ERROR CODE TABLES
Error code
Surge in inverter #1,#2 compressor discharge temperature
CHxx032
Stop applicable cycle
Surge in high pressure
CHxx034
Surge in high pressure side
Stop applicable cycle
Surge in low pressure
CHxx035
Drop in low pressure side
Stop applicable cycle
Low compression rate error
CHxx036
Low compression rate error
Stop applicable cycle
Inverter compressor CT sensor error
CHxx040
Inverter compressor CT sensor is short/open
Stop applicable cycle
Inverter compressor discharge temperature sensor error
CHxx041
Inverter compressor discharge temperature sensor is short/open
Stop applicable cycle
Low pressure sensor error
CHxx042
Low pressure sensor is short/open
Stop applicable cycle
High pressure sensor error
CHxx043
High pressure sensor is short/open
Stop applicable cycle
Heat exchanger temperature sensor error
CHxx045
Heat exchanger temperature sensor is short/open
Stop applicable cycle
144
Control during error
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Error name
Error condition
Release condition
Automatically return to normal condition
Automatically return to normal condition
Automatically return to normal condition
Automatically return to normal condition
Automatically return to normal condition
Automatically return to normal condition
Automatically return to normal condition
Automatically return to normal condition
Automatically return to normal condition

Advertisement

Table of Contents
loading

Table of Contents