This section describes how to troubleshoot a problem with the Rack Interface
Module or the I/O modules by using the information provided by the verification
screen, the LEDs, the System Event List, and the Alarm Event List. You can display
the verification screen and the two event lists by using the Rack Configuration
Software.
6.1 Verification
To perform the Rack Interface Module's verification:
1. Connect a computer running the Rack Configuration Software to the 3500 rack (if
needed).
2. Select Utilities from the main screen of the Rack Configuration Software.
3. Select Verification from the Utilities menu.
4. Select the Rack Interface Module and select the channel you want to verify.
5. Press the Verify button.
6. Select the Front Port or the Rear Port to get the status.
7. The Module OK State will show the Rack Interface Module's status and the
Channel OK State will show the channel's status.