Circutor computer max 12 Manual page 2

Power factor regulator
Hide thumbs Also See for computer max 12:

Advertisement

4.- SETUP AND MEASUREMENTS
To enter the SETUP mode, press the setup key (9), for more than 1s. If all the capacitors are disconnected, the access in immediate, otherwise a disconnection sequence
starts and then accesses to setup menu. In the SETUP mode, if no key is pressed for 3 minutes, the equipment exits such mode and returns to normal operation mode.
Key to access the SETUP mode:
- Long push to enter and exit SETUP mode. Also DELETE max values when
in the measuring mode
- Short push: to change from display mode to edit mode and vice versa.
If no key is pushed during more than 3 minutes, the regulator exits the SETUP
mode without changing the setup.
:
Symbol showing which parameter is being displayed or edited.
- In the display mode: Cursors to select an option.
- In edit mode: Change a parameter value
Display SETUP Parameters
Long
Short
Push
Push
RUN
Measurement
Long
Short
Push
Push
RUN
Measurement
Long
Short
Push
Push
RUN
Measurement
Long
Short
Push
Push
RUN
Measurement
Long
Short
Push
Push
RUN
Measurement
Long
Short
Push
Push
RUN
Measurement
Long
Short
Push
Push
RUN
Measurement
Initial screen
C/K table depending on initial cosϕ ϕ ϕ ϕ , desired cosϕ ϕ ϕ ϕ and CT ratio
6.-
CT Ratio
CT
2.5
5,00
7.5
10,0
150/5
0,12
0,24
0,36
0,48
200/5
0,09
0,18
0,27
0,36
250/5
0,07
0,14
0,22
0,29
300/5
0,06
0,12
0,18
0,24
400/5
0,05
0,09
0,14
0,18
500/5
0,07
0,11
0,14
600/5
0,06
0,09
0,12
800/5
0,07
0,09
1000/5
0,05
0,07
1500/5
0,05
2000/5
2500/5
3000/5
4000/5
For different voltages (V) of 400V, table result must be multiply for 400/V, or calculate C/K parameter using the expressions.
7.- Technical Service
For any inquiry about the regulator operation or in case of malfunction, see
detailed manual at www.circutor.es or contact with technical service.
points to the option
Edit SETUP parameters
Description
MENU OPTIONS
Increase
Next
dígit
Target cos
Target cos ϕ (def=1)
Increase
Reactive I of 1
C/K adjustment
Next
Range: 0.02 – 1.00
dígit
C/K setting
See paragraph 6
Program setting
Prog
Depends on the kvar
change
relationship between
successive steps.
Program setting
See paragraph 4.2
Increase
Delay for successive
steps (4 -999 s) .
Next
Re-connection delay
dígit
is = 5 times T ON
Delay setting
Increase
Selection of Nr of
relays , max 6 or 12
depending on type
Decrease
Nr steps setting
CT connection . See
paragraph 4.3. The
Phase
display shows T1, T2,
change
T3, T4, T5 or T6.
Accept the option
CT phase setting
giving cosϕ between
0.7 Ind and 0.98 Cap
Increase
CT primary current
Next
dígit
setting. See
CT primary
paragraph 4.4
current setting
Lower step reactive power (kvar) at 400V
12,5
15,0
20,0
25,0
30,0
37,5
0,60
0,72
0,96
0,45
0,54
0,72
0,90
0,36
0,43
0,58
0,72
0,87
0,30
0,36
0,48
0,60
0,72
0,90
0,23
0,24
0,36
0,48
0,58
0,67
0,18
0,22
0,29
0,36
0,45
0,54
0,15
0,18
0,24
0,30
0,36
0,45
0,11
0,14
0,18
0,23
0,27
0,33
0,09
0,11
0,14
0,18
0,22
0,27
0,06
0,07
0,10
0,12
0,14
0,18
0,05
0,07
0,09
0,11
0,13
0,06
0,07
0,09
0,10
0,05
0,06
0,07
0,09
0,05
0,06
4.1.- RUN & Measuring mode
