Growatt SPF 6000 ES PLUS User Manual

Growatt SPF 6000 ES PLUS User Manual

Off grid solar inverter

Advertisement

User Manual
Off Grid Solar Inverter
SPF 6000 ES PLUS
Version: 1.0

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SPF 6000 ES PLUS and is the answer not in the manual?

Questions and answers

Zeki
May 3, 2025

I have investor Sp 6000 Es pluse and i need to charge the battery from Ac & Sun not from generator

1 comments:
Mr. Anderson
May 17, 2025

To charge the Growatt SPF 6000 ES PLUS battery using AC and solar power instead of a generator:

1. Connect Solar Panels: Wire the PV panel cables to the PV input terminals on the inverter.

2. Connect AC Input: Use a circuit breaker for AC input overcurrent protection and connect the AC source (like the grid) to the AC input terminals of the inverter.

3. Set Operation Mode: Use the SBU mode. In this mode, the inverter prioritizes Solar (S), then Battery (B), and uses Utility (U) only if needed.

4. Configure Charging Parameters: Program settings 19 and 20 to appropriate voltage levels (e.g., 56.7V) to ensure proper charging behavior.

5. Ensure Correct Communication: Connect the battery BMS communication cable from the BMS Port on the inverter to the PCS Port on the battery.

This setup allows the inverter to charge the battery using solar power and AC input without requiring a generator.

This answer is automatically generated

Win Naing
February 14, 2025

Using SPF 6000 ES, Off grid Battery back up with CATL Lifepo4 300AH. In no load condition, 100% battery fully charged , CB off position in Inverter output, the input current is 3A. Is it more current used in no load condition, because 70 W mentioned in Spec.?

1 comments:
Mr. Anderson
February 14, 2025

The input current is 3A in no-load condition for the Growatt SPF 6000 ES PLUS because the power consumption at no load is 70W. Given that the nominal DC input voltage is 48V, the current can be calculated using the formula:

Power (W) = Voltage (V) × Current (A)

Rearranging for current:

Current (A) = Power (W) / Voltage (V)
= 70W / 48V
1.46A

However, considering possible losses and standby consumption, the actual measured input current may be around 3A at no load.

This answer is automatically generated

Summary of Contents for Growatt SPF 6000 ES PLUS

  • Page 1 User Manual Off Grid Solar Inverter SPF 6000 ES PLUS Version: 1.0...
  • Page 2: Table Of Contents

    Table Of Contents Information on this Manual ..............................1 Validity ..............................1 Scope ................................. 1 Target Group ............................. 1 Safety Instructions ........................... 1 Introduction ................................... 2 Features ..............................2 Product Overview ............................3 Installation ..................................... 4 Unpacking and Inspection ........................4 Preparation ...............................
  • Page 3: Information On This Manual

    Information on this Manual Validity This manual is valid for the following devices: SPF 6000 ES PLUS Scope This manual describes the assembly, installation, operation and troubleshooting of this unit. Please read this manual carefully before installations and operations. Target Group This document is intended for qualified persons and end users.
  • Page 4: Introduction

    Introduction Hybrid Power System This is a multifunctional off grid solar inverter, integrated with a MPPT solar charge controller, a high frequency pure sine wave inverter and a UPS function module in one machine, which is perfect for off grid backup power and self-consumption applications.
  • Page 5: Product Overview

    Product Overview 1. LCD display 2. Status indicator 3. Charging indicator 4. Fault indicator 5. Function buttons 6. PV2 input 7. PV1 input 8. AC input 9. Generator input 10. AC output 11. GND 12. Power on/off switch 13. Battery input 14.
  • Page 6: Installation

    Installation Unpacking and Inspection Before installation, please inspect the unit. Be sure that nothing inside the package is damaged. You should have received the following items in the package: Part List Item Item Name The unit Communication cable Current sharing cable Parallel communication cable MC4 connector User manual...
  • Page 7 SUITABLE FOR MOUNTING ON CONCRETE OR OTHER NON-COMBUSTIBLE SURFACE ONLY. Install the unit by screwing three screws. It’s recommended to use M4 or M5 screws.
  • Page 8: Battery Connection

