Electrical Data: (Cv) Ec Blower Motor - Nibe ClimateMaster Tranquility 30(SE) Series Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

TranquiliTy® 30 (SE) PrEMiEr TWO-STaGE SEriES– iOM

Electrical Data: (CV) EC Blower Motor

Models:
SE
Standard Unit
024-072
VOLTAGE
MODEL
CODE
SE*024
SE*036
SE*048
SE*060
SE*072
Notes:
Wire length based on one way measurement with 2% voltage drop.
z
Wire size based on 60°C copper conductor.
z
All fuses Class RK-5.
z
*NEUTRAL CONNECTION REQUIRED! All F and L voltage (460VAC) units with EC motor require four wire power supply with
neutral. EC motor is rated 265VAC and is wired between one hot leg and neutral.
PA G E : 3 6
C r e a t e d : M a r c h 6 , 2 0 2 4
VOLTAGE
VOLTAGE
MIN/MAX
G.J.
208/230-1-60
187.0/252.0
H.K.
208/230-3-60
187.0/252.0
F.L.
460-3-60*
432.0/504.0
G.J.
208/230-1-60
187.0/252.0
H.K.
208/230-3-60
187.0/252.0
F.L.
460-3-60*
432.0/504.0
G.J.
208/230-1-60
187.0/252.0
H.K.
208/230-3-60
187.0/252.0
F.L.
460-3-60*
432.0/504.0
G.J.
208/230-1-60
187.0/252.0
H.K.
208/230-3-60
187.0/252.0
F.L.
460-3-60*
432.0/504.0
G.J.
208/230-1-60
187.0/252.0
H.K.
208/230-3-60
187.0/252.0
F.L.
460-3-60*
432.0/504.0
FAN
TOTAL
COMPRESSOR
MOTOR
UNIT
QTY RLA
LRA
FLA
FLA
1
10.3
62
4.2
14.50
1
6.3
56
4.2
10.50
1
3.8
29
3.4
7.20
1
14.6
76
5.9
20.50
1
8.6
70
5.9
14.50
1
4.5
39
4.8
9.30
1
18.3
138
5.9
24.20
1
11.2
112
5.9
17.10
1
6.8
61.8
4.8
11.60
1
22.3
149
7.5
29.80
1
14
150
7.5
21.50
1
6.3
58
6.2
12.50
1
31.2
166
7.5
38.70
1
14
150
7.5
21.50
1
6.3
58
6.2
12.50
MIN
FUSE/
CIRCUIT
HACR
AMP
AMP
17.10
25
12.10
15
8.20
15
24.20
30
16.70
20
10.40
15
28.80
45
19.90
30
13.30
15
35.40
50
25.00
30
14.10
15
46.50
70
25.00
30
14.10
15