bad Frequency as too high Grid Frequency measurement circuit...
Page 72
8. Troubleshooting User Manual Alarms Cause Solution Reset Inverter • DC switch OFF INI-FAULT: • Master and Slave DSP • Wait until all lights/LCD turn off Initialization have different values • DC switch ON Protection • Replace inverter Inspect installation OV-TEM: •...
9. Specifications User Manual Model S6-GC25K-US 1000 Start-up voltage (Volts) 160...1000 580...850 Max. input current (Amps) 3x40 Max short circuit input current (Amps) 3x63 Rated output power (Watts) 25000 Max. output power (Watts) 27500 Max. apparent output power (VA) 27500...
Page 74
9. Specifications User Manual Model S6-GC33K-US 1000 Start-up voltage (Volts) 160...1000 580...850 Max. input current (Amps) 3x40 Max short circuit input current (Amps) 3x63 Rated output power (Watts) 33000 Max. output power (Watts) 36300 Max. apparent output power (VA) 36300 Rated grid voltage (Volts) 3/PE~480 Max.
Page 75
9. Specifications User Manual Model S6-GC36K-US 1000 Start-up voltage (Volts) 160...1000 580...850 Max. input current (Amps) 3x40 Max short circuit input current (Amps) 3x63 Rated output power (Watts) 36000 Max. output power (Watts) 39600 Max. apparent output power (VA) 39600 Rated grid voltage (Volts) 3/PE~480 Max.
Page 76
9. Specifications User Manual Model S6-GC40K-US 1000 Start-up voltage (Volts) 160...1000 580...850 Max. input current (Amps) 3x40 Max short circuit input current (Amps) 3x63 Rated output power (Watts) 40000 Max. output power (Watts) 44000 Max. apparent output power (VA) 44000 Rated grid voltage (Volts) 3/PE~480 Max.
Page 77
9. Specifications User Manual Model S6-GC50K-US 1000 Start-up voltage (Volts) 160...1000 580...850 Max. input current (Amps) 4x40 Max short circuit input current (Amps) 4x63 Rated output power (Watts) 50000 Max. output power (Watts) 55000 Max. apparent output power (VA) 55000 Rated grid voltage (Volts) 3/PE~480 Max.
Page 78
9. Specifications User Manual Model S6-GC60K-US 1000 Start-up voltage (Volts) 160...1000 550...850 Max. input current (Amps) 4x40 Max short circuit input current (Amps) 4x63 Rated output power (Watts) 60000 Max. output power (Watts) 66000 Max. apparent output power (VA) 66000 Rated grid voltage (Volts) 3/PE~480 Max.
Page 79
9. Specifications User Manual Model S6-GC30K-LV-US 1000 Start-up voltage (Volts) 160...1000 340...680 Max. input current (Amps) 4x40 Max short circuit input current (Amps) 4x63 Rated output power (Watts) 30000 Max. output power (Watts) 30000 Max. apparent output power (VA) 30000 Rated grid voltage (Volts) 3/PE~208 Max.
10. Appendix User Manual Torque Parts Cover screws 1.5-1.7 ft.lbs Ground screws (Cover) 4.4-6.0 ft.lbs Ground screws (Internal) 11-15 ft.lbs AC terminals 11-15 ft.lbs 10.1 Temperature Derating Figure 10.1 For all models of inverter Comments: A thermal sensor inside the inverter is calibrated to determine ambient temperature. All inverters will begin a sloped derate at 50°C ending at 60% output power at 60°C.
Page 81
10. Appendices User Manual 10.2 Input Voltage Derating Figure 10.2 For all models of inverter 10.3 Output Voltage Derating Figure 10.3 For all models of inverter...
Page 82
10. Appendices User Manual 10.4 P-Q Capabilities at Nominal Output Power S6-GC60K-US Inverter is capable providing reactive power of ±39.6kVAR at nominal grid voltage and rated ambient temperature. S6-GC50K-US Inverter is capable providing reactive power of ±33kVAR at nominal grid voltage and rated ambient temperature. Chart below details inverter reactive power capabilities at various ambient temperature condition.
Page 83
10. Appendices User Manual 10.5 P-Q Capabilities at Nominal Output Power S6-GC40K-US Inverter is capable providing reactive power of ±26.4kVAR at nominal grid voltage and rated ambient temperature. S6-GC36K-US Inverter is capable providing reactive power of ±23.76kVAR at nominal grid voltage and rated ambient temperature. Chart below details inverter reactive power capabilities at various ambient temperature condition.
Page 84
10.6 P-Q Capabilities at Nominal Output Power S6-GC33K-US Inverter is capable providing reactive power of ±21.78kVAR at nominal grid voltage and rated ambient temperature. S6-GC25K-US Inverter is capable providing reactive power of ±16.5kVAR at nominal grid voltage and rated ambient temperature.
Page 85
10. Appendices User Manual 10.8 Default Grid Setting for UL-480-18 Parameter Range Default Description Set grid over-voltage protection 01 value L-L 528 V OV-G-V01 L-L 528-576 V OV-G-V01 L-N 304.8-332.6 V 304.8 V Set grid over-voltage protection 01 value L-N 13 S OV-G-V01-T 1-13 S...
Page 86
10. Appendices User Manual 10.8 Default Grid Setting for UL-480-18 Parameter Range Default Description Ramp-up Set Ramp-up power slew rate during start-up 100% 1-100% Slew Rate Reconnect 0.10-100% 0.33%V Set Ramp-up power slew rate during reconnect Slew Rate 10 S Volt Watt P3Tau 0.5-60 S Set power rise time for Volt Watt condition...
Page 87
10. Appendices User Manual 10.9 Product Certificate of Compliance...
Page 88
10. Appendices User Manual 10.9 Product Certificate of Compliance...
Page 89
10. Appendices User Manual 10.9 Product Certificate of Compliance...
Page 90
10. Appendices User Manual 10.10 Mechanical Dimension Drawing...
Page 91
Manufacturer: Ginlong Technologies Co.,Ltd., Ningbo, Zhejiang, P.R.China Toll-free: 866.438.8408 I Email: sales@ginlong.com I ussales@solisinverters.com usservice@solisinverters.com Web: www.ginlong.com I www.ginlong.com/us Please adhere to the actual products in case of any discrepancies in this user manual. Please record the serial number of your inverter and quote this when you contact us.
Need help?
Do you have a question about the S6-GC25K-US and is the answer not in the manual?
Questions and answers