Programming Manual Release Time Delay - Simplex 4004R Installation, Programming And Operating Instructions

Table of Contents

Advertisement

Six selections are available in the second menu --- 3.5 minutes, 21 minutes, 25 minutes, 34 minutes, 44 minutes
and 64 minutes. Use the RESET key to scroll through the selections. When the desired choice is illuminated, press
the ACK key to save the selection in memory and move to the next programming step.
Front panel
programming
6.8

Programming Manual Release Time Delay

The Manual Release Time Delay is a programmable timer that specifies the delay between the activation of a manual release switch and
the activation of releasing appliances. The default setting for this timer is 10 seconds. A setting of 0 causes the releasing appliances to
immediately activate after a manual release switch activates.
As the timer counts down, the notification appliances sound a temporal or 20 beat per minute signal, the actual signal that plays depends
on the setting of the NAC Coding option, as described in Programming NAC Coding, later in this chapter.
page 45
4004R Fire Alarm installation, programming, and operating instructions
579-354
Rev. X