Contact Ratings - Omron G2RS Manual

Slim and space-saving power plug-in relay
Hide thumbs Also See for G2RS:

Advertisement

Contact Ratings

Number of poles
Load
Rated load
Rated carry current
Max. switching voltage
Max. switching current
Max. switching power
Failure rate (reference value)
-6
Note: P level:
= 0.1 x 10
/operation
60
Characteristics
Item
Contact resistance
100 m max.
Operate (set) time
15 ms max.
Release (reset) time
AC: 10 ms max.; DC: 5 ms max.
(w/built-in diode: 20 ms max.)
Max. operating
Mechanical:
frequency
Electrical:
Insulation resistance
1,000 M min. (at 500 VDC)
Dielectric strength
5,000 VAC, 50/60 Hz for 1 min between coil and
contacts*;
1,000 VAC, 50/60 Hz for 1 min between contacts of
same polarity
Vibration resistance
Destruction:
Malfunction:
Shock resistance
Destruction:
Malfunction:
Endurance
Mechanical:
Electrical:
Ambient temperature
Operating:
Ambient humidity
Operating:
Weight
Approx. 21 g
Note: Values in the above table are the initial values.
*4,000 VAC, 50/60 Hz for 1 minute when the P2R-05A or P2R-08A Socket is mounted.
Approved Standards
UL 508 (File No. E41643)
Model
Contact
Coil ratings
form
G2R-1-S SPDT
5 to 110 VDC
5 to 240 VAC
G2R-2-S DPDT
CSA 22.2 No.0, No.14
(File No. LR31928)
Model
Contact
Coil ratings
form
G2R-1-S SPDT
5 to 110 VDC
5 to 240 VAC
G2R-2-S DPDT
1 pole
Resistive load
Inductive load
(cos = 1)
(cos = 0.4; L/R = 7 ms)
10 A at 250 VAC;
7.5 A at 250 VAC;
10 A at 30 VDC
5 A at 30 VDC
10 A
440 VAC, 125 VDC
10 A
2,500 VA,
1,875 VA,
300 W
150 W
100 mA at 5 VDC
1 pole
18,000 operations/hr
1,800 operations/hr (under rated load)
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
10 to 55 to 10 Hz, 0.75 mm single amplitude (1.5 mm double amplitude)
2
1,000 m/s
2
200 m/s
when energized; 100 m/s
AC coil: 10,000,000 operations min.;
DC coil: 20,000,000 operations min. (at 18,000 operations/hr)
100,000 operations min. (at 1,800 operations/hr under rated load) (DC coil type)
–40°C to 70°C (with no icing or condensation)
5% to 85%
Contact ratings
Opera-
tions
10 A, 30 VDC (resistive)
6 x 10
10 A, 250 VAC (general use)
TV-3 (NO contact only)
5 A, 30 VDC (resistive)
6 x 10
5 A, 250 VAC (general use)
TV-3 (NO contact only)
Contact ratings
Opera-
tions
10 A, 30 VDC (resistive)
6 x 10
10 A, 250 VAC (general use)
TV-3 (NO contact only)
5 A, 30 VDC (resistive)
6 x 10
5 A, 250 VAC (general use)
TV-3 (NO contact only)
2 poles
Resistive load
(cos = 1)
5 A at 250 VAC;
5 A at 30 VDC
5 A
380 VAC, 125 VDC
5 A
1,250 VA,
150 W
10 mA at 5 VDC
AC: 15 ms max.; DC: 10 ms max.
(w/built-in diode: 20 ms max.)
5,000 VAC, 50/60 Hz for 1 min between coil and contacts*;
3,000 VAC, 50/60 Hz for 1 min between contacts of different polarity
1,000 VAC, 50/60 Hz for 1 min between contacts of same polarity
2
when not energized
IEC/VDE (EN61810)
Contact
Coil ratings
form
3
1 pole
6, 12, 24, 48 VDC
24, 110, 120, 230,
240 VAC
2 poles
6, 12, 24, 48 VDC
3
24, 110, 120, 230,
240 VAC
LR
Number of
Coil ratings
poles
1 pole
5 to 110 VDC
5 to 240 VDC
3
2 poles
5 to 110 VDC
5 to 240 VDC
3
General-purpose Relay
Inductive load
(cos = 0.4; L/R = 7 ms)
2 A at 250 VAC; 3 A at
30 VDC
500 VA,
90 W
2 poles
Contact ratings
Operations
5 A, 440 VAC (cos = 1.0)
100 x 10
10 A, 250 VAC (cos = 1.0)
10 A, 30 VDC (0 ms)
5 A, 250 VAC (cos =1.0)
100 x 10
5 A, 30 VDC (0 ms)
Contact ratings
Operations
10 A, 250 VAC (general use)
100 x 10
7.5 A, 250 VAC (PF0.4)
10 A, 30 VDC (resistive)
5A, 30VDC (L/R=7ms)
5 A, 250 VAC (general use)
100 x 10
2 A, 250 VAC (PF0.4)
5 A, 30 VDC (resistive)
3A, 30VDC (L/R=7ms)
G2RS
3
3
3
3
G-7