Initial Setting Procedure
1. Check the wiring and turn ON the power.
2. Set pulse input as the input type.
If a measurement value is displayed (operation level), move to the
initial setting level by holding down the Level Key for 3 s min.
Set parameter in-t to pulse.
3. Set the pulse frequency to 30 Hz.
The input pulse frequency for the application is approximately
2 Hz and so can be assumed not to exceed 30 Hz. Set parameter
p-fre to 30.
4. Set the scaling values.
Set parameter inp to 10.
Set parameter dsp to 56549.
5. Set the decimal point.
Set parameter dp to %%.%%%.
6. Operating action for OUT1 and OUT2 set values.
Set parameter out1.t to hi.
Set parameter out2.t to lo.
7. Set OUT1 set value to 10.500 and OUT2 set value to 9.500.
If an initial setting level parameter is displayed, press the Level
Key for 1 s min. to return to the operation level.
Set parameter out1 to 10.500.
Set parameter out2 to 9.500.
8. Start actual operation.