Omron CRT1 - 10-2009 Operation Manual page 382

Componet slave units and repeater unit
Table of Contents

Advertisement

Units with Connectors
Note
Note
Terminal Arrangements
Communications
Connector
358
Pin No.
Setting
4
Range settings for output
CH1
5
6
7
Always OFF.
8
Range setting method
(1) Always use the default setting (OFF) for pin 7.
(2) Always set pin 8 to ON if the DIP switch is used to set the ranges. If this
pin is OFF, the DIP switch settings will not be enabled.
(3) The DIP switch settings are read when power is turned ON.
■ Range for output CH0
Output range
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
■ Range for output CH1
Output range
0 to 5 V
1 to 5 V
0 to 10 V
–10 to 10 V
4 to 20 mA
0 to 20 mA
Do not set the DIP switches or pins other than as specified in the table above.
BS+
Communications power supply +
BDH
Communications data high
BDL
Communications data low
Communications power supply −
BS−
See the next table
Default setting: All pins OFF
Always set this pin to OFF. Malfunctions may
occur if it is set to ON.
OFF: Use CX-Integrator.
ON: Use DIP switch.
Pin 1
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Pin 4
OFF
OFF
ON
OFF
OFF
ON
ON
ON
OFF
OFF
ON
OFF
Section 6-7
Specification
Pin 2
Pin 3
OFF
OFF
OFF
OFF
ON
ON
Pin 5
Pin 6
OFF
OFF
OFF
OFF
ON
ON