Analog I/O Slave Unit (output) Functions
Adjusting the High
Limit
536
6. Output the value from the Master Unit that is equivalent to the Output Unit's
maximum (100%) value. Adjustment using the 100% value is highly recom-
mended, but adjustment can be performed using a lower value.
7. Adjust the analog value that is output from the terminal using the High Ad-
justment slide bar, as shown in the following window. Repeat adjustments
until the correct 100% value is output from the output device. After com-
pensation is completed, click the Fix Upper Adjusting Value Button.
To return to the default settings, click the Default Setting Button.
8. Click the Close Button to close the Adjustment Window.
9. Return to the General Tab Page, click the Transfer [PC to Unit] Button to
download the data, and then click the Reset Button to reset the Unit.
10. Click the OK Button and exit the window.
Note In Analog Output Slave Units, always adjust the Low Limit first. If the Low Limit
is adjusted without adjusting the High Limit 100%, dislocation may occur.