Kampmann Resistent Assembly, Installation And Operating Instructions

Advertisement

Quick Links

Issue03/24EN
SAP No.1396469
Resistent
► Assembly, installation and operating instructions
Keep these instructions in a safe place for future use!

Advertisement

Table of Contents
loading

Summary of Contents for Kampmann Resistent

  • Page 1 Resistent ► Assembly, installation and operating instructions Keep these instructions in a safe place for future use! Issue03/24EN SAP No.1396469...
  • Page 3: Table Of Contents

    Table of contents 1 General ..........................5 1.1 About these instructions ........................1.2 Explanation of Symbols.......................... 2 Safety............................ 6 2.1 Correct use............................. 2.2 Limits of operation and use........................2.3 Risk from electrocution!......................... 2.4 Personnel requirements - Qualifications ....................2.5 Personal Protective Equipment ......................3 Transport, storage and packaging..................
  • Page 4 9 Operation..........................32 9.1 Operation of electromechanical control ....................32 10 Maintenance ......................... 33 10.1 Securing against reconnection ....................... 33 10.2 Maintenance Schedule:.......................... 33 10.3 Clean the inside of the unit........................33 11 Faults ............................ 35 11.1 Fault table.............................. 36 11.2 Fault table, electromechanical control type ..58 ..................
  • Page 5: General

    Resistent Assembly, installation and operating instructions General About these instructions These instructions ensure the safe and efficient handling of this equipment. These instructions form an integral part of the equipment and have to be kept in the direct vicinity of the equipment and available to personnel at all times.
  • Page 6: Safety

    Resistent Assembly, installation and operating instructions Safety This section provides an overview of all important safety aspects to ensure optimum protection of personnel as well as safe and trouble-free operation. In addition to the safety instructions in these operating instructions, the valid safety, accident pre- vention and environmental protection regulations must be observed for the area of use of the unit.
  • Page 7 Resistent Assembly, installation and operating instructions Limits of operation and use Limits of operation Min./max. water temperature °C 5 - see type plate Min./max. air intake temperature °C -20 - (+40) Min./max. air humidity 15-75 Min. operating pressure bar/kPa Max. operating pressure...
  • Page 8: Risk From Electrocution

    Resistent Assembly, installation and operating instructions WARNING! Note the maximum flow temperatures to protect the EC fan! Long periods of idleness with high water temperatures can lead to the impermissible heating up of the EC fan motor. The flow temperatures should therefore be limited depending on the application and the motor model.
  • Page 9: Personnel Requirements - Qualifications

    Resistent Assembly, installation and operating instructions Personnel requirements - Qualifications Expertise The installation of this product requires specialist expertise in heating, cooling, ventilation, installation and electrical engin- eering. As this knowledge is normally acquired through professional training in one of the above fields, it is not dealt with further here.
  • Page 10: Transport, Storage And Packaging

    IMPORTANT NOTE! Warranty claims can only be made within the applicable period for complaints. (More information is avail- able in the T&Cs on the Kampmann website) IMPORTANT NOTE! 2 people are needed to transport the unit. Wear personal protective clothing when transporting the unit.
  • Page 11: Storage

    Resistent Assembly, installation and operating instructions Storage Store packaging under the following conditions: Do not store outdoors. Store in a dry and dust-free place. Store in a frost-free place. Do not expose to aggressive media. Protect from direct sunlight. Avoid mechanical vibrations and shocks.
  • Page 12: Technical Data

    20 - 62 [dB(A)] Tab. 5: Technical data for Resistent The sound pressure level was calculated with an assumed room insulation of 16 dB(A). This corresponds to a dis- tance of 5 m, a room volume of 3000 m³ and a reverberation time of 2.0 s (in accordance with VDI 2081).
  • Page 13: Construction And Function

    Whisper-quiet sickle-blade fan Brief description Resistent are used for the decentralised heating and ventilation of high-ceilinged buildings, either wall or ceiling-mounted. Air is drawn in through the EC fan and blown through the heat exchanger into the room through the standard one-row...
  • Page 14: Installation And Wiring

    Be sure to observe the minimum distances when using accessories and for maintenance purposes! L min Fig. 2: Resistent minimum distances (wall and ceiling installation) Unit size Type...
  • Page 15: Installation Of Accessories

    Resistent Assembly, installation and operating instructions Installation 2 people are needed to install the unit. CAUTION! Risk of injury from sharp metal housing! The inner metal of the casing can have sharp edges. Wear suitable protective gloves. IMPORTANT NOTE! Horizontal installation of units! When installing the units, ensure that they are completely horizontal to ensure proper operation.
  • Page 16: Suspension Points

    Series 85 Wall bracket, type 86044 Series 86 Tab. 7: Air-side accessories 6.3.2 Suspension points Fig. 3: Resistent suspension points I: Heat exchanger, galvanised steel II: Heat exchanger, stainless steel Unit heater series A [mm] Tab. 8: Suspension points for wall / ceiling installation...
  • Page 17: Universal 4-Point Brackets Type 80042

    Resistent Assembly, installation and operating instructions 6.3.3 Universal 4-point brackets type 80042 Fig. 4: Universal 4-point brackets, series 84-86 6.3.4 Wall brackets, type 8*044 Fig. 5: Wall brackets...
  • Page 18: Installation

