General Information - Nibe ClimateMaster Tranquility 30(SE) Series Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

TranquiliTy® 30 (SE) PrEMiEr TWO-STaGE SEriES– iOM
Models:
SE

General Information

024-072
INSPECTION
Upon receipt of the equipment, carefully check the
shipment against the bill of lading. Make sure all units
have been received. Inspect the packaging of each
unit and inspect each unit for damage. Ensure that
the carrier makes proper notation of any shortages or
damage on all copies of the freight bill and completes
a common carrier inspection report. Concealed
damage not discovered during unloading must
be reported to the carrier within 15 days of receipt
of shipment. If not filed within 15 days, the freight
company can deny the claim without recourse.
NOTE: It is the responsibility of the purchaser to file all
necessary claims with the carrier. Notify your equipment
supplier of all damage within 15 days of shipment.
STORAGE
Equipment should be stored in its original packaging
in a clean, dry area. Store units in an upright position
at all times. You may stack vertical configurations
a maximum of two units high and horizontal
configurations a maximum of three units high.
UNIT PROTECTION
Cover units on the job site with either the original
packaging or an equivalent protective covering.
Cap the open ends of pipes stored on the job site.
In areas where painting, plastering, or spraying has
not been completed, all necessary precautions must
be taken to avoid physical damage to the units and
contamination by foreign material. Physical damage
and contamination may prevent proper startup and
may result in costly equipment clean-up.
Examine all pipes, fittings, and valves before
installing any of the system components. Remove
any dirt or debris found in or on these components.
PA G E : 6
C r e a t e d : M a r c h 6 , 2 0 2 4
PRE-INSTALLATION
Installation, Operation, and Maintenance instructions
are provided with each unit. Horizontal equipment
is designed for installation above false ceiling or in a
ceiling plenum. Other unit configurations are typically
installed in a mechanical room. The installation site
chosen should include adequate service clearance
around the unit. Before unit startup, read all manuals
and become familiar with the unit and its operation.
Thoroughly check the system before operation.
PREPARE UNITS FOR
INSTALLATION AS FOLLOWS:
1.
Compare the electrical data on the unit
nameplate with ordering and shipping
information to verify that the correct unit has
been shipped.
2. Keep the cabinet covered with the original
packaging until installation is complete and all
plastering, painting, etc. is finished.
3.
Verify refrigerant tubing is free of kinks or dents
and that it does not touch other unit components.
4. Inspect all electrical connections. Connections
must be clean and tight at the terminals.
5. Remove any blower support packaging
(water-to-air units only).
6. Some airflow patterns are field convertible
(horizontal units only). Locate the airflow
conversion section of this IOM.
7.
Locate and verify any hot water generator
(HWG), hanger, or other accessory kit located in
the compressor section or blower section.
CHECKS TO THE AREA
Prior to beginning work on systems containing
FLAMMABLE REFRIGERANTS, safety checks are
necessary to ensure that the risk of ignition
is minimized. For repair to the REFRIGERATING
SYSTEM, these steps shall be completed prior to
conducting work on the system.
w w w. c l i m a t e m a s t e r. c o m

Advertisement

Table of Contents
loading

Table of Contents