CP1W-CIF11 Setup
Set the DIP switches as follows.
(Rear panel)
No.
1
Presence of terminating resistance
2
2/4-wire selection
3
2/4-wire selection
4
-
5
RS control for RD
6
SD control for RD
CIMR-V7 Setup
Set the DIP switches as follows.
• SW2-1: ON (terminating resistance present) Terminating resistance for RS422/
485 communication
Next, set the parameters as follows:
No.
n003
Operation command
n004
Frequency command
n019
Acceleration time 1
n020
Deceleration time 1
n151
RS-422/485 communication
Timeout detection
n152
RS-422/485 communication
Frequency commands and
monitoring
n153
RS-422/485 communication
Slave address
n154
RS-422/485 communication
Baud rate
n155
RS-422/485 communication
Parity
n156
RS-422/485 communication
Transmission wait time
n157
RS-422/485 communication
RTS control
CPU unit connector
Operation setup
DIP switches
Setting
Name
Value
2
6
5.0
5.0
1
1
1
2
0
10
0
A-4 CP1L Programming Examples
ON/OFF
Content
ON
Terminating
resistance
present
ON
2-wire type
ON
2-wire type
OFF
Always OFF
ON
Enabled
ON
Enabled
Comments
RS-422/485 communication enabled
Frequency commands from RS-422/485
communication enabled
Acceleration time (sec)
Deceleration time (sec)
Detection enabled, detect errors, stop
deceleration after deceleration time 1 (Default)
Select unit for communication of frequency
commands data and frequency monitoring data.
Unit: 0.01Hz (Default).
Slave address (slave node number), unit 1
Communication baud rate (communication
speed): 9600bps (Default)
Even parity
Sets the response wait time for request messages
received from the master. 10ms (Default).
RTS control enabled (Default)
SYSMAC CP1L Getting Started Guide