    Recommended battery cable and terminal size: Torque value Model Wire Size SPF 6000 ES PLUS 1 * 2 AWG 2-3 Nm Note: For lead acid battery, the recommended charge current is 0.2C(Cbattery capacity) Please follow below steps to implement battery connection: 1.
  • Page 9: Lithium Battery Connection

    Lithium Battery Connection If choosing lithium battery for SPF 6000 ES PLUS, you are allowed to use the lithium battery only which we have configured. There're two connectors on the lithium battery, RJ45 port of BMS and power cable. Please follow below steps to implement lithium battery connection: 1.
  • Page 10 LCD setting To connect battery BMS, need to set the battery type as “LI” in Program 05. After set “LI” in Program 05, it will switch to Program 36 to choose communication protocol. You can choose RS485 communication protocol which is from L01 to L50, and you can also choose CAN communication protocol which is from L51 to L99.
  • Page 11 Default 20%, 5%~50% Settable Note: Any questions about communicating with BMS, please consult with Growatt. Communicating with battery BMS in parallel system If need to use communicate with BMS in a parallel system, you should make sure to connect the BMS communication cable between the battery and one inverter of the parallel system.
  • Page 12: Ac Input/Gen/Output Connection

    AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully protected from over current of AC input. The recommended spec of AC breaker is 50A for SPF 6000 ES PLUS . CAUTION!! There are three terminal blocks with “AC INPUT”, “GEN”and “AC OUTPUT” markings. Please do NOT mis-connect input and output connectors.
  • Page 13: Pv Connection

    WARNING! It’ very important for system safety and efficient operation to use appropriate cable for PV module connection. To reduce risk of injury, please use the proper recommended cable size as below. Torque value Model Wire Size SPF 6000 ES PLUS 1 * 12 AWG 1.2-1.6 Nm...
  • Page 14: Communication Connection

    1. Open circuit Voltage (Voc) of PV modules not exceeds max. PV array open circuit voltage of inverter. 2. Open circuit Voltage (Voc) of PV modules should be higher than start-up voltage. INVERTER MODEL SPF 6000 ES PLUS Max. PV Array Open Circuit Voltage 500Vdc...
  • Page 15: Dry Contact Signal

    Dry Contact Signal There is one dry contact(3A/250VAC) available on the rear panel. It could be used to deliver signal to external device when battery voltage reaches warning level. Dry contact port: Unit Status Condition NC & C NO & C Power Off Unit is off and no output is powered Close...
  • Page 16: Operation

    Operation Power ON/OFF Once the unit has been properly installed and the batteries are connected well, simply press On/Off switch (located on the button of the case) to turn on the unit. Operation and Display Panel The operation and display panel, shown in below chart, is on the front panel of the inverter. It includes three indicators, four function keys and a LCD display, indicating the operating status and input/output power information.
  • Page 17: Lcd Display Icons

    LCD Display Icons Icon Description AC Input Information AC input icon Indicate AC input power, AC input voltage, AC input frequency, AC input current Indicate AC power loads in bypass PV Input Information Left:PV1 input icon Right:PV2 input icon Indicate PV power, PV voltage, PV current, etc Output Information Inverter icon Indicate...
  • Page 18 In AC mode, battery icon will present Battery Charging Status Status Battery voltage LCD Display <2V/cell 4 bars will flash in turns. Bottom bar will be on and the other three bars Constant Current 2 ~ 2.083V/cell will flash in turns. mode / Constant Bottom two bars will be on and the other two bars 2.083 ~ 2.167V/cell...
  • Page 19: Lcd Setting

