Power Source Installation; Refrigerant Charge Label - Haier 3HUM18HB03/R2 - annexe 1 Installation Manual

Room air conditioner
Hide thumbs Also See for 3HUM18HB03/R2 - annexe 1:
Table of Contents

Advertisement

Available languages

Available languages

5.
No gas leakage?
In case of gas leakage, tighten parts of pipe connection. If
leakage stops, then proceed 6. steps
If it does not stop gas leakage, discharge whole refrigerants from the service
port. After flaring work again and vacuumize, fill up prescribed
refrigerant from the gas cylinder.
6.
from the service port, open 3-way(L) valve and 3-way(G).
Detach the charge hose
Turn the valve rod anticlockwise until hitting lightly.
7.
To prevent the gas leakage, turn the service port's cap, the valve rod's cap for 3-way
(L)valve and 3-way's(G) a little more than the point where the torque increases suddenly.
8.
After attaching the each caps, check the gas leakage around the caps.
Step 1.
3-way valve(G)
3-way valve(L)
Gaugemanifold(for R410A)
Tube(for R410A)
Step 4.
3-way valve(G)
3-way valve(L)
Open
90
o
3-way valve(L)
Service port cap
CAUTION
If the refrigerant of the air conditioner leaks, it is necessary to discharge all the
refrigerant. Vacuumize first, then charge the liquid refrigerant into air conditio-
ner according to the amount marked on the name plate.
Please do not let other cooling medium, except specified one (R410A), or air
enter into the cooling circulation system. Otherwise, there will be abnormal
high pressure in the system to make it crack and lead to personal injuries.
1

Power Source Installation

The power source must be exclusively used for air
In the case of installing an air conditioner in a moist place,
rth leakage breaker.
For installation in other places, use a circuit breaker as far
2
Cutting and Flaring Work of Piping
Pipe cutting is carried out with a pipe cutter and burs must
After inserting the flare nut, flaring work is carried out.
Flare tool for R410A
Clutch-type
clutch-type(Rigid-type) Wing-nut type (Imperial-type)
A
0~0.5mm
1.0~1.5mm
1.Cut pipe
Flare tooling die
3.Insert the flare nut
Correct
Lean
Damage of flare
4
Step 2.
Open
Anti countercurrent joint
Step 3.
Close
Vacuum pump(for R410A)
Step 6.
3-way valve(L)
Step 7.
3-way valve(G)
Valve rod cap
conditioner. (Over I0A)
please install an ea-
as possible.
be removed.
Conventional flare tool
1.5~2.0mm
2.Remove burs
4.Flare pipe
Incorrect
Crack
Partial
Too outside
On Drainage
3
Please install the drain hose so as to be downward slope without fail.
Please don't do the drainage as shown below.
It becomes
high midway.
Please pour water in the drain pan of the indoor unit, and
drainage is carried out surely to outdoor.
In case that the attached drain hose is in a room, please
insulation to it without fail.

Refrigerant charge label

3-way valve(G)
This product contains fluorinated greenhouse gases covered by
the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type:R410A
GWP* value:1975
GWP=global warming potential
Please fill in with indelible ink,
• 1
the factory refrigerant charge of the product
• 2
the additional refrigerant amount charged in the field and
• 1+2 the total refrigerant charge
on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product
charging port (e.g. onto the inside of the stop value cover).
A contains fluorinated greenhouse gases covered by the Kyoto
Protocol
B factory refrigerant charge of the product: see unit name plate
C additional refrigerant amount charged in the field
D total refrigerant charge
E outdoor unit
F refrigerant cylinder and manifold for charging
Check for Installation and Test Run
Please kindly explain to our customers how to operate
through the instruction manual.
Gas leak from pipe connecting?
Heat insulation of pipe connecting?
Are the connecting wirings of indoor and outdoor firmly
inserted to the terminal block?
Is the connecting wiring of indoor and outdoor firmly fixed?
Is drainage securely carried out?
Is the earth line securely connected?
Is the indoor unit securely fixed?
Is power source voltage abided by the code?
Is there any noise?
Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performed normally?
Is the operation of room temperature regulator normal?
Less than
The end is imm-
It waves.
The gap with the
ersed in water.
ground is too small.
Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
R410A
1=
2
2=
1
1+2=
F
E
Check Items for Test Run
Put check mark
in boxes
5cm
There is the bad
smell from a ditch
confirm that
apply heat
A
kg
B
kg
C
kg
D