    Resistent Assembly, installation and operating instructions Installation Actuator with ‘First Open’ function When delivered, the actuator is normally open in a de-energised state, thanks to the First Open function. This enables heating mode to run even if the electric wiring is not yet completed.
  • Page 19: Connection To The Pipe Network

    Important! Use an appropriate tool (e.g. pipe wrench) to prevent connection spigots from shearing off and twist- ing. All mechanical connections must be mounted stress-free! Heat exchanger, stainless Heat exchanger, galvanised steel, 1-layer steel, 1-layer Fig. 7: Resistent EX heat exchanger versions Series A [mm]...
  • Page 20: Electrical Connection

    85**58 50/60 0.39 1.74 <3.5 86**58 50/60 0.46 2.13 <3.5 Tab. 9: Electrical data Resistent, without KaControl and valve drive Type Number Speed controller, type 30510 Room thermostat, type 30155 Tab. 10: Maximum connectible Resistent with EC fan per speed control unit...
  • Page 21: Electromechanical Control Type 8***58

    (Contact C - NO open). The fault signalling chain in types 85xx58 and 86xx58 is protected by a relay with a unit fuse Ø5x20 mm, T0,1A. Fig. 8: Resistent with motor junction box...
  • Page 22 Resistent Assembly, installation and operating instructions...
  • Page 23 Resistent Assembly, installation and operating instructions...
  • Page 24 Resistent Assembly, installation and operating instructions Heating...
  • Page 25 Resistent Assembly, installation and operating instructions Heating...
  • Page 26 Resistent Assembly, installation and operating instructions Heating...
  • Page 27 Resistent Assembly, installation and operating instructions...
  • Page 28 Resistent Assembly, installation and operating instructions...
  • Page 29 Resistent Assembly, installation and operating instructions...
  • Page 30 Resistent Assembly, installation and operating instructions 2-pipe heating/cooling 2-pipe heating/cooling Unit 2 motor fault Contact open = fault Unit 2 speed (respect unit’s internal resistance!) Unit 1 motor fault Contact open = fault Unit 1 speed (respect unit’s internal resistance!)
  • Page 31: Pre-Commissioning Checks

    Resistent Assembly, installation and operating instructions Pre-commissioning checks Before initial commissioning, check whether all the necessary conditions have been met so that the unit can operate safely and properly. Structural tests Check that the unit is securely standing and fixed.
  • Page 32: Operation

    0 to 100 %, manual or automatic, 0-10 VDC, recirculation air, in- cluding sensor Suitable for: EC units, electromechanical, max. number of connectible units: ten TIP, TOP, Resistent, Ultra or Venkon, two KaCool D AF or KaCool W Fig. 10: Electronic fan speed controller type 30515...
  • Page 33: Maintenance

    Resistent Assembly, installation and operating instructions Maintenance 10.1 Securing against reconnection DANGER! Risk of death by unauthorised or uncontrolled restart! Unauthorised or uncontrolled restarting of the equipment can result in serious injury or death. Before restarting, ensure that all safety devices are fitted and working properly and that there is no haz- ard to humans.
  • Page 34: Clean The Inside Of The Unit

    Resistent Assembly, installation and operating instructions 10.3 Clean the inside of the unit Check all elements that come into contact with air (internal surfaces of the unit, outlet elements etc.) for dirt or deposits dur- ing maintenance and use a commercially available product to remove.
  • Page 35: Faults

    Resistent Assembly, installation and operating instructions Faults The following chapter describes possible causes of faults and the work needed to rectify them. Should faults occur frequently, shorten the maintenance intervals in line with the actual loading on the unit. Contact the manufacturer with any faults that cannot be rectified using the following information.
  • Page 36 Resistent Assembly, installation and operating instructions Status output via flash code The EC fans are blockage protected. Protective functions that trigger an automatic shut-off in case of a fault are integrated. These depend on the fan type. Viewing window for status LED Fig. 11: Flash code...
  • Page 37: Fault Table

    Resistent Assembly, installation and operating instructions 11.1 Fault table Fault Possible cause Remedy Check voltage, switch on repair switch. No function. No power supply. Replace fuse. Speed too high. Set a lower speed, if possible. Air inlet/outlet opening is obstructed.
  • Page 38: Certificates

    Resistent Assembly, installation and operating instructions Certificates EU-Konformitätserklärung EU Declaration of Conformity Déclaration de Conformité CE Deklaracja zgodności CE EU prohlášení o konformite KAMPMANN Wir (Name des Anbieters, Anschrift): GMBH & Co. KG Friedrich-Ebert-Str. 128-130 We (Supplier’s Name, Address): 49811 Lingen (Ems)
  • Page 39 Resistent Assembly, installation and operating instructions Gemäß den Bestimmungen der Richtlinien: Following the provisions of Directive: Conformément aux dispositions de Directive: Zgodnie z postanowieniami Dyrektywy: Odpovídající ustanovení směrnic: 2014/30/EU EMV-Richtlinie 2014/35/EU Niederspannungsrichtlinie Frank Bolkenius Lingen (Ems), den 29.04.2022 ______________________________ Ort und Datum der Ausstellung...
  • Page 40 Resistent Assembly, installation and operating instructions Table Tab. 1 Limits of operation ..............................7 Tab. 2 Maximum flow temperatures ..........................7 Tab. 3 Operating voltage ..............................7 Tab. 4 Water quality................................7 Tab. 5 Technical data for ..............................12 Tab. 6 Overview of types with minimum distances......................
  • Page 44 heaters/resistent...