Operating Guide | How to update rmware on EKE 1P (080G0325) with counter reset problem
Step 2: Update Firmware of
EKE 1P with new version
© Danfoss | Climate Solutions | 2024.08
Alarm con g.
• Battery alarm
Valve con g.
• Valve con guration
• Valve fallback OD
• Valve OD during stop
• Overdrive
• Overdrive enable OD
• Overdrive block time
• Valve neutral zone
Communication
• Controller adr.
• Can baudrate
(This registration takes about 6 minutes.)
1. Get your MYK programmer ready, if you don't have one please contact your normal sales channel.
Search for a Programming key, MMIMYK, 080G0073. For more information please refer to this site:
Danfoss Global Product
2. Install MYK Manager software.
3. Connect the MYK to your PCs USB-A port with a USB-A MINI USB cable, and use a
telephone cable to connect the MYK to the EKE 1P, you will need a RJ11 RJ11 cable.
If there is CAN connection with AK-PC 572 and another EKE 1P controller, disconnect
controller you are trying to update from that network and make sure it's connected only
to MYK (one to one) with RJ11 cable.
4. Start
the MYK software, press "Connect" and right click on your drive name and
choose "import directory".
5. Choose the folder with the update from your PC (there should be 2 les in that folder app.pk and
mmimyk.cfg).