HMI SCREENS
How to connect the flow rate sensor
• You can check the current flow and set the minimum/maximum flow rate by connecting a flow
sensor to the product.
• Connect the flow rate sensor to UI2,G.
In case of interface control, if you select setting 2 on the device mode screen, the following
screen appears.
• Set the Flow sensor Usage to 'Use', and select the flow rate display unit (GPM or LPM) and
flow rate range (Min/Max Flow rate).
(The Min flow rate must be lower than The Max flow rate, So be careful when you changing
the setting.)
• You can check the current flow in System Information.
CAUTION
!
• Use a flow sensor with a voltage of 0.5~10 V.
• We are not responsible for abnormal operation of the flow rate sensor and error range of
the flow rate range during installation on site.