2 Cautions, Warnings, and Regulatory Information
READ AND SAVE THESE INSTRUCTIONS Follow the instructions in this installation manual. These instructions must be followed to avoid
damage to this product and associated equipment. Product operation and reliability depend upon proper installation.
DO NOT INSTALL ANY SIMPLEX™ PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product, inspect
the contents of the carton for shipping damage. If damage is apparent, immediately file a claim with the carrier and notify an
authorized Simplex product supplier.
ELECTRICAL HAZARD Disconnect electrical field power when making any internal adjustments or repairs. All repairs should
be performed by a representative or an authorized agent of your local Simplex product supplier.
STATIC HAZARD Static electricity can damage components. Handle as follows:
• Ground yourself before opening or installing components.
• Prior to installation, keep components wrapped in anti-static material at all times.
EYE SAFETY HAZARD Under certain fiber optic application conditions, the optical output of this device may exceed eye safety
limits. Do not use magnification (such as a microscope or other focusing equipment) when viewing the output of this device.
SULFURIC ACID WARNING Battery contains sulfuric acid, which can cause severe burns to the skin and eyes and can
destroy fabric. Replace any leaking or damaged battery while wearing appropriate protective gear. If you come in contact with
sulfuric acid, immediately flush skin or eyes with water for 15 minutes and seek immediate medical attention.
FCC RULES AND REGULATIONS – PART 15 This equipment has been tested and found to comply with the limits for a Class A digital
device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy
and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct
the interference at his own expense.
SYSTEM REACCPTANCE TEST AFTER SOFTWARE CHANGES To ensure proper system operation, this product must be tested in
accordance with NFPA-72, after any programming operation or change in site-specific software. Reacceptance testing is required after
any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All
components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition, to
ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper system operation verified.
Important: Verify FACU System Programmer, Executive, and Card Software compatibility when installing, or replacing system components.
Refer to the Technical Support Information and Downloads website for compatibility information.
2.1
Emissions Compliance, Radio Frequency Immunity Safety, and Agency Approvals
This product has been tested and found to comply with the following standards for RF Emissions and Immunity:
• FCC Part 15A
• EN55022: 1998, Class A, Emissions (CISPR 22: 1993)
• EN50130-4: 1995 EMC
This product has also been tested and found to meet the requirements of EN60950 (1992) "Safety of Information Technology
Equipment Including Electrical Business Equipment": +A1:93 + A2:93 + A3:95 + A4:97 + A11:97
This product is listed to the following standards:
• UL 864 9th Edition
• S527-11 - ULC
• FM
• CSFM
• MEA
page 4
4004R Fire Alarm installation, programming, and operating instructions
579-354
Rev. X