Brink Renovent Sky 300 Plus Enthalpy Installation Instructions Manual

Hide thumbs Also See for Renovent Sky 300 Plus Enthalpy:

Advertisement

Quick Links

INSTALLATION INSTRUCTIONS
(English)
WWW.BRINKAIRFORLIFE.NL
617605-A

Advertisement

loading
Need help?

Need help?

Do you have a question about the Renovent Sky 300 Plus Enthalpy and is the answer not in the manual?

Questions and answers

Summary of Contents for Brink Renovent Sky 300 Plus Enthalpy

  • Page 1 INSTALLATION INSTRUCTIONS (English) WWW.BRINKAIRFORLIFE.NL 617605-A...
  • Page 3 Children may not play with the appliance. If you need a new power cable, always order the replacement from Brink Climate Systems B.V. To prevent dangerous situations, a damaged mains connection must...
  • Page 4: Table Of Contents

    5.4.1 Connection of the power plug ............................. 5.4.2 “Brink Air Control” connection............................. Display ..................................Switching the appliance on and off ..........................General explanation “Brink Air Control” ........................View on Display ................................Main menu .................................. 6.4.1 Device information menu ............................6.4.2 Basic settings menu ..............................
  • Page 5: Delivery

    Chapter 1 Delivery Scope of delivery Before starting installation of the appliance, check that it has been supplied complete and undamaged. The scope of delivery of the Renovent Sky 300 (Plus) Enthalpy includes the following components: 1: Heat recovery appliance 2: Wall mounting bracket kit;...
  • Page 6: Accessories Renovent Sky 300 (Plus) Enthalpy

    Receiver wireless remote control (for battery version) 532172 Kit wireless remote control 2 positions (1 transmitter & 1 receiver) 532173 Kit wireless remote control 4 positions (1 transmitter & 1 receiver) 532174 Brink Air control 510498 Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 7 Chapter 1 Delivery G4 +F7 2x G4 G3 +F7 2X G3 G4 + Frame RH (humidity)-sensor 310657 G4 +F7 G3 +F7 Filterset 1 x ISO ePM 1 50% (F7) filter (1 pcs) 532001 Filterset 1x ISO Coarse 60% (G4) & 1x ISO ePM 1 50% (F7) (2 pcs) 532002 Servicetool 531961...
  • Page 8: Application

    • high efficiency connection of a simple 4-way switch is possible as well. If a 4-way switch is installed instead of a “Brink Air Con- trol”, the settings of the appliance can only be changed Renovent Sky 300 Enthalpy is available in two types: •...
  • Page 9: Version

    1185 x 644 x 310 Duct diameter [mm] Ø150 / Ø160 Weight [kg] Filter class ISO Coarse 60% (G4) Fan setting (factory setting) -”Brink Air Control” Max. 4-way switch Ventilation capacity [m Permissible resistance ducts system [Pa] 3 - 6 11 - 26...
  • Page 10: Connections And Dimensions

    Chapter 3 Version Connections and dimensions 1 Supply air   2 Exhaust air 3 Extract air 4 Outdoor air    5 Electric connections Fan graph Note: The value stated in the circle is the ca- pacity per fan (in Watt) Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 11: Exploded View Appliance

    Chapter 3 Version Exploded view 1 Extract air filter 2 Indoor temperature sensor 3 Enthalpy heat exchanger 4 Extract fan Locking screw front panel (mounted in front panel) 6 Supply air filter 7 Outdoor temperature sensor 8 Bypass 9 Control board 10 Connector X14 11 Supply fan Sleeve cable 230 V.
  • Page 12: Operation

    Chapter 4 Operation Description The appliance comes plug and play and operates fully auto- The air flow rate can be adjusted per ventilation mode. The matically. The extracted indoor air heats up the fresh, clean constant volume control system ensures that the air flow rate outdoor air.
  • Page 13: Installation

    Chapter 5 Installation Installation general Installation must take place under: • Any additional regulations of the local utilities. • The installation instructions for the Renovent Sky 300 (Plus) • Quality requirements ventilation systems dwellings. Enthalpy. • Quality requirements balanced ventilation in dwellings. •...
  • Page 14: Placing The Appliance For Ceiling Mounting

    Chapter 5 Installation 5.2.1 Placing the appliance for ceiling mounting Click! Appliance disconnecting from mounting bracket      install the supplied sleeve and end cap on condensate outlet!! Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 15: Placing The Appliance For Wall Mounting

    Chapter 5 Installation 5.2.2 Placing the appliance for wall mounting m i n . 2 5 m 4 9 0 m i n . 2 5 m 2 0 0 m 6 5 0 Click! Appliance disconnecting from mounting bracket ...
  • Page 16: Electric Connections