    LCD Setting After pressing and holding ENTER button for 3 seconds, the unit will enter setting mode. Press “UP” or “DOWN” button to select setting programs. Then press “ENTER” button to confirm the selection or ESC button to exit. Program Description Setting Option Solar first...
  • Page 20 Saving mode disable (default) If disabled, no matter connected load is low or high, the on/off status of inverter output will not be effected. Power saving mode enable/disable Saving mode enable If enabled, the output of inverter will be off when connected load is pretty low or not detected.
  • Page 21 Maximum utility charging Default 30A, 0A~80A Settable current Note: If setting value in Program 02 is smaller than that in Program 11, the inverter will apply charging current from Program 02 for utility charger Setting voltage point back to utility source when selecting “SBU priority”...
  • Page 22 Low DC cut-off voltage. Default 42.0V, 40.0V~48.0V Settable If self-defined is selected in program 5, this program can When reach Low DC cut-off voltage: be set up. 1) If battery power is only power source available, inverter will shut down. Low DC cut-off voltage will 2) If PV energy and battery power are available, inverter will charge be fixed to setting value no...
  • Page 23 Battery equalization enable Battery equalization disable(default) Battery equalization If “Flooded” or “User-Defined” is selected in program 05, this program can be set up. Battery equalization voltage Default 58.4V, 48.0V~58.4V Settable Default 60min, 5min~900min Battery equalized time Settable Default 120min, 5min~900min Battery equalized timeout Settable Default 30days, 1 days~90 days...
  • Page 24: Display Information

    Display Information The LCD display information will be switched in turns by pressing “UP” or “DOWN” key. The selectable information is switched as below order: voltage, frequency, current, power, firmware version. Setting Information LCD display ① AC Input voltage (If it flashes, it indicates that the input voltage of the generator is displayed at this time, and the current, power and frequency...
  • Page 25: Operating Mode Description

    ① AC input power in Watts ② Inverter temperature ③ Load power in Watts ④ Left:PV1 input power in Watts Right:PV2 input power in Watts ⑤ Battery percentage ⑥ Warning or Fault code Firmware version (CPU1: 040-00-b21; CPU2:041-00- b21) Time (15:20:10, December 15, 2018) Operating Mode Description Operation mode...
  • Page 26 Charging by PV energy The unit will Charging by utility provide output power from the Line Mode mains. It can also charge the battery at line mode. No battery connected Power from battery and PV energy The unit will provide output Battery Mode power from Power from battery only...
  • Page 27: Parallel Installation Guide

    O-type terminal: Model Wire Size Torque value SPF 6000 ES PLUS 1 * 2 AWG 2-3 Nm WARNING: Be sure the length of all battery cables is the same. Otherwise, there will be voltage difference between inverter and battery to cause parallel inverters not working.
  • Page 28 PLUS Note1: You can use 50A breaker for SPF 6000 ES PLUS for only 1 unit, and each inverter has a breaker at its AC input. Note2: Regarding three phase system, you can use 4 poles breaker, the rating is up to the current of the phase which has the maximum units.
  • Page 29: Parallel Operation In Single Phase

    Parallel Operation in Single Phase WARNING! All inverters must be connected to the same batteries and ensure each group of cables from the inverters to the batteries in the same length. Two inverters in parallel: Power Connection Communication Connection WARNING! Make sure that PAR-OUT of one inverter is connected to the PAR-IN of another inverter. No matter single or three-phase parallel, it is not allowed to connect the PAR-OUT of one inverter with the PAR-OUT of another inverter,or it is not allowed to connect the PAR-IN of one inverter with the PAR-IN of another inverter.
  • Page 30 Four inverters in parallel: Power Connection Communication Connection Five inverters in parallel: Power Connection Communication Connection...
  • Page 31: Parallel Operation In Three Phase

