Download Print this page

Features Of Cpu - Maple Systems PLC-ES1616P User Manual

Modular plc

Advertisement

► Built-in Functions
• PID Control
It operates 32 LOOP PID without PID module.
• Positioning
Up to 100Kpps 2 axes of Pulse Output (ES1616P, ES0808P)
• RTC
It reads time from RTC and saves it in the F device address.
• I/O reservation
It scans the module at the designated slot.
It refers to a reservation function which writes a program without I/O change in case of
expansion, damage or replacement.
• Online Edit
Program can be edited while in Run mode.
► Features
• SD/MMC Built-in
Scan program or firmware can be upgraded by SD memory card.
(Stop mode  Power off  Insert SD card  Power on  Run mode in 5 sec
 Firmware downloading (wait 20 sec)  Confirm flickering RUN, STOP, ERR LED
 Remove SD card  Power off  Power on)
• 20 kHz High Speed Counter (2 Channels) Built-in.
2 PH. 2/4 Multi. (2 PH. –10 kHz) Input mode possible, Voltage input type (Photocoupler
Insulated)
• Max. 3 communications can work simultaneously. (Ethernet, RS-232, RS-
485/422) MODBUS RTU/TCP, High-speed PLC Link,
User protocol, Loader protocol support, Remote access & up/download support.
• Abundant memory
Maximum 10k steps for a user program is available.
• Data reserved in case of power cut
Built-in Flash memory enabling permanent backup of the program without any separate battery.
Recommendations on using USB Cable
1. Recommended to use MAPLE SYSTEMS's shielded cable within 3 m length.
2. In case of using a PC that is vulnerable to noises, it is recommended to use USB Hub or
Isolator.