Item
Rated supply voltage
Allowable supply voltage range
Power consumption
Ambient operating temperature
Ambient storage temperature
Ambient operating humidity
Ambient storage humidity
Operating atmosphere
Noise resistance
Vibration resistance (in
operation)
Shock resistance (in operation)
Dimensions (excluding
protrusions)
Weight
Degree of protection
Note 1: The maximum surrounding air temperature rating is 50°C. The ambient operating
Note 1-1: No PCI Board or One of Following Expansion Boards Installed
• 3G8F7-CLK21-V1 Controller Link Board (hereafter CLK Board)
• CS1PC-PCI01-DRM SYSMAC CS1 Board (hereafter CS1 Board)
(1) The ambient operating temperature is 0 to 25°C when the installation angle is greater than
0° and less than 15° off horizontal (excluding the memory card).
(2) The ambient operating temperature is 0 to 30°C when the installation angle is greater than
15° and less than 45° off horizontal (excluding the memory card).
(3) The ambient operating temperature is 0 to 40°C when the installation angle is greater than
45° and less than 75° off horizontal (excluding the memory card).
(4) The ambient operating temperature is 0 to 50°C when the installation angle is greater than
75° and less than 90° off horizontal (excluding the memory card).
The service life is a guideline that is provided strictly for reference. It varies with factors
such as the installation location and operating conditions.
The file system is formatted in advance with NTFS. Both C and D drives have been
created as partitions. The D drive is used by the OS and RAS Utility to store the event
logs.
NSA15-TX01B/S-01E only: 4 GB
NSA15-TX01B/S-01E only: 1 GB
24 V DC
20.0 V DC to 27.6 V DC (24 V DC±15%)
NSA12: 80 W max., NSA15: 100 W max.
0 to 50°C (See notes 1 and 2.)
−10 to 60°C (See note 2.)
10% to 80% with no condensation (See note 2.)
10% to 85% with no condensation (See note 2.)
Must be free of corrosive gases.
Must be fairly dust free.
Conforms to IEC6100-4-4, power supply line: 2 kV
Conforms to JIS C0041, 0.05-mm amplitude at 10 to 55 Hz for 50 min each
in the X, Y, and Z directions
Conforms to JIS C0041, 196 m/s
directions
NSA12: 322 mm x 264 mm x 100 mm (W x H x D)
NSA15: 384 mm x 312 mm x 108 mm (W x H x D)
NSA12: 5 kg max., NSA15: 7 kg max.
Front panel: IP65 or the equivalent (display side only) (See note 3.)
temperature may be restricted as described below depending on whether a PCI Board
is installed, the type of Board installed, and the mounting angle of the Unit.
1-2
Specifications
1-2-2 General Specifications
Specifications
2
three times each in the X, Y, and Z
1
1-5