    5.3.2 “Brink Air Control” connection The “Brink Air control” (option) must be connected to the eBus ed on the outside of the appliance (see also §10.1). connector. This (detachable) 2-pole eBus connector is mount- nr.1 nr.2...
  • Page 17: Brink Air Control" Connection

    General explanation optional Brink Air control The “Brink Air control” display shows what the operating mode the operating keys. Ex factory the “Brink Air Control” is set for of the appliance is. Settings in the “Brink Air control” software of the English language.
  • Page 18: View On Display

    This fault symbol appears when an appliance fault has occurred. ➃ When the text “Filter” appears on the “Brink Air control” display, the filters in the appliance must be cleaned or replaced. ➄ This indicates in what (preprogrammed) time interval the appliance is.
  • Page 19: Main Menu

    Chapter 6 Display Main menu Pressing the right-hand setting knob on the “Brink Air control” takes you to the MAIN MENU 10.54 23/11/15 In this main menu you can use the right-hand setting knob to HRU-Ventilation 0 8 :0 0 17:0 0...
  • Page 20: Device Information Menu

    Chapter 6 Display 6.4.1 Device information menu From the main menu, turn the right-hand setting knob 10.54 23/11/15 10.56 01.03.16 to select the ”Device information” menu and confirm HRU-Ventilation 0 8 :0 0 17:0 0 Main menu the selection by pressing the right-hand setting knob. Device information If several appliances are connected, a selection from Basic settings...
  • Page 21: Basic Settings Menu

    - Clock - Date - Backlight - Key lock Language   In this menu you can choose a language; ex factory the “Brink Air Control” is set for the English language. 10.56 01.03.16 10.58 01.03.16 Basic settings Language Language...
  • Page 22: Installer Menu

    Chapter 6 Display 6.4.3 Installer menu 10.56 10.54 23/11/15 01.03.16 Main menu HRU-Ventilation 0 8 :0 0 17:0 0 From the main menu, turn the right-hand setting knob Device information to select the “Installer” menu and confirm the selection Basic settings ...
  • Page 23: Fault

    Chapter 7 Fault Trouble shooting When the appliance control system detects a fault, it is indi- cated on the display of the “Brink Air control” with a spanner symbol, possibly together with a fault code. Non-locking fault 10.59 01.03.16 Messages...
  • Page 24: Display Codes

    Chapter 7 Fault Display codes Fault Cause Action appliance Action installer code Pressure sensor supply fan • Take the voltage from the appliance. - Switches to constant rpm control. defective. • Check the red pressure hoses (and E100 - The preheater switches on at outdoor Red pressure hoses blocked pressure tubes) for fouling, kinking temperatures below 0°C.
  • Page 25: Maintenance

    Chapter 8 Maintenance User maintenance User maintenance is limited to periodically cleaning or replac- ing the filters. The filter only has to be cleaned when that is 10.54 01.03.16 indicated on the display (it shows the text “FILTER”) or, if a HRU-Ventilation 0 8 :0 0 17:0 0 multiple switch with filter indication is mounted, when the red...
  • Page 26 Chapter 8 Maintenance Click! 10.54 01.03.16 HRU-Ventilation Manual Filter 10.54 01.03.16 HRU-Ventilation Manual 5 sec. Filter reset Filter A filter reset can also be done with the 4-way switch when swit- 10.54 01.03.16 ching 4 times (at normal speed) between position 1 and 0 or 0 HRU-Ventilation 0 8 :0 0 17:0 0 and 1.
  • Page 27: Maintenance Installer

    Chapter 8 Maintenance Maintenance installer Installer maintenance includes cleaning the heat exchanger and fans. Dependent on the conditions, this must done about once every three years. Swing open the front panel (can also be taken from the hinges, if required). Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 28 Chapter 8 Maintenance  max.60 ºC  The heat exchanger should be checked regularly for dirt and be cleaned if necessary. At least once a year the heat exchanger must be cleaned in order to maintain its latent effectiveness. For ceiling mounting, carefully remove the condensate Moderate contamination can be dealt with by bin;...
  • Page 29 Chapter 8 Maintenance   Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 30 Chapter 8 Maintenance S1.01.01 > ± 25 sec 10.54 23/11/15 HRU-Ventilation 0 8 :0 0 17:0 0 Filter reset; see §8.1 point 6 Press the Return key ( ) to leave any selected menu and the appliance will return to operating mode. Click! Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 31: Wiring Diagram

    Motor bypass pre-heater temperature extract fan temperature switch board connector valve sensor sensor “Brink Air external sensor 0-10 V RH-sensor Control” post-heater output 0-10V 24V. switch (optional) applicable post-heater input contact (optional) Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 32: Elektric Connections Accessories

    Chapter 10 Electric connections accessories 10.1 Connections connectors 1 Power plug 230V. 2 EBus connector 3 Modular connector for rpm control 4 Connector for preheater 5 Service connector Nine-pole screw connector (only for Plus version) 7 Additional cable feed option 1 2 3 4 5 6 7 8 9 10.2 Connecting wireless remote control Max 6...
  • Page 33: Connection Rh (Humidity)-Sensor

