netvox R718PA1 User Manual

Wireless co sensor
Hide thumbs Also See for R718PA1:

Advertisement

Quick Links

R718PA1
Wireless CO Sensor
Wireless CO Sensor
R718PA1
User Manual
Copyright©Netvox Technology Co., Ltd.
This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in
strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX
Technology. The specifications are subject to change without prior notice.

Advertisement

loading
Need help?

Need help?

Do you have a question about the R718PA1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for netvox R718PA1

  • Page 1 This document contains proprietary technical information which is the property of NETVOX Technology. It shall be maintained in strict confidence and shall not be disclosed to other parties, in whole or in part, without written permission of NETVOX Technology. The specifications are subject to change without prior notice.
  • Page 2: Table Of Contents

    Table of Contents 1. Introduction ........................2 2. Appearance ........................3 3. Features ..........................3 4. Set Up Instruction ......................4 5. Data Report ........................5 5.1 ReportDataCmd ......................5 5.2 ReportConfiguration ....................6 5.3 GlobalCalibrateCmd ....................8 5.4 AlarmThresholdCmd ....................9 5.5 LoRaWANRejoin ......................
  • Page 3: Introduction

    Netvox and is compatible with the LoRaWAN protocol. R718PA1 can be connected to a corresponding carbon monoxide sensor (RS485) to report the concentration of carbon monoxide collected by the device to the corresponding gateway. The device is compatible with the LoRaWAN protocol.
  • Page 4: Appearance

    2. Appearance Indicator Function Key 3. Features  SX1276 wireless communication module  12V DC power supply  CO Concentration detection  Magnetic base  Protection level: Main body IP65 / IP67 (optional), CO Sensor IP54  Compatible with LoRaWAN Class A ...
  • Page 5: Set Up Instruction

    4. Set Up Instruction On/Off Power on DC12V adapter Turn on DC12V power supply, the green indicator flashing once means turn on successfully. Turn off (Restore to factory setting) Press and hold the function key for 5 seconds till the green indicator flashes 20 times. Power off Remove DC12V adapter.
  • Page 6: Data Report

    CO Concentration, Range: 0~2000ppm, Unit: 0.1ppm Threshold Alarm: Low CO Alarm = 0x00000000000040 (bit6=1) High CO Alarm = 0x00000000000080 (bit7=1) Note Please refer to Netvox LoRaWAN Application Command document and Netvox Lora Command Resolver http://www.netvox.com.cn:8888/cmddoc to resolve uplink data. 5.1 ReportDataCmd FPort: 0x06...
  • Page 7 Device NetvoxPayLoadData Type Type SoftwareVersion HardwareVersion DateCode Reserved 0x00 (1Byte) (1Byte) (4Bytes) (2Bytes,fixed 0x00) Battery Reserved 0x05 R718PA1 0x57 (1Byte,unit:0.1V) (2Bytes,0.1ppm) (2Bytes,0.1ppm) (2Bytes,0.1ppm) (1Byte,fixed0x00) ThresholdAlarm (7Bytes) Battery 0x12 Bit6_LowCOAlarm (1Byte,unit:0.1V) Bit7_HighCOAlarm Example of Uplink Packet 1: 01570500FFFF012CFFFF00 byte (01): Version (57): DeviceType —...
  • Page 8: Reportconfiguration

    MinTime MaxTime Reserved ConfigReportReq 0x01 (2Bytes Unit: s) (2Bytes Unit: s) (5Bytes,Fixed 0x00) Status Reserved ConfigReportRsp 0x81 (0x00_success) (8Bytes, Fixed 0x00) R718PA1 0x57 ReadConfig Reserved 0x02 ReportReq (9Bytes, Fixed 0x00) ReadConfig MinTime MaxTime Reserved 0x82 ReportRsp (2Bytes Unit: s) (2Bytes Unit: s) (5Bytes,Fixed 0x00) (1) The value of the maxtime should be greater than (report count *mintime+10), and mintime must be ≧10 (s)
  • Page 9: Globalcalibratecmd

    5.3 GlobalCalibrateCmd FPort: 0x0E (port = 14, Dec) Sensor Description PayLoad(Fix =9 Bytes) Type SetGlobal Channel Multiplier Divisor DeltValue Reserved 0x01 CalibrateReq (1Byte, 0_Channel1) (2Bytes, Unsigned) (2Bytes, Unsigned) (2Bytes, Signed) (2Bytes, Fixed 0x00) SetGlobal Channel Status Reserved 0x81 0x05 CalibrateRsp (1Byte, 0_Channel1) (1Byte,0x00_success) (7Bytes, Fixed 0x00)
  • Page 10: Alarmthresholdcmd

    5.4 AlarmThresholdCmd FPort: 0x10 (port = 16, Dec) CmdID CmdDescriptor Payload(10Bytes) (1Byte) SensorType(1Byte) Channel SetSensorAlarm 0x00_ Disable ALL SensorHighThreshold SensorLowThreshold 0x01 (1Byte) ThresholdReq SensorthresholdSet (4Bytes,Unit:0.1ppm) (4Bytes,Unit:0.1ppm) 0x00_Channel 1 0x0B_CO SetSensorAlarm Status Reserved 0x81 ThresholdRsp (0x00_success) (9Bytes,Fixed 0x00) SensorType(1Byte) GetSensorAlarm Channel(1Byte) 0x00_ Disable ALL Reserved 0x02...
  • Page 11: Lorawanrejoin

    5.5 LoRaWANRejoin Check if the device is still in the network. If the device is disconnected, it will automatically rejoin back to the network. FPort: 0x20 (port = 32, Dec) CmdID CmdDescriptor Payload(5Bytes) (1Byte) SetNetvoxLoRaWAN RejoinCheckPeriod RejoinThreshold 0x01 RejoinReq (4Bytes,Unit:1s) (1Byte) SetNetvoxLoRaWAN Status...
  • Page 12: Installation

    6. Installation 1. R718PA1 has a built-in magnet. It can be attached to the surface 2. The device periodically reports the data according to of an iron object conveniently and quickly when it is installed. Max Time. The default Max Time is 3min.
  • Page 13: Important Maintenance Instructions

    7. Important Maintenance Instructions Kindly pay attention to the following in order to achieve the best maintenance of the product: •Do not put the device near or submerge into water. Minerals in rain, moisture, and other liquids could cause corrosion of electronic components.