18.2.8 To connect the refrigerant branching kit

RXYSA4~6A7V/Y1B
VRV 5-S system air conditioner
4P600330-1D – 2023.02
NOTICE
When brazing: First braze the liquid side piping, then the gas side piping. Enter the
filler rod from the front of the unit and the brazing torch from the right side to braze
with the flame pointing outside. Avoid heating the compressor sound insulation and
other piping.
Wrap both stop valves in a wet cloth in order to protect the valve internals from
overheating.
A
a
b
a Filler rod
b Fire resistant plate
c Torch
d Flame
e Compressor sound insulation
f Liquid side piping
g Gas side piping
4 Connect the field piping to the accessory pipes using the accessory bend pipes
(brazing). Mind the orientation of the bends.
NOTICE
Always protect the surrounding surfaces (e.g. wiring, insulation foam, ...) from heat
when brazing.
NOTICE
Make sure to open the stop valves after installing the refrigerant piping and
performing vacuum drying. Running the system with the stop valves closed may
break the compressor.
For installation of the refrigerant branching kit, refer to the installation manual
delivered with the kit.
Mount the refnet joint so that it branches either horizontally or vertically.
Mount the refnet header so that it branches horizontally.
b
A
B
A
e
d
a
b f
g
c
c
d
a
a
18
Piping installation
|
c
Installer and user reference guide
91