● The addresses of all T/H sensors are 1 by default.
● After the addresses are set, power on the device, choose Settings > System
Settings > T/H sensor on the home screen of the display module, and set the
sensors in the aisles corresponding to the addresses to Enable. Otherwise, the
sensors will not work.
● If the T/H sensor provided uses an eight-bit DIP switch, bits 1 to 6 of the DIP
switch are used to set the device address, bit 7 is reserved, and bit 8 is used to
switch the temperature display mode.
----End
4.12 Removing the Transport Fasteners and Protective
Covers
Procedure
Step 1 Open the No. 2 maintenance door. Loosen the three bolts on the compressor
transport fasteners using a 13# solid wrench.
Figure 4-45 Removing the transport fasteners from the compressor
Issue 10 (2024-01-30)
Display Name
Hot aisle 6
temp/humid
NO TICE
NO TE
● Do not remove the bolts directly.
● Put away the removed transport fasteners so that you can reinstall them if the indoor
unit is to be transported again in the container scenario.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Add
DIP Switch Sequence No.
ress
1
2
26
OFF
ON
4 Installation Guide
3
4
5
OFF
ON
ON
6
OFF
82