In normal operation mode (RUN mode) the regulator display may show different
parameters (V, I, cos ϕ , etc.) The displayed parameter is pointed by the sign
By default the regulator displays the cos ϕ , but pushing the keys
following parameters can be explored: Current (I), Current harmonics (THD), Mains
Voltage (V), Maximum current (I MAX) y Maximum voltage (V MAX). If both keys
are pushed simultaneously the regulator displays the Nr of connected steps.
A long push of
key when maximum values are displayed causes de deletion of
recorded max values.
4.2.- Program selection
This setting depends on the kvar ratio between the different capacitor steps. For
instance if the bank is 10+20+20+20 kvar the program is 1:2:2:2, so the option 122
must be selected.
Display
111
122
124
4.3.- Selecting the CT connection phase
st
step,
Choose among the options in the table depending on CT connection and the
phases where V is measured. In normal installations (no exported energy) choose
the option for which the displayed cos ϕ is between 0.7 Ind and 0.98 Cap.
V-I phase shift at
Display
cosϕ ϕ ϕ ϕ =1
T1
T2
T3
T4
T5
T6
4.4.- Selecting the rated primary current of CT
If the LED is blinking indicates that we are in SETUP mode and
adjusting primary CT current. When in RUN mode or when Iprimary is displayed,
the LED indicates whether the displayed current has a scale factor x1 (LED OFF)
or x10 (LED ON)
5.- Error Codes
ERR CODE
DISPLAY
E.01
Alll zeros
cos ϕ and E.02
E.02
alternate blinking
cos ϕ and E.03
E.03
alternate blinking
cos ϕ and E.04
E.04
alternate blinking
cos ϕ and E.05
E.05
alternate blinking
C/K calculation:
40,0
50,0
60,0
75,0
80,0
If It is the primary rated current of the CT and
Ic the rated current of the lower capacitor step,
the C/K must be set according to the
calculations shown below:
0,96
0,72
0,87
Example : CT current ratio = 500/5
0,54
0,72
0,87
Lower step power: 60 kvar at 400V
0,48
0,60
0,72
0,90
0,96
0,36
0,45
0,54
0,68
0,72
K
0,29
0,36
0,43
0,54
0,57
0,19
0,24
0,29
0,36
0,38
C
0,14
0,18
0,22
0,27
0,28
0,12
0,14
0,17
0,22
0,23
0,10
0,12
0,14
0,18
0,19
0,07
0,09
0,11
0,14
0,14
Circutor SÁ.
Vial Sant Jordi, s/n
08232 - Viladecavalls
TEL - 93 745 29 00 & fax - 93 745 29 14
E-mail : central @ circutor.es
computer max
Program
Display
1:1:1:1
248
1:2:2:2
112
1:2:4:4
Measuring phases
for V
30º
L3-L2
270º
L3-L2
150º
L3-L2
210º
L3-L2
90º
L3-L2
330º
L3-L2
DESCRIPCIÓN
Load current below measuring threshold or
CT not connected
Overcompensation. The regulador is asking to
disconnect Cs and they are all disconnected
Sub-compensation. The regulator is asking for more
Cs and they are all connected
Over current. The current is + 20%. Above primary
rated current
Overvoltage. Voltage is +15%. Above rated voltage
500
60
.
000
=
=
=
=
100
;
I
×
C
5
, 1
73
400
Ic
86
7 ,
=
=
=
/
K
, 0
867
K
100
max 6 / max
max 12
max
max
max
max
.
the
Program
1:2:4:8
1:1:2:2
Phase where TC is
connected
L3
L1
L2
L3 (CT reversed)
L1 (CT reversed)
L2 (CT reversed)
ACTUACIÓN
Forces all the
relays OFF
NO ACTION
NO ACTION
NO ACTION
NO ACTION
It
=
K
5
Q
=
I
C
3
V .
86
7 ,
A
Ic
=
C K
/
K
__M98227601-03-09E__