4 INSTALLATION
1.
Rating plate with supply
connection data
4.5

Recommended fuse sizes and minimum cable area for

Rebel EMP 205ic AC/DC
WARNING!
An electrical shock or fire hazard is probable if the following electrical service guide
recommendations are not followed. These recommendations are for a dedicated
branch circuit sized for the rated output and duty cycle of the welding power source.
CAUTION!
Disconnect input power and secure employing 'Lock-out/Tagging' procedures.
Ensure input power line disconnect switch is locked (Lock-out/Tagging) in the 'Open'
position BEFORE removing input power fuses. Connecting/disconnecting should be
carried out by competent persons.
Supply voltage
Maximum current rating (I
MMA/Stick/SMAW
Maximum effective supply current (I
MMA / Stick / SMAW
Maximum recommended fuse* or circuit breaker
rating
*Time delay fuse UL class RK5, refer to UL 248
Maximum recommended fuse* or circuit breaker
rating
Normal operating UL class K5, refer to UL 248
Mains supply cable
Maximum recommended extension cord length
Minimum recommended grounding conductor
size
0463 652 101
Rebel EMP 205ic AC/DC
)
1max
)
1eff
- 19 -
120 V AC 1 P -
50/60 Hz
30 A
15.2 A
30 A
50 A
2
13 AWG (2.5 mm
) 13 AWG (2.5 mm
25 ft (8 m)
2
13 AWG (2.5 mm
) 13 AWG (2.5 mm
230 V AC 1 P -
50/60 Hz
33 A
15.12 A
40 A
50 A
2
)
50 ft (15 m)
2
)
© ESAB AB 2024