20
|
Electrical installation
20.1.3 Guidelines when knocking out knockout holes
Installer and user reference guide
108
A
C
A Outdoor unit
B Indoor unit
C Central user interface (etc...)
a Main line
b1, b2, b3 Branch lines
c1, c2 No branch is allowed after branch
Example:
220-240 V
380-415 V
1~ 50 Hz
3N~ 50 Hz
a
b
c
V
Y
a Main switch
b Earth connection
c Power supply wiring (including earth) (EMC shielded cable)
F1/F2 Interconnection wiring (EMC shielded cable)
P1/P2 Remote controller wiring
V Outdoor unit (RXYSA4~6_V)
Y Outdoor unit (RXYSA4~6_Y)
d Indoor unit
e User interface
NOTICE
Precautions when making knockout holes:
▪
Avoid damaging the casing.
▪
After making the knockout holes, we recommend you remove the burrs and paint
the edges and areas around the edges using repair paint to prevent rusting.
▪
When passing electrical wiring through the knockout holes, wrap the wiring with
protective tape to prevent damage.
b1
b2
c1
b3
c2
a
B
220-240 V
1~ 50 Hz
F1/F2
(16 V)
d
P1/P2
(16 V)
e
RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02