Omron H3DE Manual page 20

Solid-state timer h3de series
Table of Contents

Advertisement

Specifications
■ General
Item
Operating mode
Operating/Reset method
Terminal block
Terminal screw tightening torque 0.98 N·m max. {approx. 10 kgf·cm max.}
Output type
Mounting method
Attachment
Approved standards
Note: Can be mounted to 35-mm DIN track with a plate thickness of 1 to 2.5 mm.
■ Time Ranges
Time scale display
x 1
1 to 12 s
x 10
10 to 120 s
Star-delta transfer time
■ Ratings
Rated supply voltage (see note)
Operating voltage range
Power reset
Reset voltage
Power consumption
Control output
Ambient temperature
Ambient humidity
Note: DC ripple rate: 20% max.
B-70
Solid-state Star-delta Timer
Star-delta operation
Time-limit operation/Self-reset
2
Clamps two 2.5 mm
max. bar terminals without sleeves
(Star operation circuit) Relay: SPDT
(Delta operation circuit) Relay: SPDT
DIN track mounting (see note)
Nameplate
UL508, CSA 22.2 No.14
Conforms to EN61812-1, IEC60664-1 4 kV/2, VDE0106/P100
Output category according to IEC60947-5-1 (AC-13; 250 V 5A/AC-15; 250 V 3 A/DC-13; 30 V 0.1 A)
Star operation time ranges
Programmable at 0.05 s, 0.1 s, 0.25 s or 0.5 s
24 to 230 VAC/VDC (50/60 Hz)
85% to 110% of rated supply voltage
Minimum power-off time: 0.5 s
24 VAC/DC max.
AC: Approx. 3 VA (1.8 W) at 230 VAC
DC: Approx. 0.8 W at 24 VDC
Contact output: 5 A at 250 VAC with resistive load (cos = 1)
Operating:
Storage:
Operating: 35% to 85%
H3DE-G
H3DE-G
5 A at 30 VDC with resistive load (cos = 1)
10 C to 55 C (with no icing)
25 C to 65 C (with no icing)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

H3de-mH3de-sH3de-fH3de-gH3de-h

Table of Contents