Operating Guide | How to update rmware on EKE 1P (080G0325) with counter reset problem
© Danfoss | Climate Solutions | 2024.08
6. The green bar at the bottom of the windows shows the process of the les moving from the PC to
the MYK.
Make sure les were uploaded to MYK
7. You are ready to update the EKE 1P.
Make sure that you connected everything the right way, hold the MYK, log into the CAN SETTINGS.
8. From the CAN SETTINGS choose ACTIVE NODES.
9. Here you will see a map of the connected devices, The L represent the MYK and 1 is the EKE, if you
see only one of them then something is wrong (check cable, CAN addresses and CAN speed on
both).
On two photos below you can see how controller with CAN address 1 and with CAN address 96
can be identify:
10. To start the programming process, go back to the main menu of the MYK (click 2 times on the X
bottom) and choose PROGRAM.
11. Go down to TARGET SEL. And choose PEER2PEER.
12. After choosing the protocol you will be set back to the program menu, from here choose
DOWNLOAD X:/ "folder name of the update" push Enter.
13. And in the next menu choose ALL and push Enter, now the program process will start (the bar in
the middle shows the programming process).
14. When the bar is full, you will get a FINISHED message, now you are done.