    Chapter 10 Electric connections accessories 10.3 Connection RH (humidity)-sensor Setting parameter 29 & 30 (§12) Cable sleeve 10.4 Coupling several Renovent Sky 300 (Plus) Enthalpy appliances  Master Slave 1 The slave appliances must be set as slaves before the appli- ance.
  • Page 34: Connection Preheater

    Chapter 10 Electric connections accessories 10.5 Preheater connection 230V 230V 50Hz 50Hz Setting parameter 11 (§12) 10.6 Connection postheater or extra preheater The postheater or extra preheater (only possible for the Plus version) are electrically connected to connector X14; just for a postheater there is also a temperature sensor that must be connected to no.
  • Page 35: Connection Geo Heat Exchanger

    Chapter 10 Electric connections accessories 10.7 Connection geo heat exchanger Ⅰ 30°C Ⅲ Ⅱ Ⅳ Ⅳ Minimum temperature 25°C Ⅰ Maximum temperature Ⅲ Supply air Ⅰ Exhaust air Ⅱ Ⅱ Extract air Ⅲ Outdoor air Ⅳ 15°C Ⅳ Ⅳ Ⅰ Ⅲ...
  • Page 36: Connecting External Switch Contact

    Chapter 10 Electric connections accessories 10.8 Connecting external switch contact An external switch contact (e.g. switch or relay contact) can be If a second input is required as external switch contact, if nec- connected to the appliance. essary connections no. 3 and no. 4 can be reprogrammed. Connections no.
  • Page 37: Service

    Chapter 11 Service 11.1 Exploded view When ordering parts, in addition to the article code number Example (see exploded view), please state the type of the heat recovery Appliance type : Renovent Sky 300 (Plus) Enthalpy appliance, the serial number, the year of production and the Serial number : 4220030249999 (Example) name of the part:...
  • Page 38 To avoid dangerous situations, a damaged mains should only be replaced by a qualified person! Modifications reserved Brink Climate Systems B. V. continuously strives after improvement of products and reserves the right to change the specifications without prior notice. Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 39: Setting Values

    Chapter 12 Setting values FACTORY SETTING STEP NO. DESCRIPTION ADJUSTING RANGE STEP RENOVENT SKY 300 ENTHALPY Air flow rate mode 50 m /h or 50 m Air flow rate mode 1 / 100 m 50 m /h - 300 m Air flow rate mode 2 / 150 m 50 m...
  • Page 40 Chapter 12 Setting values FACTORY SETTING STEP NO. DESCRIPTION RENOVENT SKY PLUS 300 ADJUSTING RANGE STEP ENTHALPY 0 (= Extract fan off) 1 (= Absolute min. flow rate 50 m 2 (= Flow rate mode 1) Extract fan mode 3 (= Flow rate mode 2) switching input 1 4 (= Flow rate mode 3) 5 (= Multiple switch)
  • Page 41 Default position switch 0 - 1 FACTORY SETTING STEP NO. DESCRIPTION RENOVENT SKY 300 ADJUSTING RANGE STEP ENTHALPY Brink Connect function (exter- nal, Brink connect no RH sen- Brink Connect sor) Brink Connect (internal) Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 42: Erp-Values

    Internal 0,9% Leakage*: External 2,0% On the Manual switch / “Brink Air Control” Filterwarning: Attention! For optimal energy efficiency and a proper operation a regular filter inspection, cleaning or replacement is necessary. Internet address for Assembly instructions: http://www.brinkclimatesystems.nl/support/downloads Bypass: Yes;...
  • Page 43: Declaration Of Conformity

    Brink Climate Systems B.V. Address: P.O. Box 11 NL-7950 AA Staphorst, The Netherlands Product: Renovent Sky 300 Enthalpy Renovent Sky 300 Plus Enthalpy The product described above complies with following directives: ● 2014/35/EU (OJEU L 96/357; 29-03-2014) ● 2014/30/EU (OJEU L 96/79; 29-03-2014) ●...
  • Page 44 Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 45: Recycling

    Chapter 13 Recycling Recycling Sustainable materials are used in the manufacture of this appliance. The packaging should be disposed of in a responsible manner and inaccordance with governmental regulations. Renovent Sky 300 (Plus) Enthalpy 617605-A...
  • Page 46 BRINK CLIMATE SYSTEMS B.V. P.O. Box 11 NL-7950 AA Staphorst The Netherlands Wethouder Wassebaliestraat 8 7951SN Staphorst The Netherlands T. +31 (0) 522 46 99 44 F. +31 (0) 522 46 94 00 info@brinkclimatesystems.nl www.brinkclimatesystems.nl...

This manual is also suitable for:

Renovent sky 300 enthalpy