Chilled Water Operation Limits And Performance - LG KCHH Series Installation Manual

Air-cooled inverter scroll heat pump chillers
Table of Contents

Advertisement

CHILLED WATER OPERATION LIMITS AND
KCHH Chilled Water Operation Limits and Performance
105
95
85
75
65
55
45
35
25
15
5
5
15
Cold Water Inlet
Temperature F
Cold Water Outlet
Temperature F
Ambient Range
Approved Δ between EWT and LWT is 4°F to 20°F
25
35
45
55
Ambient Air Degrees F
18°F to 97°F
14°F to 77°F
5°F to 125°F
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
PERFORMANCE
65
75
85
1. Proper Glycol Solution is required for LWT at
or below 32°F.
2. Proper Glycol Solution Evaluation is
Required in Ambient Conditions below 41°F
3. Ambient Air Operation Limits: 208-230V
is 122°F and 460V is 125°F.
4. LG LATS ISC Selection Software is to be used to
confirm selection and performance.
95
105
115
125
31

Advertisement