    Six inverters in parallel: Power Connection Communication Connection Parallel Operation in Three Phase WARNING! All inverters must be connected to the same batteries and ensure each group of cables from the inverters to the batteries in the same length. One inverter in each phase: Power Connection Communication Connection...
  • Page 32 Two inverters in one phase and only one inverter for the remaining phases: Power Connection Communication Connection Two inverters in two phases and only one inverter for the remaining phase: Power Connection Communication Connection...
  • Page 33 Three inverters in one phase and only one inverter for the remaining two phases: Power Connection Communication Connection Two inverters in each phase: Power Connection Communication Connection...
  • Page 34 Three inverters in one phase, two inverters in second phase and one inverter for the third phase: Power Connection Communication Connection Four inverters in one phase and one inverter for the other two phases: Power Connection Communication Connection WARNING: Do not connect the current sharing cable between the inverters which are in different phases. Otherwise, it may damage the inverters.
  • Page 35: Pv Connection

    PV Connection Please refer to user manual of single unit for PV Connection on Page 12. CAUTION: Each inverter should connect to PV modules separate. LCD Setting and Display Refer to Program 23 on Page 20 Parallel in Single Phase Step 1: Check the following requirements before commissioning: Correct wire connection ...
  • Page 36 Step 3: Turn on all units sequentially. Please turn on HOST inverter first, then turn on the rest one by one. LCD display in L1-phase unit LCD display in L2-phase unit LCD display in L3-phase unit Step 4: Switch on all AC breakers of Line wires in AC input. If AC connection is detected and three phases are matched with unit setting, they will work normally.
  • Page 37: Fault Reference Code

    Fault Reference Code Fault Code Fault Event Icon on Fan is locked Over temperature Battery voltage is too high Battery voltage is too low Output short circuited Output voltage is too high. Overload time out Bus voltage is too high Bus soft start failed Over current or surge Bus voltage is too low...
  • Page 38: Warning Indicator

    Warning Indicator Warning Warning Event Audible Alarm Icon Code flashing Fan is locked when inverter is on. Beep 3 times every second Beep once every second Over temperature Beep once every second Battery is over-charged Beep once every second Low battery Beep once every 0.5 second Overload Output power derating...
  • Page 39: Battery Equalization

    Battery Equalization Equalization function is added into charge controller. It reverses the buildup of negative chemical effects like stratification, a condition where acid concentration is greater at the bottom of the battery than at the top. Equalizationalso helps to remove sulfate crystals that might have built up on the plates. If left unchecked, this condition, called sulfation, will reduce the overall capacity of the battery.
  • Page 40: Specifications

    Specifications Table 1 Line Mode Specifications INVERTER MODEL SPF 6000 ES PLUS Input Voltage Waveform Sinusoidal (utility or generator) Nominal Input Voltage 230Vac Low Loss Voltage 170Vac±7V (UPS); 90Vac±7V (Appliances) Low Loss Return Voltage 180Vac±7V (UPS); 100Vac±7V (Appliances) High Loss Voltage 280Vac±7V...
  • Page 41 Table 2 Inverter Mode Specifications INVERTER MODEL SPF 6000 ES PLUS Rated Output Power 6KVA/6KW Pure Sine Wave Output Voltage Waveform 230Vac±5% Output Voltage Regulation Output Frequency 50Hz Nominal Output Current Overload Protection 5s@≥150% load; 10s@110%~150% load Surge Capacity 2* rated power for 5 seconds...
  • Page 42 Table 3 Charge Mode Specifications Utility Charging Mode INVERTER MODEL SPF 6000 ES PLUS Charging Algorithm 3-Step 80Amp(@V =230Vac) Max. AC Charging Current Bulk Charging Flooded Battery 58.4Vdc Voltage AGM / Gel Battery 56.4Vdc Floating Charging Voltage 54Vdc Charging Curve MPPT Solar Charging Mode Max.
  • Page 43: Trouble Shooting

    Trouble Shooting Problem LCD/LED/Buzzer Explanation What to do LCD/LEDs and buzzer Unit shuts down The battery voltage is too low . 1. Re-charge battery. will be active for 3 Automatically during seconds and then (<1.91V/Cell) 2. Replace battery. startup process. complete off.
  • Page 44 1. If you connect to a lithum battery without communication, check whether the voltage points of the program 19 and 21 are too high Fault code 08 Bus voltage is too high. for the lithum battery. 2. Restart the unit, if the error happens again, please return to repair center.