11. PRINTER FUNCTIONS
MELSEC-A
(1)
Designating the message data length
The following explains the method and gives an example showing the
-
~
designation of a message data length.
esignation method
I
b15
to
b O
Write the number of characters of the fixed message
to
be registered.
POINT
I
Set the message data length i n the following range:
I
.
0 <number of characters s 80
besignation example
To set a fixed message length at 14 characters (AlSJ71C24-PRF I10 addresses: 20H to
3FH).
(Sequence program)
I-+
l r 1
TOP
I
ti2
I
HBAO
1
K14
I
K1
'14' is written to buffer address 8AOH.