Connecting The Device; Notes On Connection - Siemens IFP V2 UL Operating Manual

Table of Contents

Advertisement

Wall mounting
Fasten the Transceiver Unit to a wall with two M4 screws via the two elongated holes of the
mounting rail.
NOTICE
Sufficient carrying capacity of the wall is required.
If the wall does not have a sufficient load-bearing capacity, the device may fall and be
damaged.
Ensure that the wall can bear four times the total weight of the device, including mounting
material.
NOTICE
Mounting material
If you use anchors and screws other than those specified below for wall mounting, safe
mounting is not guaranteed. The device can fall and may be damaged.
Use only the anchors and screws specified in the following table.
Wall material
Concrete
Plasterboard, at least 13 mm
thick
Metal, at least 2 mm thick
3.5

Connecting the device

3.5.1

Notes on connection

Requirement
• The device has been installed according to the information provided in these operating
instructions.
IFP V2 UL hazardous information
Operating Manual, 11/2023
Hole diameter
Select based on the
specifications for the
mounting material used
Installing and connecting the device
3.5 Connecting the device
Mounting material
Anchor, ∅ 6 mm, 40 mm long
Screw, ∅ 4 mm, 40 mm long
Toggle plug, ∅ 12 mm, 50 mm
long
Screw M4 × 15
M4 nut
31