Download Print this page
Growatt SYN-50-XH-10 (MIN XH) Manual
Growatt SYN-50-XH-10 (MIN XH) Manual

Growatt SYN-50-XH-10 (MIN XH) Manual

Advertisement

Quick Links

1
Overview
.
2
3
4
5
1
1: Front panel
2: LED indicator
5: Mounting bracket
6: COM wiring port
9: Inverter wiring port
10: Backup wiring port
2
.
Installation
System overview
The system diagram is as follows:
SYN 50-XH-1
Generator
Non-backup
Backup Load
Load
Non-backup
Backup
Load panel
Load panel
Grid
AC
AC
AC
AC AC
AC
Breaker
Inverter
Battery
PV
DC
DC
2.2
Installation steps
1.Determine SYN 50-XH-1 mounting location, on a wall, stud framing or pole.It is recommended to mount it in a location proected from direct
sunlight.
2.To allow proper heat dissipation, maintain at least a 300mm clearance between the SYN 50-XH-1 and other objects.
3.Position the mounting bracket against the wall/pole and mark the drilling hole locations.
4.Drill the holes and mount the bracket. Verify that the bracket is firmly attached to the mounting surface.
5.Hang SYN 50-XH-1 on the bracket.
Note:
The above dimensions are in "mm".
SYN 50-XH-1 Quick Guide
Backup
Com Generator
Grid
Inverter
Load
12
12
12
6
7
8
9
10
3: Screw for front cover
4: The main frame body
7: Generator wiring port(Reversed)
8: Grid wiring port
11: Non-backup wiring port
12: Waterproof plugs
2.1
Installation requirements
The front, back and side pictures of the SYN 50-XH-1 are as follows:
≤15°
≥300
365
≥300
≥300
≥300
≥500
Note:
The above dimensions are in "mm".
2.3
Required tools
Non-backup
Load
1
2
3
3
.
Wire specification suggestions
11
The cable specifications of this SYN 50-XH-1 are as follows, and the wiring end is stripped 10mm.
project
Wire diameter
Grid input cable
Inverter input cable
Load output cable
Generator input cable
Communication cable
3.1
Wiring instructions
134.7
120.2
3.1.1 Connecting SYN 50-XH-1 to the Grid
1.Take out the two screws on the front cover of the SYN 50-XH-1, open the front cover, and do not
remove the safety plate inside the machine.
2.Loosen the plastic cover printed as " Grid " counterclockwise, remove the three waterproof plugs,
and reserve three holes.
3.Route the three power grid cables (L/N/PE) through the three holes and connect them to the power
grid input terminal and the ground copper bar. The screw torque on the power grid terminal is 26.5
in*lbs / 3.0 N*m to 31 in*lbs / 3.5 N*m, and the screw torque on the ground terminal is 13 in*lbs / 1.5
N*m.
4.Finally, fasten the plastic cover clockwise. Wiring as shown in Figure 3:
Note:
PE cables needs to be pressed into the O-type terminal in the accessory bag, as shown in Figure 2.
2
3.1.2 Connecting SYN 50-XH-1 to the Inverter
When connecting the SYN 50-XH-1 to the XH Inverter, we need to connect AC power cable and communication cable.
1)Connecting the AC cable:
1.Loosen the plastic cover printed as "Inverter" counterclockwise, remove the three waterproof plugs, and reserve three holes.
2.Route the cables of the three inverters (L/N/PE) through the three holes, connect the cables to the inverter circuit breaker terminal and
the ground copper bar. The screw torque of the inverter circuit breaker terminal is 17.5 in*lbs / 2 N*m, and the screw torque on the ground
terminal is 13 in*lbs / 1.5 N*m.
3.Finally, fasten the plastic cover clockwise. Wiring is shown as follows:
No.
Name
straight
1
screwdriver
3
Allen wrench
5
Electric drill
4
5
6
7
Line pressing
7
pliers
Line length
10m
6-8AWG
L
6-8AWG
10m
10mm
10m
8-12AWG
20m
6-8AWG
N
10mm
8-12AWG
20m
10m
6-8AWG
PE
6-8AWG
10m
10mm
Grid and Generator AC cable
22-26AWG
20m
3
Grid
PE N
L
Size
No.
Name
Size
Φ2&5mm
2
hammer
/
Φ5mm
4
Cross rise
Φ5mm
Φ6mm
6
Wire stripper
/
/
20m
8-12AWG
L
10mm
20m
20m
8-12AWG
N
22-26AWG
10mm
10mm
20m
20m
8-12AWG
PE
22-26AWG
10mm
10mm
Load and lnverter AC cable
Communication cable
1
L N
Breaker
PE
Grid
Connection to the Grid

Advertisement

loading
Need help?

Need help?

Do you have a question about the SYN-50-XH-10 (MIN XH) and is the answer not in the manual?

Questions and answers

Summary of Contents for Growatt SYN-50-XH-10 (MIN XH)

  • Page 1 SYN 50-XH-1 Quick Guide Required tools Overview Name Size Name Size straight Φ2&5mm hammer screwdriver Backup Non-backup Com Generator Grid Inverter Load Load Allen wrench Φ5mm Cross rise Φ5mm Electric drill Φ6mm Wire stripper Line pressing pliers Wire specification suggestions The cable specifications of this SYN 50-XH-1 are as follows, and the wiring end is stripped 10mm.
  • Page 2 Please note that the maximum backup load capacity is determined by the When SYN 50-XH-1 fails, it cannot work normally, in order to ensure that the household power supply can be manually switched to the grid Growatt inverter's maximum output power. (For instance, if you have bypass state.
Save PDF