Summary of Contents for netvox R718B

  • Page 1 R718B Mode: Wireless Resistance Temperature Detector Wireless Resistance Temperature Detector R718B User Manual...
  • Page 2: Table Of Contents

    Table of Content 1. Introduction....................................................2 2. Appearance....................................................3 3. Main Features...................................................3 4.Set up Instruction..................................................4 5. Data Report....................................................5 6. Installation....................................................7 7. Important Maintenance Instruction............................................7...
  • Page 3: Introduction

    Introduction The R718B series equipment is the temperature detection based on the LoRaWAN open protocol. The external PT1000 measures the temperature and the device is compatible with the LoRaWAN protocol. LoRa Wireless Technology: LoRa is a wireless communication technology dedicated to long distance and low power consumption. Compared with other communication methods, LoRa spread spectrum modulation method greatly increases to expand the communication distance.
  • Page 4: Appearance

     Applicable to third-party platforms: Actility/ThingPark, TTN, MyDevices/Cayenne  Low power consumption and long battery life Note*: Battery life is determined by the sensor reporting frequency and other variables, please refer to http://www.netvox.com.tw/electric/electric_calc.html On this website, users can find battery life of various models in different configurations.
  • Page 5: Set Up Instruction

    4.Set up Instruction On/Off Insert batteries. Power on (users may need a flat blade screwdriver to open) Turn on Press and hold the function key for 3 seconds till the green indicator flashes once. Turn off Press and hold the function key for 5 seconds till green indicator flashes for 20 times. (Restore to factory setting) Power off Remove Batteries.
  • Page 6: Data Report

    R718B default Max Interval = 60min, Min Interval = 60min (if there is special custom shipment, the setting is changed according to customer requirements) The data can be decoded by the Netvox LoraWAN Application Command document and http://www.netvox.com.cn:8888/page/index Report configuration example:...
  • Page 7 Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V MaxTime MaxTime leeping(MinTime) leeping(MinTime) Wakes up and collects data Wakes up and collects data Wake up and collects data REPORTS 3.6V REPORTS 3.5V REPORTS 3.6V Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BtteryVoltageChange value. Example#2 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e.
  • Page 8: Installation

    6. Installation This product comes with waterproof function. When using it, the back of it can be adsorbed on the iron surface, or the two ends can be fixed to the wall with screws. Note: To install the battery, use a screwdriver or similar tool to assist in opening the battery cover. 7.