Startup Log Sheet - Nibe ClimateMaster Tranquility 30(SE) Series Installation, Operation & Maintenance Manual

Table of Contents

Advertisement

TranquiliTy® 30 (SE) PrEMiEr TWO-STaGE SEriES– iOM
Models:
SE

Startup Log Sheet

024-072
Installer: Complete Unit and System Checkout and follow Unit Startup Procedures in the IOM. Use this
form to record unit information, temperatures, and pressures during startup. Keep this form for reference.
Job Name:
Street Address:
Model Number:
Unit Location in Building:
Date:
In order to minimize troubleshooting and costly system failures, complete the following checks and data
entries before the system is put into full operation.
Fan Motor
CV EC
Temperatures (check one):
Pressures (check one):
Entering Fluid Temperature
Leaving Fluid Temperature
Fluid Temperature Differential
Return-Air Temperature
Supply-Air Temperature
Air Temperature Differential
Water Coil Heat Exchanger
(Water Pressure IN)
Water Coil Heat Exchanger
(Water Pressure OUT)
Pressure Differential
Flow Rate GPM (l/s)
Compressor
Amps
Volts
Discharge Line Temperature
Motor
Amps
Volts
NOTES:
1.
Allow unit to run 15 minutes in each mode before taking data.
2.
Never connect refrigerant gauges during startup procedures.
3.
Conduct water-side analysis using P/T ports to determine water fl ow and temperature difference.
4.
If water-side analysis shows poor performance, refrigerant troubleshooting may be required.
5.
Connect refrigerant gauges as a last resort.
PA G E : 6 4
C r e a t e d : M a r c h 6 , 2 0 2 4
7300 S.W. 44th Street, Oklahoma City, OK 73179 • Phone:
Description
CFM Setting
°F
°C
Antifreeze:
PSIG
kPa
Type:
Cooling Mode
DB
DB
Startup Log Sheet
Small Packaged Units
Serial Number:
Sales Order Number:
Value
%
WB
WB
Models:
Ty, TZ
1-800-299-9747
Heating Mode
DB
DB
w w w. c l i m a t e m a s t e r. c o m